| Plan Review Stops For Permit 11110076 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-12-22 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-12-22 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-11-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-11-10 |
Time |
13:47 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2011-11-10 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2011-11-10 14:14:18 | BUILDING PLAN REVIEW | | | PERMIT: 11110076 | | | ADD: 1016 CLARE AVE | | | CONT: TRI R CONSTRUCTION COMPANY | | | TEL: (772)336-6444 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THESE ARE MINIMUMS FOR COMMERCIAL BUILDING REVIEW. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | BUILDING: | | | | | | 1A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED. | | | | | | 1B). MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED | | | (SEE TABLE 503). | | | | | | | | | 1C) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL | | | INCLUDE THE FOLLOWING COMPONENTS: | | | FIRE-RESISTANT SEPARATIONS | | | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION | | | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS | | | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE | | | RESISTANCE | | | | | | 1D) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL | | | INCLUDE THE FOLLOWING REQUIREMENTS: | | | OCCUPANT LOAD AND EGRESS CAPACITIES | | | | | | 1E) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | DOORS AMOUNT OF OCCUPANTS ALLOWED THROUGH EGRESS | | | DOORWAYS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | SPECIFIC OCCUPANCY REQUIREMENTS | | | | | | 2) PLANS SHEET A-2 DO NOT PROVIDE ENOUGH OCCUPANTS ON | | | THE SOCCER FIELDS, ARE NOT INDICATING LINESMEN, ETC. | | | ALONG THE SIDE LINES NO OCCUPANT LOAD HAS BEEN | | | ESTABLISHED SEE | | | FBC-B TABLE 1004.1.1 FOR OCCUPANT LOADS FOR SPECTATOR | | | WAITING AND SEATING AREA BY BAR. THERE IS ANOTHER AREA | | | TO THE RIGHT OF THE MAIN ENTRANCE APPROXIMATELY 45'X45' | | | WITH NO DESINATION OF USAGE, NOR OCCUPANT LOAD. 106.1.2 | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 3) SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT INDICATE | | | COMPLIANCE WITH 11-4.21 SHOWER STALLS NOR DRESSING | | | ROOMS. | | | | | | 4) SHEET A-2 THE DOUBLE DOORS LOCATED BETWEEN THE MAIN | | | ENTRY LOBBY AND WAITING/ SEATING AREA SWING THE WRONG | | | WAY, WITH OCCUPANT LOADS 50 AND GREATER SWING IN THE | | | DIRECTION OF EXIT TRAVEL, FBC-B 1008.1.2. | | | | | | 5) A-2) PLEASE PROVIDE ON THE LIFE SAFETY PLAN THE | | | LOCATION FOR TABLE & CHAIRS, IF BLEACHERS WILL BE | | | INSTALLED? IF SO OF WHAT TYPE MATERIALS? HOW HIGH OF | | | TIERS? ACCESSIBILITY? | | | | | | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2011-12-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2011-12-21 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2011-12-21 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2011-12-21 16:20:20 | LIGHTING CONTROL SHALL BE SHOWN ON DRAWINGS AS TO HOW | | | IT WILL BE DONE. (NOTE NOT ACCEPTABLE) | | | | | | LIGHTING DENSITY CALCULATION REQUIRED TO BE SHOWN ON | | | DRAWINGS TO COMPLY WITH THE FBC 13.415.ABC.5 | | | | | | A/C EQUIPMENT LOCATION TO BE SHOWN ON DRAWINGS, | | | LOCATION, LOCATION, LOCATION | | | | | | PANELS SHOWN ARE ON THE PLAYING FIELD????? | | | | | | SEE 410.10E FOR PROTECTION OF LIGHTING FIXTURES. | | | | | | JAKE LEAHY | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2011-12-12 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-12-12 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-12-12 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2011-12-12 11:06:21 | 11110076 | | | 1016 CLARE AVE #7 | | | INTERIOR BUILD OUT | | | | | | THE FOLLOWING ITEMS FROM THE FIRST REVIEW HAVE NOT BEEN | | | ADEQUATELY ADDRESSED. | | | | | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN | | | BATHROOMS, OUTDOORS, AND ADJACENT TO SINKS. NEC 210.8 | | | PROVIDE SPECIFICATIONS ON LIGHT FIXTURES SHOWING | | | PROTECTION AGAINST DAMAGE. LUMINAIRES SUBJECT TO | | | PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS AND | | | SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM DAMAGE. | | | NEC 410.10(E) | | | SHOW SERVICE LOCATION ON THE PLAN. NEC 230.72 | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | | NEC 110.26, 240.24, 408.17 | | | PROVIDE A MECHANISM TO GUARD THE PANEL BOARDS TO | | | PREVENT PHYSICAL DAMAGE. NEC 110.27 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-11-08 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-11-08 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-11-07 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2011-11-08 09:40:21 | 11110076 | | | 1016 CLARE AVE #7 | | | INTERIOR BUILD OUT | | | | | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | | EXISTING