Plan Review Details - Permit 11110349
Plan Review Stops For Permit 11110349
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-27 Cont ID  
Sent By rmcdouga Date 2011-12-27 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2011-12-27 Time 11:52 Sent To  
Notes
2011-12-27 15:47:33PROVISO
  
 PROVIDE THE CURRENT PRODUCT APPROVAL (NOA # 10-0930.02)
 FOR THE LARGE MISSLE IMPACT RATED SERIES "1700 IMPACT
 VIEW" SINGLE HUNG WINDOW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-29 Cont ID  
Sent By rmcdouga Date 2011-11-29 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2011-11-28 Time 16:40 Sent To  
Notes
2011-11-29 07:55:502007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE WIND DESIGN CRITERIA FOR THE DESIGN ON
 THE PLANS. SPECIFY WIND SPEED AND EXPOSURE CATEGORY.
 SEE FBC R 301.2.1.
  
 2) PROVIDE A BUCK FASTENING DETAIL FOR THE NEW FRENCH
 DOORS ON THE PLANS. SEE FBC R613.6.1.1
  
 3) REVISE GENERAL NOTE NUMBER 4 ON THE COVER SHEET TO
 REFERENCE THE CURRENT BUILDING CODE WHICH IS THE 2007
 FBC WITH 2009 REVISIONS.
  
 4) THE SOIL THAT IS REMOVED TO INSTALL THE NEW UNDER
 SLAB PLUMBING WILL BE REQUIRED TO BE TREATED FOR
 TERMITES IN ACCORDANCE WITH FBC R320.
  
 5) THE EXISTING WINDOW THAT WAS LOCATED IN THE BEDROOM
 AND AS A RESULT OF THE RECONFIGURATION OF THE FLOOR
 SPACE WILL NOW BE LOCATED IN THE MASTER BATH IS
 REQUIRED TO COMPLY WITH FBC R 308.4 (5) FOR GLAZING
 LOCATED IN HAZARDOUS LOCATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-11-28 Cont ID  
Sent By rlecky Date 2011-11-28 Time 11:21 Rev Time 0.00
Received By rlecky Date 2011-11-28 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-27 Cont ID  
Sent By rmcdouga Date 2011-12-27 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2011-12-22 Time 17:24 Sent To  
Notes
2011-12-22 17:24:21GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-19 Cont ID  
Sent By shill Date 2011-12-16 Time 10:39 Rev Time 0.00
Received By shill Date 2011-11-15 Time 11:21 Sent To  
Notes
2011-11-15 11:22:07SENT TO R3 SHELF FOR REVIEW BY ALL TRADES. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-11-28 Cont ID  
Sent By rmcdouga Date 2011-11-28 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2011-11-28 Time 16:16 Sent To  
Notes
2011-11-28 16:17:03NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL
 SUB-CONTRACTOR SIGNED ON APPLICATION. SEPARATE
 APPLICATION, PLANS AND REVIEW IS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-27 Cont ID  
Sent By rmcdouga Date 2011-12-27 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2011-12-27 Time 15:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-11-28 Cont ID  
Sent By rmcdouga Date 2011-11-28 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2011-11-28 Time 15:41 Sent To  
Notes
2011-11-28 16:15:272007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF SANITARY ISOMETRIC RISER DIAGRAMS
 FOR THE NEW MASTER BATHROOM. SPECIFY PIPE SIZES. CITY
 AMENDMENTS FBC 106.3.5.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-12-16 Cont ID  
Sent By astelly Date 2011-12-16 Time 15:17 Rev Time 0.00
Received By astelly Date 2011-12-16 Time 15:17 Sent To  
Notes
***NONE***