| 2011-12-05 16:33:02 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) BOTH PAGES OF THE PLAN SHEETS ARE LABELED SHEET |
| | NUMBER A1.1. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| | |
| | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | ADDITION AS REQUIRED BY FBC N1100.0.3. |
| | |
| | 3) THE VALUE FOR THE WORK ON THE APPLICATION OF $8,000 |
| | IS TOO LOW FOR THE ADDITION OF 265 SQFT WITH A FULL |
| | BATH AND A 46 SQFT WOOD DECK. PLEASE ADJUST VALUE TO |
| | INCLUDE LABOR, MATERIALS, COST, OVERHEAD AND PROFIT AS |
| | A CONTRACTOR WOULD CHARGE. PLEASE PROVIDE A REVISED |
| | VALUE. CITY AMENDMENTS 108.3 |
| | |
| | 4) THE BATH ROOM DOES NOT COMPLY WITH FBC R307.1 FOR |
| | THE REQUIRED MINIMUM FIXTURE CLEARANCES AT THE SHOWER |
| | AND WATER CLOSET. A MINIMUM OF 24" CLEAR IS REQUIRED IN |
| | FRONT OF THE SHOWER AND 21" CLEAR IN FRONT OF THE WATER |
| | CLOSET. |
| | |
| | 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | ADDITION AS REQUIRED BY 2007 FBC ENERGY AMENDMENTS |
| | SECTION N1100.0.3 THAT HAS BEEN SIGNED BY THE PREPARER |
| | AND BY THE OWNER. |
| | |
| | 6) A CONTINOUS EAVE VENT IS REQUIRED IN ORDER TO |
| | PROVIDE VENTILATION AS REQUIRED BY FBC R806.1 TO THE |
| | ENCLOSED RAFTER SPACES ON A SINGLE ASSEMBLY ROOF |
| | SYSTEM. PLEASE REVISE PLANS. |
| | |
| | 7) SPECIFY THE TYPE OF EXTERIOR SHEATHING THAT WILL BE |
| | INSTALLED ON THE EXTERIOR OF THE WOOD FRAME WALLS. FBC |
| | R703.4 |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A |
| | BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE WATER |
| | RESISTIVE BARRIER. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063 |
| | WHICH REQUIRES A WEEP SCREED AT THE BOTTOM OF ALL |
| | FRAMED EXTERIOR WALLS, BELOW THE FLOOR LINE. |
| | |
| | 10) SUBMIT 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE EXTERIOR FRENCH DOORS, STORAGE |
| | ROOM DOOR AND WINDOW THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 106.3.3 |
| | |
| | 11) THE PLANS SPECIFY THE ROOFING TO BE TORCH DOWN OR |
| | COLD PROCESS, HOWEVER, THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED ARE FOR A CONVENTIONAL BUILT-UP HOT MOP |
| | SYSTEM. PLEASE CLARIFY. |
| | |
| | 12) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES AND |
| | FASTENING OPTION FROM THE ROOFING PRODUCT APPROVAL WILL |
| | BE USED. SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS |
| | FOR ENHANCED FASTENING REQUIREMENTS AT THE ROOF |
| | PERIMETER AND CORNER AREAS. FBC R301.2.1 |
| | |
| | 13) SUBMIT TWO SETS OF STRUCTURAL DRAWINGS FOR THE NEW |
| | EXTERIOR DECK AND STAIRS. CITY AMENDMENTS 106.1 |
| | |