Plan Review Details - Permit 11110625
Plan Review Stops For Permit 11110625
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-29 Cont ID  
Sent By jwitmer Date 2011-12-29 Time 11:23 Rev Time 0.00
Received By jwitmer Date 2011-12-29 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-30 Cont ID  
Sent By jwitmer Date 2011-11-30 Time 15:40 Rev Time 0.77
Received By jwitmer Date 2011-11-30 Time 15:31 Sent To  
Notes
2011-11-30 16:07:43BUILDING PLAN REVIEW
 PERMIT: 11110625
 ADD: 3720 S DIXIE HWY SUITE B
 CONT: FOX VALLEY BUILDING CORP
 TEL: (561)282-8281
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW THE PERMIT APPLICATION ADDRESS FIELD
 AND PLANS. BOTH INDICATE THE JOB LOCATION TO BE AT 3720
 N DIXIE WHILE THE PROPERTY CONTROL NUMBER SUBMITTED IS
 FOR 3720 S DIXIE? 106.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) THE SECOND ISSUE IS THIS A SINGLE TENANT SPACE FOR
 TWO TENANTCIES? PLEASE PROVIDE IF TWO SEPERATE
 TENANTCIES WHAT TYPE OF BUSINESSES WILL BE IN EACH,
 DEPENDING ON THIS INFORMATION EITHER TENANT SEPERATION
 WALLS MAY BE REQUIRED PER SECTION FBC-B 708.1 OR
 OCCUPANCY SEPERATION WALLS PER FBC-B TABLE 508.3.3.
  
 3) IF THIS RECONFIGURATION OF SPACE IS TWO SEPERATE
 TENANTS THEN THE TENANT SEPERATION WALL SHOULD CONTINUE
 TO THE ROOF DECK ABOVE. FBC-B 708.1.
  
 4) THE PLANS ALSO INDICATE BY DETAIL THE NEW SECTION OF
 INTERIOR WALL, PLEASE REVIEW CEILING INSULATION CAN NOT
 LAY ON THE DROP IN CEILING TILE. FBC-B 13.404.AB.1.
  
 5A) THE PLANS DO HAVE TWO BUILDING VIOLATIONS THE
 KITHEN DOOR BLOCKS EGRESS WITHIN THIC CORRIDOR.
 FBC-B1008.1.8.8.
  
 5B) THE PLANS ALSO SHOW THE DOUBLE DOORS AT THE
 VESTIBULE ENTRY BEING BLOCKED BY THE SWING OF A ENTRY
 DOOR INTO THE NEWLY FORMED SPACE.
  
 6) MAY REQUIRE: BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-01-04 Cont ID  
Sent By rlecky Date 2012-01-04 Time 10:01 Rev Time 0.00
Received By rlecky Date 2012-01-04 Time 10:01 Sent To  
Notes
2012-01-04 10:02:12PLAN NOTE:
  
 ELECTRICAL PERMIT REQUIRED FOR NEW OUTLETS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-13 Cont ID  
Sent By rlecky Date 2011-12-13 Time 18:26 Rev Time 0.00
Received By rlecky Date 2011-12-13 Time 18:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-12-19 Cont ID  
Sent By wjolin Date 2011-12-19 Time 14:33 Rev Time 0.00
Received By wjolin Date 2011-12-19 Time 13:56 Sent To  
Notes
2011-12-19 14:33:143720 SOUTH DIXIE HIGHWAY - SUITE B
 PERMIT #11110625
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-30 Cont ID  
Sent By wjolin Date 2011-11-30 Time 14:20 Rev Time 0.00
Received By wjolin Date 2011-11-30 Time 13:40 Sent To  
Notes
2011-11-30 14:20:163720 SOUTH DIXIE HIGHWAY - SUITE B
 PERMIT #11110625
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS ON THE PERMIT APPLICATION AND DRAWINGS
 INDICATE "NORTH DIXIE HIGHWAY."
  
 THIS WALL APPEARS TO BE A TENANT SEPARATION WALL THAT
 WOULD NEED TO HAVE A FIRE RATING OF AT LEAST ONE-HOUR.
 SEPARATED MULTI-USE OCCUPANCIES WOULD NEED TO HAVE A
 TWO-HOUR FIRE RATED SEPARATION BETWEEN A MERCANTILE
 OCCUPANCY AND A BUSINESS OCCUPANCY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-04 Cont ID  
Sent By rlecky Date 2012-01-04 Time 10:02 Rev Time 0.00
Received By rlecky Date 2011-12-15 Time 17:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-15 Cont ID  
Sent By shill Date 2011-12-13 Time 17:10 Rev Time 0.00
Received By shill Date 2011-11-28 Time 08:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-12-05 Cont ID  
Sent By eschneid Date 2011-12-05 Time 13:57 Rev Time 0.25
Received By eschneid Date 2011-12-05 Time 13:50 Sent To  
Notes
2011-12-05 14:05:02INTERIOR WORK ONLY, LESS THEN 50% VALUE.
  
 NOTE - ADDRESS ON PERMIT AND TITLE BLOCK SHALL BE
 CORRECTED TO 3720 S. DIXIE.