Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-21 Cont ID  
Sent By jwitmer Date 2011-12-19 Time 15:18 Rev Time 0.00
Received By jwitmer Date 2011-12-19 Time 11:52 Sent To  
Notes
2011-12-19 11:53:16BUILDING PROVISO:
 2007/09 FBC-B 712.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER
 WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION.
 SUCH IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS:
 "FIRE AND SMOKE BARRIER - PROTECT ALL OPENINGS."

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-29 Cont ID  
Sent By jwitmer Date 2011-11-29 Time 09:14 Rev Time 0.77
Received By jwitmer Date 2011-11-29 Time 09:14 Sent To  
Notes
2011-11-29 09:15:36BUILDING PLAN REVIEW
 PERMIT: 11110630
 ADD: 330 CLEMATIS ST SUITE 118
 CONT: MUNNA CONTRACTING & DEVELOPMENT
 TEL: (561)371-7677
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES WITH A NOTE DETAIL # 3 TO BE A
 1-HOUR TENANT SEPERATION WALL TO DECK ABOVE BUT THERE
 IS NO SUCH DETAIL.
  
 2) PLEASE PROVIDE THE FOLLOWING NOTATION ABOVE THE
 CEILING ON RATED WALLS: "FIRE AND SMOKE BARRIER -
 PROTECT ALL OPENINGS." 712.6 FIRE WALLS, FIRE BARRIERS,
 FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR
 ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDENTIFICATION
 SHALL BE ABOVE ANY DECORATIVE CEILING AND IN CONCEALED
 SPACES.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-05 Cont ID  
Sent By rlecky Date 2011-12-05 Time 13:50 Rev Time 0.00
Received By rlecky Date 2011-12-05 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-12-21 Cont ID  
Sent By jwitmer Date 2011-12-21 Time 15:18 Rev Time 0.00
Received By jwitmer Date 2011-12-21 Time 15:18 Sent To  
Notes
2011-12-21 15:18:54SEE FIRE APPROVAL UNDER MASTER 11110361

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-30 Cont ID  
Sent By wjolin Date 2011-11-30 Time 11:08 Rev Time 0.00
Received By wjolin Date 2011-11-30 Time 11:08 Sent To  
Notes
2011-11-30 11:08:41330 CLEMATIS STREET - SUITE #118
 PERMIT #11110630
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE SUITE NUMBER IN ADDRESS TITLEBLOCK.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. PENETRATIONS THROUGH A FIRE-RATED WALL
 ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR
 DEVICE.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 MODIFICATIONS SHOWN ON THE PLANS WILL AFFECT THE
 EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEM. SEPARATE
 PLANS AND PERMITS ARE REQUIRED FOR THE MODIFICATION OF
 THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM. THE
 PLANS ONLY INDICATE ONE FIRE ALARM STROBE APPLIANCE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-19 Cont ID  
Sent By hmoser Date 2011-12-14 Time 12:30 Rev Time 0.00
Received By shill Date 2011-11-16 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-12-19 Cont ID  
Sent By hmoser Date 2011-12-19 Time 12:30 Rev Time 0.00
Received By hmoser Date 2011-12-19 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-21 Cont ID  
Sent By jwitmer Date 2011-12-21 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2011-12-21 Time 15:19 Sent To  
Notes
2011-12-21 15:19:36SEE APPROVAL UNDER MASTER 11110361

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-12-02 Cont ID  
Sent By lwagner Date 2011-12-02 Time 14:31 Rev Time 0.00
Received By lwagner Date 2011-12-02 Time 14:31 Sent To  
Notes
2011-12-02 14:32:36SEE NOTES FOR MASTER #11110361

Review Stop Z ZONING
Rev No 1 Status P Date 2011-12-07 Cont ID  
Sent By aaponte Date 2011-12-07 Time 16:25 Rev Time 0.00
Received By aaponte Date 2011-12-07 Time 16:25 Sent To  
Notes
2011-12-07 16:26:03PROVISO:
 1. ACCORDING TO SECTION 94-105 (D)(1)D - ALONG CLEMATIS
 STREET, RETAIL USES SHALL OCCUPY THE MINIMUM REQUIRED
 ACTIVE USE LINER DEPTH OF 25 FEET. MERCHANDISE OR FOOD
 SALES SHALL REPRESENT A MINIMUM OF 50% OF BUSINESS
 REVENUE AT REQUIRED RETAIL FRONTAGES.
 2. NO RETAIL USES MAY OCCUPY THE SPACE BEHIND THE
 MINIMUM 25 FEET ACTIVE USE LINER, BUT RETAIL SPACE
 SHALL BE SEPARATED FROM THE OTHER USES BY A DEMISING
 WALL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE