Plan Review Details - Permit 11110177
Plan Review Stops For Permit 11110177
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By jwitmer Date 2011-12-28 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2011-12-27 Time 16:44 Sent To  
Notes
2011-12-28 08:36:50BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) VIP LOUNGE
 2007/09 FBC-B 1008.1.2 DOOR SWING
 DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR
 A GROUP H OCCUPANCY.
  
 2) STORAGE ROOM WALLS ARE SHOWN AS TYPICAL WALL TO THE
 CEILING:
 2007/09 FBC-B 508.2.2.1. CONSTRUCTION.
  
 WHERE TABLE 508.2 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF
 RESISTING THE PASSAGE OF SMOKE. THE PARTITIONS SHALL
 EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY OR
 FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY ABOVE OR TO
 THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, OR SUB
 DECK ABOVE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-17 Cont ID  
Sent By jwitmer Date 2011-11-17 Time 10:08 Rev Time 3.33
Received By jwitmer Date 2011-11-17 Time 10:08 Sent To  
Notes
2011-11-17 11:59:57BUILDING PLAN REVIEW
 PERMIT: 11110177
 ADD: 2223 PALM BEACH LAKES BLVD SUITE # 103
 CONT: LTA INC
 TEL: (561)635-8478
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THERE IS A HOLD ON THIS SUITE NUMBER, REQUIRING A
 CHANGE OF OCCUPANCY FROM MERCANTILE TO ASSEMBLY. THERE
 IS A DISCREPANCY BETWEEN SHEET A1 & A2, A1 INDICATES
 THE OCCUPANCY AS MERCANTILE (RETAIL) AND SHEET A2 AS A
 A-3 OCCUPANCY. THE ACTUAL USAGE OF THE SPACE OR
 MULTIPLE USES OF THIS SPACE MUST BE KNOWN TO ACCURATELY
 PLACE THIS TENANCY IN THE CORRECT ASSEMBLY
 SUB-GROUPING. FOR THE PURPOSE OF THIS REVIEW THE
 OCCUPANCY CLASSIFICATION WILL BE A A2 NOT THE A3 AS
 INDICATED BY THE DESIGNER OF RECORD. THERE ARE TWO
 REASONS:
  
 1A) PERMIT # 11040096 WAS FOR CONSTRUCTING A JUICE BAR
 WITHIN A MERCANTILE OCCUPANCY THE JUICE BAR HAD A
 OCCUPANCY LOAD OF LESS THAN 50 SO IT WAS STILL
 CONSIDERED RETAIL OCCUPANCY JUST AS THE FURNATURE STORE
 PORTION OF THE TENANCY, SHEET A-5 INDICATED A FURNITURE
 PLAN CONSISTENT WITH THE RETAIL OCCUPANCY. WITH THE
 DECLARED USE ON SHEET A2 OF
 A A3 OCCUPANCY WITH FOOD & DRINK THAT IS WHAT BUMPS
 THIS INTO THE A2 CATEGORY JUST AS A DANCE HALL THAT HAS
 FOOD & DRINK CONSUMPTION ON SITE.
  
 1B) CURRENTLY THE PERMIT APPLICATION APPLIED FOR IS FOR
 ONLY NEW RESTROOMS, NOT FOR A CHANGE OF USE WHICH WILL
 REQUIRE A NEW CERTIFICATE OF OCCUPANCY. THE LESSEE
 SHALL DECIDE HOW THEY WANT TO PROCEED IN GAINING CODE
 COMPLIANCE. EITHER THE CURRENT GENERAL CONTRACTOR CAN
 CHANGE THE DESCRIPTION OF WORK ON THE PERMIT
 APPLICATION UNDER THE DESCRIBE PROJECT IN DETAIL TO
 INCLUDE THE CHANGE OF OCCUPANCY AND INCLUDE THE
 ADDITIONAL WORK (INCREASED VALUE OF PROJECT) THAT WILL
 BE REQUIRED OR A SEPIRATE PERMIT CAN BE APPLIED FOR AS
 A CHANGE OF OCCUPANCY AND THE ADDITIONAL WORK THAT WILL
 BE REQUIRED UNDER THAT PERMIT. IF THE TENANT WISHES TO
 GO THE ROUTE OF A SEPARATE PERMIT FOR THE CHANGE OF
 OCCUPANCY PLEASE NOTE THE HOLD WILL NOT LET THE PERMIT
 FOR THE RESTROOMS BE ISSUED UNTIL
 THE CHANGE OF OCCUPANCY PERMIT IS ISSUED.
  
