Plan Review Details - Permit 11110506
Plan Review Stops For Permit 11110506
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-02-03 Cont ID  
Sent By jgomez Date 2012-02-03 Time 11:04 Rev Time 0.00
Received By jgomez Date 2012-02-03 Time 08:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-01-20 Cont ID  
Sent By jgomez Date 2012-01-19 Time 16:04 Rev Time 0.00
Received By jgomez Date 2012-01-19 Time 16:04 Sent To  
Notes
2012-01-19 16:07:22RE-SUBMITTAL BUILDING REVIEW COMMENTS.
  
 1- SHEET #6.0: WHAT'S "FAST DRY TFS INSULATION" THAT
 WAS SPECIFIED FOR THE CEILING INSULATION. PROVIDE
 MANUFACTURER SPECIFICATIONS. INSULATION NEED TO COMPLY
 WITH SEC. R316.
  
 2- REVISE THE ENERGY CALCULATIONS:
 A) INFORMATION ON ITEM #6A WAS NOT ENTERED. THIS
 INFORMATION IS REQUIRED.
  
 B) INFORMATION ON ITEM #6B NEED TO BE REVISED. THE
 VALUE FOR THE SHGC NEEDS TO BE THE SAME VALUE AS SHOWN
 ON TABLE 11B-1 (0.35) ON SECOND PAGE OR BETTER.
 INFORMATION SUBMITTED SHOWS .78. THE LOWER THE NUMBER
 THE BETTER PERFORMANCE. REVISE AS REQUIRED.
  
 C) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM
 ALSO.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-07 Cont ID  
Sent By jgomez Date 2011-12-07 Time 13:31 Rev Time 0.00
Received By jgomez Date 2011-12-07 Time 10:28 Sent To  
Notes
2011-12-07 13:34:11RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLEASE TAKE DRAWINGS TO THE PALM BEACH COUNTY
 BUILDING (2300 N. JOG RD.) TO CHECK IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 2- PLEASE PROVIDE PRODUCT APPROVALS (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. SINGLE HUNG NOA 07-0717.05
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. PLEASE VISIT
 THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL COMPONENTS SPECIFIED BY THE
 ENGINEER ON THE SECTIONS AND DETAILS.
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE CONNECTOR. OR, ENGINEER MAY
 SPECIFY PRODUCT APPROVAL NUMBER (2007 CODE VERSION) ON
 DRAWINGS SUBMITTED.
  
 3-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, AND ENGINEER FEES. PLEASE UPDATE
 VALUATION AS REQUIRED.
  
 5- PLEASE, PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY CHAPTER 713 FLORIDA STATUTES.
  
 6- SHEET 2.0:
 A) WINDOW SCHEDULE CALLS WINDOW NO 1 TO BE SH-24.
 ACCORDING TO THE WIDTH & HEIGHT SPECIFIED THE CORRECT
 WINDOW TYPE IS SH25. PLEASE REVISE AS REQUIRED.
  
 B) R-19 INSULATION DOESN'T FIT IN A 2X4 WALL. REVISE
 WALL LEGEND. ALSO, COORDINATE WITH THE REVISED ENERGY
 CALCULATIONS.
  
 7- SHEET 6.0:
 A) WALL SECTIONS DON'T SHOW ROOF VENTILATION. PLEASE
 SPECIFY ROOF VENTILATION. SEC. R806.1. COORDINATE WITH
 THE REVISED ENERGY CALCULATIONS.
  
 B) WALL SECTIONS SHOW R19 INSULATION ON THE ROOF. R-19
 BATT INSULATION DOESN'T FIT ON THE 3X6 ROOF RAFTERS.
 COORDINATE WITH THE REVISED ENERGY CALCULATIONS.
  
 C) PLEASE COORDINATE THE R-VALUE SPECIFIED FOR THE
 WALLS ON WALL SECTIONS. PLEASE COORDINATE WITH THE
 REVISED ENERGY CALCULATIONS.
  
 8- PLEASE REVISE THE ENERGY CALCULATIONS SUBMITTED:
 A) TABLE 11B-1 ON THE SECOND PAGE REQUIRES R-30
 INSULATION ON THE CEILING. ITEM #10 ON FIRST PAGE
 SPECIFIES R-19. NEED TO PROVIDE R-30 MIN. (ALSO, CHECK
 SIZE OF RAFTERS ON SHEET 6.0).
  
 ***NOTE: FORM 1100B-08 IS A PRESCRIPTIVE METHOD AND
 NEED TO INSTALL THE MINIMUM REQUIREMENTS SHOWN ON TABLE
 11B-1. YOU MAY TRY TO SEE IF USING FORM 1100A-08 WILL
 COMPLY.
  
 B) COMPLETE ALL THE INFORMATION ON THE FORM ON ITS
 ENTIRETY. SEE ITEMS 4, 6B, 6C, 8A. ALSO, THE SQUARE
 FOOTAGE FOR ITEM 9A IS INCORRECT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-02 Cont ID  
Sent By rlecky Date 2011-12-02 Time 16:32 Rev Time 0.00
Received By rlecky Date 2011-12-02 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-02-03 Cont ID  
Sent By jgomez Date 2012-02-03 Time 09:57 Rev Time 0.00
Received By jgomez Date 2012-02-01 Time 15:08 Sent To  
Notes
2012-02-01 15:09:08SENT TO JULIO'S DESK. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2012-01-19 Cont ID  
Sent By jgomez Date 2012-01-19 Time 17:22 Rev Time 0.00
Received By jgomez Date 2012-01-11 Time 15:33 Sent To  
Notes
2012-01-12 15:33:35SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-11 Cont ID  
Sent By lmartine Date 2012-01-09 Time 11:48 Rev Time 0.00
Received By lmartine Date 2011-11-21 Time 14:09 Sent To  
Notes
2011-11-21 14:15:59R1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-01-19 Cont ID  
Sent By jgomez Date 2012-01-19 Time 16:07 Rev Time 0.00
Received By jgomez Date 2012-01-19 Time 16:07 Sent To  
Notes
2012-01-19 16:08:40STAMPED PLANS SHOW NO FEES DUE. MU-2011-20932.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-12-07 Cont ID  
Sent By jgomez Date 2011-12-07 Time 11:00 Rev Time 0.00
Received By jgomez Date 2011-12-07 Time 11:00 Sent To  
Notes
2011-12-07 11:04:14PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD.) TO CHECK IF IMPACT FEES ARE DUE. PLEASE, BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-12-07 Cont ID  
Sent By jgomez Date 2011-12-07 Time 15:51 Rev Time 0.00
Received By jgomez Date 2011-12-07 Time 15:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-12-07 Cont ID  
Sent By jgomez Date 2011-12-07 Time 13:31 Rev Time 0.00
Received By jgomez Date 2011-12-07 Time 13:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-01-09 Cont ID  
Sent By astelly Date 2012-01-09 Time 15:36 Rev Time 0.00
Received By ajones Date 2012-01-09 Time 15:36 Sent To  
Notes
***NONE***