Plan Review Details - Permit 11110301
Plan Review Stops For Permit 11110301
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-01-27 Cont ID  
Sent By lmartine Date 2012-01-27 Time 16:50 Rev Time 0.00
Received By lmartine Date 2012-01-27 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-12-30 Cont ID  
Sent By lmartine Date 2011-12-30 Time 10:34 Rev Time 0.00
Received By lmartine Date 2011-12-30 Time 10:34 Sent To  
Notes
2011-12-30 10:39:05PREVIOUS COMMENTS WERE NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By lmartine Date 2011-12-01 Time 16:00 Rev Time 0.00
Received By lmartine Date 2011-12-01 Time 16:00 Sent To  
Notes
2011-12-01 16:08:41BUILDING REVIEW COMMENTS
  
  
  
 PROVIDE WIND LOAD ANALYSIS FOR THE OPENINGS ON THE
 BUILDING. THE DOOR SPEC'S SUBMITTED ARE ONLY GOOD FOR
 -70 PSF.
  
 SUBMIT DOCUMENTION CERTIFYING A 1HR ASSEMBLY,
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-01-20 Cont ID  
Sent By wjolin Date 2012-01-20 Time 13:55 Rev Time 0.00
Received By wjolin Date 2012-01-20 Time 13:55 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-12-19 Cont ID  
Sent By wjolin Date 2011-12-19 Time 12:17 Rev Time 0.00
Received By wjolin Date 2011-12-19 Time 11:46 Sent To B
Notes
2011-12-19 12:17:07525 SOUTH FLAGLER DRIVE
 PERMIT #11110301
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DOORS SHALL HAVE A FIRE RATING OF AT LEAST 90-MINUTES
 WHEN LOCATED IN A TWO-HOUR FIRE-RATED STAIR SHAFT.
  
 FIRE DOORS SHALL MEET THE REQUIREMENTS OF NFPA 80.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By wjolin Date 2011-12-01 Time 11:03 Rev Time 0.00
Received By wjolin Date 2011-12-01 Time 10:56 Sent To B
Notes
2011-12-01 11:03:40525 SOUTH FLAGLER DRIVE
 PERMIT #11110301
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS AND PERMIT APPLICATION INDICATE THE REPLACEMENT
 OF FIRE DOORS. NO HOURLY FIRE PROTECTION RATING COULD
 BE FOUND ON THE INFORMATION SUBMITTED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-01-27 Cont ID  
Sent By lmartine Date 2012-01-27 Time 16:50 Rev Time 0.00
Received By lmartine Date 2012-01-10 Time 16:38 Sent To  
Notes
2012-01-10 16:43:22TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-30 Cont ID  
Sent By lmartine Date 2011-12-30 Time 10:39 Rev Time 0.00
Received By lmartine Date 2011-12-13 Time 16:19 Sent To  
Notes
2011-12-21 15:04:47TO LM DESK
  
2011-12-13 16:19:52SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-01 Cont ID  
Sent By lmartine Date 2011-12-01 Time 16:08 Rev Time 0.00
Received By lmartine Date 2011-11-14 Time 14:36 Sent To  
Notes
2011-11-14 14:37:01TO FIRE BOX