 2) ) SHEET A-2 INDICATES A NEW 20?X 30? PLATFORM BUT NO
 DESIGN CRITERIA (HEIGHT- FBC-B 410.3.1.1.) AS TO
 MATERIALS (FBC-B 410.3 / 603.1 ALLOWABLE MATERIALS),
 LIVE LOAD DESIGN & USAGE (FBC-B TABLE 1607.1),
 ACCESSIBILITY ( 11-4.1.6(1)(K)(III) VERTICAL
 ACCESSIBILITY).
  
 3) PLEASE PROVIDE A LIFE SAFETY SHEET WITH CHAIRS,
 TABLES AND OR FURNITURE LAYOUT. PLEASE PROVIDE THE
 FOLLOWING AS PART OF A MINIMUM COMMERCIAL PLAN
 REVIEW(FBC-B 106.3.5)
 3A) SITE PLAN SQUARE FOOTAGE OF THE TOTAL BUILDING
 3B) SITE PLAN ACCESSIBLE ENTRANCE AND PARKING
 3C) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS :
 COMMON PATH OF TRAVEL 1025.8/ 1025.9
 EXIT ACCESS
 EXIT
 DOORS 1025.6.1.
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 4) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING- ALARM SYSTEMS
 ASSEMBLY OCCUPANCY OVER 100 OCCUPANTS FBC-B
  
 5) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY STAGE OR PLATFORM
 TOILET AND BATHING FACILITIES PLEASE REVIEW 11-4.22.4
 WHERE 6 OR MORE TOILET STALLS ARE PROVIDED
 SPECIAL OCCUPANCY REQUIREMENTS 11-4.33 (ASSEMBLY AREAS)
 & 11-5 (RESTAURANTS & CAFETERIAS).
 PROVIDE 20% DISPROPORTIONATE COST PER FBC-B 11-4.1.6(2)
 PROVIDE IN LETTER FORM WHERE THESE FUNDS WILL BE
 IMPLEMENTED IN THE ALTERATIONS.
  
 6) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 TABLE 803.5.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-01-10 Cont ID  
Sent By rlecky Date 2012-01-10 Time 11:34 Rev Time 0.00
Received By rlecky Date 2012-01-10 Time 11:18 Sent To  
Notes
2012-01-10 11:24:54PROVISO:
  
 CONTRACTOR REQUESTED TO BRING IN THE ELECTRICAL PLAN
 UNDER A SEPERATE SUBMITTAL BY THE ELECTRICAL
 CONTRACTOR. PLANS RELEASED WITH THIS CONDITION AS A
 PROVISO. RL

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-12-28 Cont ID  
Sent By rlecky Date 2011-12-28 Time 15:29 Rev Time 0.00
Received By rlecky Date 2011-12-28 Time 15:19 Sent To  
Notes
2011-12-28 15:28:4411110177
 2223 PALM BEACH LAKES BLVD #103
 INTERIOR RENOVATION
  
 THE ELECTRICAL COMMENTS FROM THE FIRST REVIEW OF
 NOVEMBER 15, 2011 NOTED BELOW WERE NOT ADDRESSED IN THE
 NEW SUBMITTAL OF DECEMBER 22, 2011.
  
  
 1. PROVIDE AN ELECTRICAL RISER PLAN; LOCATE THE SERVICE
 AND ALL PANELS ON A FLOOR PLAN; INCLUDE A SUMMARY LOAD
 CALCULATION SHOWING EXISTING ELECTRIC SERVICE CAN
 HANDLE THE NEW LOADS; VERIFY SAFETY CLEARANCES AND
 ACCESS. NEC 110.26, 215.5
 2. SPECIFY ON THE PLANS HOW THE NEW LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-11-15 Cont ID  
Sent By rlecky Date 2011-11-15 Time 15:33 Rev Time 0.00
Received By rlecky Date 2011-11-15 Time 15:06 Sent To  
Notes
2011-11-15 16:04:1811110177
 2223 PALM BEACH LAKES BLVD #103
 INTERIOR RENOVATION
  
