Plan Review Details - Permit 11110147
Plan Review Stops For Permit 11110147
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-11-09 Cont ID  
Sent By rlecky Date 2011-11-09 Time 14:40 Rev Time 0.00
Received By rlecky Date 2011-11-09 Time 14:15 Sent To  
Notes
2011-11-09 14:39:031110147
 4000 N. FLAGLER DR.
 TEMP ELECTRIC FOR TENT
 ELECTRIC REVIEW COMMENTS
  
 PROVISO:
 ALL WORK SHALL CONFORM WITH THE REQUIREMENTS OF TEH
 NATIONAL ELECTRICAL CODE ARTICLE 590 FOR TEMPORARY
 WIRING.
  
 A MAIN DISCONNECT IS REQUIRED AT THE GENERATOR
 ALL GENERAL PURPOSE OUTLETS SHALL BE GFCI PROTECTED.
 ALL FEEDERS AND CORDS SHALL BE PROPERLY PROTECTED
 AGAINST PHYSICAL DAMAGE.
 ALL LUMINARIES SHALL BE PROTECTED AGAINST PHYSICAL
 DAMAGE.
 OVERCURRENT PROTECTION SHALL BE PROVIDED FOR ALL
 CIRCUITS.
 BOXES AND PANEL BOARDS SHALL HAVE ALL UNUSED OPENINGS
 SEALED.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-11-09 Cont ID  
Sent By wjolin Date 2011-11-09 Time 14:07 Rev Time 0.00
Received By wjolin Date 2011-11-09 Time 13:49 Sent To E
Notes
2011-11-09 14:06:594000 NORTH FLAGLER DRIVE
 PERMIT #11110147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE GENERATOR SHALL BE PROTECTED FROM CONTACT BY THE
 PUBLIC BY MEANS OF A FENCE OR ENCLOSURE.
  
 PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY
 MATERIAL.
  
 CAR/VEHICLE SHALL CONTAIN LESS THAN 10 GALLONS OF FUEL.
 VEHICLE SHALL HAVE AT LEAST ONE CABLE REMOVED FROM THE
 BATTERY. VEHICLE SHALL NOT BE MOVED DURING THE EVENT.
  
 EXIT DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE
 REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-09 Cont ID  
Sent By rlecky Date 2011-11-09 Time 14:41 Rev Time 0.00
Received By rlecky Date 2011-11-07 Time 14:41 Sent To  
Notes
***NONE***