Plan Review Details - Permit 11110560
Plan Review Stops For Permit 11110560
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-01-06 Cont ID  
Sent By jgomez Date 2012-01-06 Time 17:43 Rev Time 0.00
Received By jgomez Date 2012-01-06 Time 17:43 Sent To  
Notes
2012-01-06 17:45:01BUILDING REVISION COMMENTS:
  
 1- A) LOAD SCHEDULE INFORMATION ON SHEET C-1 AND LOAD
 SCHEDULE INFORMATION ON THE TRUSS DRAWINGS SUBMITTED
 DON'T MATCH. PLEASE COORDINATE INFORMATION. LIVE LOAD
 SPECIFICATIONS AND DEAD LOAD SPECIFICATIONS DON'T
 MATCH. REVISE AS REQUIRED TO MATCH.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 2- PLEASE PROVIDE REVISED PLUMBING RISER DIAGRAM THAT
 MATCHES FLOOR PLAN. DIAGRAM SUBMITTED IS MISSING THE
 KITCHEN ISLAND SINK AND THE KITCHEN SINK IS A DOUBLE
 SINK NOT SINGLE. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-30 Cont ID  
Sent By jgomez Date 2011-11-30 Time 15:16 Rev Time 0.00
Received By jgomez Date 2011-11-30 Time 15:16 Sent To  
Notes
2011-11-30 16:12:52BUILDING REVISION COMMENTS:
  
 1- LOAD SCHEDULE INFORMATION ON SHEET C-1 AND LOAD
 SCHEDULE INFORMATION ON THE TRUSS DRAWINGS DON'T MATCH.
 PLEASE COORDINATE INFORMATION. NOTE: LOADS NEED TO
 COMPLY WITH TABLE R301.5 INCLUDING THE LIVE LOADS FOR
 LIMITED STORAGE. PLEASE, SHOW THAT TRUSSES FOR LIMITED
 STORAGE AT GARAGE AREA ARE DESIGNED FOR THE 20PSF LIVE
 LOAD AS REQUIRED BY TABLE R301.5.
  
 2- PLEASE PROVIDE COMPLETE INFORMATION FOR SCREEN
 ENCLOSURE ON COVERED PATIO #2 UNDER A SEPARATE PERMIT.
 NO INFORMATION WAS SUBMITTED YET.
  
 3- PLEASE PROVIDE REVISED PLUMBING RISER DIAGRAM TO
 INCLUDE THE NEW SINK SHOWN ON COVERED PATIO #2.
  
 4- A) PROVIDE COMPLETE ICYNENE SPECIFICATIONS AS
 SPECIFIED ON PLANS.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 THIS SPECIFICATIONS. SEC. 106.3.3 CITY AMENDMENTS.
  
 5- A) PLEASE REVISE THE ENERGY CALCULATIONS. REVISE THE
 CEILING R VALUE ON ITEM #10. NEED R-19 MINIMUM AS
 REQUIRED BY SEC. N1104.AB.1. NOTE: UNVENTED ATTIC AND
 R-INSULATION ARE TWO DIFFERENT THINGS. CEILING
 INSULATION IS ALWAYS REQUIRED.
  
 B) OWNER/AGENT TO SIGN AND DATE THE BOTTOM OF THE FORM
 ALSO.
  
 6- PLEASE ADDRESS ZONING COMMENTS NOTED ON REVISION
 #11080512 TO AVOID ANY CONFLICTS OR DELAYS. CONTACT
 LINDA FRANCO AT (561)822-1443.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-06 Cont ID  
Sent By jgomez Date 2012-01-06 Time 17:43 Rev Time 0.00
Received By jgomez Date 2011-12-21 Time 11:30 Sent To  
Notes
2011-12-21 11:30:45IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-30 Cont ID  
Sent By jgomez Date 2011-11-30 Time 15:16 Rev Time 0.00
Received By jgomez Date 2011-11-22 Time 16:22 Sent To  
Notes
2011-11-28 16:22:18SENT TO JULIO'S DESK. JG.