 PROVIDE AN ELECTRICAL RISER PLAN; LOCATE THE SERVICE
 AND ALL PANELS ON A FLOOR PLAN; INCLUDE A SUMMARY LOAD
 CALCULATION SHOWING EXISTING ELECTRIC SERVICE CAN
 HANDLE THE NEW LOADS; VERIFY SAFETY CLEARANCES AND
 ACCESS. NEC 110.26, 215.5
 SPECIFY ON THE PLANS HOW THE NEW LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-02-03 Cont ID  
Sent By mgonzale Date 2012-02-03 Time 14:20 Rev Time 0.00
Received By mgonzale Date 2012-02-03 Time 14:22 Sent To  
Notes
2012-02-03 14:22:35PASSED
  
 COMMENTS HAVE BEEN ADDRESSED WITH SUBMITTAL OF
 DOCUMENTATION. LETTER FROM EOR DATED FEB 3, 2012
  
 MANUEL JULIAN GONZALEZ
 DSD ENGINEERING REVIEW
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By   Date 2012-01-09 Time   Rev Time 1.00
Received By   Date 2012-01-09 Time   Sent To  
Notes
2012-01-09 10:42:43PLEASE RESPOND TO COMMENTS IN WRITING:
  
 #1 BUILDING PLANS (SHEET A-4) SHOW USE OF A FIRELINE,
 THE CITY OF WPB SHOWS NO ACCOUNT FOR THE FIRELINE.
 PLEASE CONTACT ME DIRECTLY TO DISCUSS ACCOUNT SETUP.
  
 #2 SITE PLAN (SHEET A-2) SHOWS EXIT RAMPS AT DOORS,
 FROM LOOKING AT THE PLAN IT CANNOT BE DETERMINED IF
 THEY ARE NEW OR EXISTING.
 ALSO PLEASE CALL OUT AS ADA IF FOR ADA PURPOSES. CALL
 OUT IF HANDRAIL IS EXISTING OR PROPOSED. IF ELEMENTS
 ARE TO BE PORPOSED THEN SHOUL WILL BE REQUIRED TO SHOW
 DETAIL WITH DIMENSIONS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-01-05 Cont ID  
Sent By wjolin Date 2012-01-05 Time 13:27 Rev Time 0.00
Received By wjolin Date 2012-01-05 Time 12:18 Sent To  
Notes
2012-01-05 13:04:142223 PALM BEACH LAKES BOULEVARD - SUITE #103
 PERMIT #11110177
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 A PLAN REVISION IS NEEDED FOR EXISTING SPRINKLER PERMIT
 #11080365. SPRINKLER VALUE HAS INCREASED WITH
 QUICK-RESPONSE SPRINKLER CONVERSION IN SUITE #101-#103.
 SPRINKLER PROTECTION TO BE PROVIDED IN NEW RESTROOM
 AREAS.
  
 A PLAN REVISION IS NEEDED FOR EXISTING FIRE ALARM
 PERMIT #11090530 TO INCLUDE THE NEW BATH AREA.
  
 SEATING NOT SECURED TO THE FLOOR SHALL BE FASTENED
 TOGTHER IN GROUPS OF AT LEAST THREE SEATS PER GROUP.
  
 ALL FIRE RATED DOORS AND FRAMING TO BE LABELED AND
 IDENTIFIED IN THE FIELD.
  
 FURTURE KITCHEN/STORAGE TO BE FIRE RATED, SELF CLOSING
 AND POSITIVE LATCHING.
  