BUILDING 711.1 | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC 13-415 ABC.5 | | | ELECTRICAL FEEDERS TO BAY 1 AND 2 IMPROPERLY SIZED. NEC | | | TABLE 310-16, 215.5 | | | PROVIDE AN ELECTRICAL LOAD CALCULATION FOR BOTH PANELS. | | | NEC 215.5 | | | GFCI PROTECTION REQUIRED FOR RECEPTACLES IN BATHROOMS, | | | OUTDOORS, ROOFTOPS AND ADJACENT TO SINKS. NEC 210.8 | | | PROVIDE SPECIFICATIONS ON LIGHT FIXTURES. LUMINAIRES | | | SUBJECT TO PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS | | | AND SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM | | | DAMAGE. NEC 410.10(E) | | | VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN | | | ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC | | | 230.72 | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT. NEC 110.26, | | | 240.24, 408.17\ | | | LOCATE THE AIR CONDITIONING EQUIPMENT ON THE PLAN. | | | PROVIDE A GFCI PROTECTED RECEPTACLE WITHIN 25 FEET OF | | | ALL HEATING, AND AIR CONDITIONING FOR SERVICING OF THE | | | EQUIPMENT. NEC 210.63 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-12-28 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-12-28 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-12-28 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2011-12-28 10:31:12 | 1016 CLARE AVENUE - SUITE #7 | | | PERMIT #11110076 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION***** | | | | | | THE TOTAL OCCUPANT LOAD NEEDS TO BE LESS THAN 300 | | | PERSONS, OTHERWISE A FIRE ALARM SYSTEM IS REQUIRED AND | | | THE MAIN ENTRANCE (DOUBLE DOORS) WOULD NEED TO BE | | | EQUIPPED WITH PANIC HARDWARE. | | | | | | PROVIDE ADDITIONAL PORTABLE FIRE EXTINGUISHERS AS | | | TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 | | | FEET. | | | | | | REPEAT COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT | | | HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE | | | ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT | | | FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE | | | NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | REPEAT COMMENT: PROVIDE BUILDING ADDRESS VISIBLE FROM | | | THE STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING | | | AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE | | | AND SHALL CONTRAST THE BACKGROUND. | | | | | | REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED | | | EXIT DOORS WITH EXIT SIGNS. | | | | | | REPEAT COMMENT: SEPARATE PLANS AND PERMITS ARE REQUIRED | | | FOR THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM. FIRE | | | SPRINKLER SYSTEM TO BE SUPERVISED BY A MONITORING | | | COMPANY. SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW | | | CEILING SPACES THAT ARE NOT CONCEALED. | | | | | | DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE | | | FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE | | | BEEN SATISFIED. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-11-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-11-08 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-11-08 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2011-11-08 13:19:14 | 1016 CLARE AVENUE - SUITE #7 | | | PERMIT #11110076 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | | REMOVED FROM THE SITE DAILY. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF | | | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS | | | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A | | | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. | | | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF | | | OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. | | | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT | | | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL | | | CONTRAST THE BACKGROUND. | | | | | | INDICATE NEW AND EXISTING EMERGENCY LIGHTING. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE | | | PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO | | | RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE | | | PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC | | | HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN | | | ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR | | | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING | | | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS | | | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN | | | HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE | | | SUBSTITUTED FOR A KEYED LOCK. | | | | | | DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF EGRESS | | | TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM. FIRE | | | SPRINKLER SYSTEM TO BE SUPERVISED BY A MONITORING | | | COMPANY. SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW | | | CEILING SPACES THAT ARE NOT CONCEALED. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2011-12-28 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-12-28 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-12-09 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2011-12-16 11:23:31 | THIRD ELECTRICAL SUBMITTAL RECEIVED ON 12/15/16. SENT | | | TO B13 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-12-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-12-13 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-12-09 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2011-12-16 11:21:02 | LAST REVIEW DONE BY PLUMBING ON 12/13/11. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-11-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-11-29 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-11-03 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2011-11-10 15:12:46 | ****************EXPEDITED****************** | | | 11/10/11 | | 2011-11-03 16:22:48 | B--13 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2011-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-12-22 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-12-22 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2011-12-22 10:48:16 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2011-11-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-11-10 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-11-10 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2011-11-10 14:23:07 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-12-16 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-12-16 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-12-13 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2011-12-14 10:47:16 | ****PROVISO**** | | | FIXTURE COUNT GOOD FOR UP TO 195 WOMEN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2011-11-16 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-11-16 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-11-15 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2011-11-15 10:49:28 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. OCCUPANCY GROUP AND OCCUPANT COUNT NEED TO BE | | | DETERMINED SO THAT A FIXTURE COUNT CAN BE DETERMINED. | | | 1A. IF OCCUPANCY IS ASSEMBLY A SERVICE SINK WILL BE | | | REQUIRED. PLUMBING TABLE 403.1 | | | 1B. SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT | | | INDICATE COMPLIANCE WITH 11-4.21 SHOWER STALLS. | | | 1C. SHEET A-2 THE ADA TOILET STALLS DO NOT APPEAR TO | | | COMPLY WITH 11-4.17.3 SIZE AND ARRANGEMENT (EXCEPTION) | | | SEE FIGURE 30(E) THE REQUIRED WIDTH WOULD BE A MINIMUM | | | OF 7'-1" CLEAR. | | | | | | 2. FLOOR DRAINS REQUIRE TRAP PRIMERS. PLUMBING 1002.4 | | | | | | 3. PLEASE INCLUDE IN THE WATER PIPE DRAWING THE WATER | | | HEATER RELIEF AND PAN DRAIN PIPE AND TERMINATION PER | | | 504.6 AND 504.7.2 | | | 3A PLEASE INCLUDE THE REQUIRED WATER SHUTOFF VALVES ON | | | THE WATERPIPE DRAWING. 606.1 LOCATION OF FULL-OPEN | | | VALVES. FULL-OPEN VALVES SHALL BE INSTALLED IN THE | | | FOLLOWING LOCATIONS: | | | ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE | | | INTO THE STRUCTURE. | | | ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER. | | | | | | 4. PER CITY OF WEST PALM BEACH BACKFLOW AND | | | CROSS-CONNECTION CONTROL POLICY AN RPZ BACKFLOW | | | PREVENTER IS REQUIRED AS CLOSE AS POSSIBLE TO THE WATER | | | METER ON PRIVATE PROPERTY. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2011-12-16 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2011-12-16 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2011-12-16 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2011-12-16 15:43:50 | AMY STELLY | | | PLANNING AND ZONING | | | 561-822-1442 | | | | | | DETAILS FOR THE SCREENING OF THE AC EQUIPMENT AND | | | SUPPORTING RACK MUST BE SUBMITTED FOR REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-11-29 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2011-11-29 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2011-11-29 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2011-11-29 16:40:56 | AMY STELLY | | | PLANNING AND ZONING | | | 561-822-1442 | | | | | | THE LOCATION OF THE NEW AC EQUIPMENT IS NOT SHOWN ON | | | THE DRAWINGS. | | | | | | PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE | | | EQUIPMENT ON THE PROPERTY AND THE SETBACKS FROM ALL | | | PROPERTY LINES. | | | | | | IF THE EQUIPMENT WILL BE LOCATED ON THE ROOF, | | | ELEVATIONS OF THE BUILDINGS MUST BE SUBMITTED FOR | | | REVIEW. | | | | | | THE OVERALL HEIGHT OF THE BUILDING AND ANY MECHANICAL | | | EQUIPMENT MUST BE SHOWN. | | | | | | ADDITIONALLY, A SITE PLAN MUST BE SUBMITTED SHOWING THE | | | LOCATION OF THE DUMPSTER ENCLOSURE. | | | | | | THE PARKING SHOULD ALSO BE SHOWN ON THE SITE PLAN. | | | | | | YOUR REVIEW MAY GENERATE ADDITIONAL COMMENTS. |
|
|