Plan Review Details - Permit 11110659
Plan Review Stops For Permit 11110659
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-03 Cont ID  
Sent By jwitmer Date 2012-01-03 Time 13:01 Rev Time 0.66
Received By jwitmer Date 2012-01-03 Time 12:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By jwitmer Date 2011-12-01 Time 11:42 Rev Time 0.99
Received By jwitmer Date 2011-11-30 Time 16:46 Sent To  
Notes
2011-12-01 12:03:48BUILDING PLAN REVIEW
 PERMIT: 11110659
 ADD: 5335 N MILITARY TRL. # 15/16
 CONT: AMERICAN FOUNDATION
 TEL: (305)887-1221
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) SHEET # 1 CODE SUMMARY LIST THE OCCUPANCY TYPE AS
 MERCANTILE (FBC-B 304.1- BUSINESS) AND THEN THE
 OCCUPANT LOAD IS FIGURED AT 100 SQ /OCCUPANT WHICH IS
 BUSINESS WHICH IS CORRECT, BUT THE OCCUPANT LOAD WOULD
 BE 31 NOT 30.
  
 1B) SHEET # 1 THE FIXTURE COUNT IS FIGURED AS
 MERCANTILE NOT BUSINESS.
  
 2) SHEET # 2 INDICATES THE USE OF (2) NEW EXTERIOR
 LOUVERS WILL NEED PRODUCT APPROVALS FOR LOUVERS.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4)MISSING WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 1.THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2. AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3. AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4. A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 5. 2007/09 FBC-B 1603.1.4 (5) WIND DESIGN CRITERIA:
 PRESSURES FOR COMPONENTS AND CLADDING .
  
 5) SHEET # 3 VIEW "E" PLEASE PROVIDE COMPLIANCE FOR
 FBC-B 11-4.27.3 & 11-4.27.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-13 Cont ID  
Sent By rlecky Date 2011-12-13 Time 17:46 Rev Time 0.00
Received By rlecky Date 2011-12-13 Time 17:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-12-02 Cont ID  
Sent By wjolin Date 2011-12-02 Time 09:57 Rev Time 0.00
Received By wjolin Date 2011-12-01 Time 15:00 Sent To  
Notes
2011-12-02 09:56:285335 NORTH MILITARY TRAIL - SUITE #15/#16
 PERMIT #11110659
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT ONCE OTHER PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By lwagner Date 2011-12-28 Time 15:07 Rev Time 0.00
Received By lwagner Date 2011-12-28 Time 15:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2011-12-15 Cont ID  
Sent By lwagner Date 2011-12-15 Time 10:18 Rev Time 0.00
Received By lwagner Date 2011-12-15 Time 08:43 Sent To  
Notes
2011-12-15 08:55:56FBC 2007 GAS REVIEW:
  
 PLEASE INCLUDE THE FOLLOWING ON THE GAS PLAN:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 PLEASE INCLUDE A DETAIL FOR THE 2 POUND TO 1/2 POUND
 REGULATOR/S THAT WILL BE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-03 Cont ID  
Sent By jwitmer Date 2012-01-03 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2011-12-27 Time 11:30 Sent To  
Notes
2011-12-28 11:30:38GAVE TO LARRY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-27 Cont ID  
Sent By shill Date 2011-12-21 Time 11:22 Rev Time 0.00
Received By shill Date 2011-11-30 Time 12:19 Sent To  
Notes
2011-11-30 12:20:07***************EXPEDITED****************
 B-16

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By lwagner Date 2011-12-28 Time 14:54 Rev Time 0.00
Received By lwagner Date 2011-12-28 Time 13:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-12-15 Cont ID  
Sent By lwagner Date 2011-12-15 Time 10:15 Rev Time 0.00
Received By lwagner Date 2011-12-14 Time 14:30 Sent To  
Notes
2011-12-14 15:24:45FBC 2007 PLUMBING:
  
 1. PAGE 6 - VENTS WILL BE REQUIRED FOR THE SANITARY
 ISOMETRIC DRAWING. THE RUNOUTS ARE CONSIDERED A
 COMBINATION DRAIN AND VENT SYSTEM.
 912.2.2 CONNECTION. THE COMBINATION DRAIN AND VENT
 SYSTEM SHALL BE PROVIDED WITH A DRY VENT CONNECTED AT
 ANY POINT WITHIN THE SYSTEM OR THE SYSTEM SHALL CONNECT
 TO A HORIZONTAL DRAIN THAT IS VENTED IN ACCORDANCE WITH
 ONE OF THE VENTING METHODS SPECIFIED IN THIS CHAPTER.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-12-21 Cont ID  
Sent By lfranco Date 2011-12-21 Time 20:04 Rev Time 0.50
Received By lfranco Date 2011-12-21 Time 20:04 Sent To  
Notes
2011-12-21 20:05:21PLANNING: ***** ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE. ******