 SEPARATE PLANS AND PERMIT WILL BE NEEDED FOR MECHANICAL
 VENTILATION OF THE RESTROOMS AND EXTERIOR FIRE LANE
 STRIPING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-14 Cont ID  
Sent By wjolin Date 2011-11-14 Time 12:05 Rev Time 0.00
Received By wjolin Date 2011-11-14 Time 09:09 Sent To  
Notes
2011-11-14 12:05:042223 PALM BEACH LAKES BOULEVARD - SUITE #103
 PERMIT #11110177
 REVIEW COMMENTS - FIRE DEPARTMENT
 SCOPE: CHANGE OF USE FROM MERCANTILE TO ASSEMBLY
 OCCUPANCY
  
 PER NFPA 101 PLANS FOR THE EXPOSITION (SPECIAL EVENT,
 CONCERT, SHOW, ETC.) SHALL BE SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO THE
 SETTING UP ANY EVENT. THE PLANS SHALL SHOW ALL DETAILS
 OF THE PROPOSED EXPOSITION. NO EXPOSITION SHALL OCCUPY
 ANY EXPOSITION FACILITY WITHOUT APPROVED PLANS.
  
 SHEET A-1 STILL INDICATES THIS SPACE TO BE A MERCANTILE
 OCCUPANCY IN LIEU OF AN ASSEMBLY OCCUPANCY.
  
 SHEET A-1 INDICATES CLASS C INTERIOR WALL AND CEILING
 FINISHES. FOR OCCUPANT LOADS GREATER THAN 300 PERSONS,
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASS A OR
 CLASS B.
  
 THE TWO SETS OF DOUBLE EXIT DOORS (WEST WALL) NEED TO
 BE INCLUDED IN THE SCOPE OF WORK AND OVERALL PROJECT
 VALUE. SUBMIT DOOR AND HARDWARE INFORMATION. NOTE:
 THESE UNPERMITTED DOORS WERE RECENTLY INSTALLED AND
 NEED TO BE INSPECTED, TESTED AND APPROVED.
  
 THE DOUBLE EXIT DOORS (SOUTHWEST) NEED TO BE INCLUDED
 IN THE SCOPE OF WORK AND OVERALL PROJECT VALUE. SUBMIT
 DOOR AND HARDWARE INFORMATION.
  
 THE EXISTING STANDARD RESPONSE FIRE SPRINKLERS NEED TO
 BE REPLACED WITH QUICK RESPONSE SPRINKLERS. EXISTING
 SPRINKLER PERMIT #11080365 NEEDS TO HAVE SCOPE AND JOB
 VALUE REVISED TO REFLECT THIS CHANGE.
  
 THE OCCUPANT LOAD ON SHEET A-2 IS BASED UPON 5 SQUARE
 FEET PER PERSON. THE OCCUPANT LOAD SHALL NOT EXCEED ONE
 PERSON PER SEVEN SQUARE FEET WHEN AREAS ARE LARGER THAN
 10,000 SQUARE FEET.
  
 NORTHWEST STORAGE ROOM SHALL BE PROVIDED WITH A DOOR TO
 SEPARATE THE STORAGE OCCUPANCY FROM THE ASSEMBLY
 OCCUPANCY.
  
 DEAD-END CORRIDOR (PLAN NORTH) SHALL NOT EXCEED 20
 FEET.
  
 PROVIDE ADDITIONAL INFORMATION AND DETAILS FOR THE
 20X30 FOOT STAGE.
  
 ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A MINIMUM
 OF ONE TRAINED CROWD MANAGER FOR EVERY 250 OCCUPANTS.
  
 POST PERMANENT NO SMOKING SIGNS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 DETAILS.
  
 PROVIDE EMERGENCY LIGHTING IN ALL RESTROOMS.
  
 NO ELECTRICAL WIRING PLAN SUBMITTED SHOWING POWER TO
 ALL EXIT SIGNS.
  
 FIRE ALARM SYSTEM SHALL BE UL (OR OTHER APPROVED
 AGENCY) CERTIFIED FOR CENTRAL STATION SERVICE BY FINAL
 FIRE INSPECTION.
  
 EXTERIOR KEY SAFE CAN BE ORDERED FROM WWW.KNOXBOX.COM.
  
 THE PAVED DRIVE TO THE WEST NEEDS TO BE MARKED AND
 STRIPED - FIRE LANE NO PARKING. A SEPARATE PLAN AND
 PERMIT IS REQUIRED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-09 Cont ID  
Sent By shill Date 2012-01-09 Time 14:14 Rev Time 0.00
Received By shill Date 2011-12-22 Time 16:23 Sent To  
Notes
2011-12-22 16:27:46*****************EXPEDITED********************
 B--20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-01 Cont ID  
Sent By lmartine Date 2011-11-30 Time 16:39 Rev Time 0.00
Received By lmartine Date 2011-11-09 Time 10:31 Sent To  
Notes
2011-11-09 10:31:57B19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2012-02-07 Cont ID  
Sent By jwitmer Date 2012-02-07 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2012-02-07 Time 13:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-02-06 Cont ID  
Sent By jwitmer Date 2012-02-06 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2012-02-06 Time 11:30 Sent To  
Notes
2012-02-06 11:30:53BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
2011-12-28 08:37:51BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-11-17 Cont ID  
Sent By jwitmer Date 2011-11-17 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2011-11-17 Time 10:07 Sent To  
Notes
2011-11-17 10:08:16BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-27 Cont ID  
Sent By lwagner Date 2011-12-27 Time 14:09 Rev Time 0.00
Received By lwagner Date 2011-12-27 Time 12:42 Sent To  
Notes
2011-12-27 14:09:241" WATER SUPPLY FIGURED THROUGH FLOW CHART - 60 POUNDS
 @ 1" PIPE = 47 GPM
 TABLE E103.3(3) - 70 FIXTURE UNITS REQUIRE 35 GPM = 12
 GPM RESERVE

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-11-30 Cont ID  
Sent By lwagner Date 2011-11-30 Time 10:34 Rev Time 0.00
Received By lwagner Date 2011-11-22 Time 09:07 Sent To  
Notes
2011-11-22 14:47:18FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 IF THIS PROJECT IS A-3, THEN A UNISEX RESTROOM WILL BE
 REQUIRED. THIS RESTROOM CAN COUNT AS PART OF THE
 REQUIRED FIXTURE COUNT.
 1. FBC PLUMBING 403.7 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. THE NEW MENS ROOM REQUIRES AN ADA STALL COMPLIANT
 WITH 11-4.17.3 SIZE AND ARRANGEMENT.
 EXCEPTION (1)
 11-4.22 TOILET ROOMS.
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17
 THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
  
 3. THE WOMENS RESTROOM HAS MORE THAN 6 WATER CLOSETS SO
 IT WILL REQUIRE A STALL THAT COMPLIES WITH FIGURE
 11-4.17.3 - 36" WIDE WITH PARALLEL GRAB BARS.
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER
 CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL
 COMPLY WITH SECTION 11-4.16.
  
 3. THE FIXTURE UNIT COUNT FOR THE NEW FIXTURES SHOWN ON
 P-1 IS 71 FIXTURE UNITS. THE COLD WATER SUPPLY IS SHOWN
 AS 3/4". TABLE 603.1 REQUIRES 1 1/2" FOR 71 FU. THE
 DROP FOR THE WOMENS ROOM WOULD BE 1" FOR 45 FU.
 604.1 GENERAL. THE DESIGN OF THE WATER DISTRIBUTION
 SYSTEM SHALL CONFORM TO ACCEPTED ENGINEERING PRACTICE.
 METHODS UTILIZED TO DETERMINE PIPE SIZES SHALL BE
 APPROVED. TABLE 603.1 SHALL BE PERMITTED TO BE USED TO
 SIZE THE WATER DISTRIBUTION SYSTEM.
  
 4. WHERE THE MULTIPLE WATER CLOSETS ARE SHOWN, A DRY
 VENT BETWEEN THE TWO MOST UPSTREAM WATER CLOSETS IS
 REQUIRED
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 ***NOTE***
 IF THE PROJECT IS A-3 AND THE OCCUPANT LOAD FOR MEN IS
 1100, THE WC FIXTURE COUNT FOR MEN WOULD BE 9 ( 9 X 125
 = 1125 MEN). THE PLAN SHOWS TOTAL OF TEN WC AND
 URINALS.
 ALSO THE UNISEX RESTROOM IS PERMITTED TO BE PART OF THE
 FIXTURE COUNT FOR MEN OR WOMEN.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2011-12-27 Cont ID  
Sent By eschneid Date 2011-12-27 Time 09:25 Rev Time 0.00
Received By eschneid Date 2011-12-27 Time 09:25 Sent To  
Notes
2011-12-27 09:25:32VALUE OF PERMITS PAST YEAR LESS THAN 50% OF STRUCTURE
 VALUE.