Plan Review Details - Permit 11110076
Plan Review Stops For Permit 11110076
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-22 Cont ID  
Sent By jwitmer Date 2011-12-22 Time 10:55 Rev Time 0.00
Received By jwitmer Date 2011-12-22 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-10 Cont ID  
Sent By jwitmer Date 2011-11-10 Time 13:47 Rev Time 1.50
Received By jwitmer Date 2011-11-10 Time 13:47 Sent To  
Notes
2011-11-10 14:14:18BUILDING PLAN REVIEW
 PERMIT: 11110076
 ADD: 1016 CLARE AVE
 CONT: TRI R CONSTRUCTION COMPANY
 TEL: (772)336-6444
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THESE ARE MINIMUMS FOR COMMERCIAL BUILDING REVIEW.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 BUILDING:
  
 1A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 1B). MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
  
 1C) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 1D) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
  
 1E) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 DOORS AMOUNT OF OCCUPANTS ALLOWED THROUGH EGRESS
 DOORWAYS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 2) PLANS SHEET A-2 DO NOT PROVIDE ENOUGH OCCUPANTS ON
 THE SOCCER FIELDS, ARE NOT INDICATING LINESMEN, ETC.
 ALONG THE SIDE LINES NO OCCUPANT LOAD HAS BEEN
 ESTABLISHED SEE
 FBC-B TABLE 1004.1.1 FOR OCCUPANT LOADS FOR SPECTATOR
 WAITING AND SEATING AREA BY BAR. THERE IS ANOTHER AREA
 TO THE RIGHT OF THE MAIN ENTRANCE APPROXIMATELY 45'X45'
 WITH NO DESINATION OF USAGE, NOR OCCUPANT LOAD. 106.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT INDICATE
 COMPLIANCE WITH 11-4.21 SHOWER STALLS NOR DRESSING
 ROOMS.
  
 4) SHEET A-2 THE DOUBLE DOORS LOCATED BETWEEN THE MAIN
 ENTRY LOBBY AND WAITING/ SEATING AREA SWING THE WRONG
 WAY, WITH OCCUPANT LOADS 50 AND GREATER SWING IN THE
 DIRECTION OF EXIT TRAVEL, FBC-B 1008.1.2.
  
 5) A-2) PLEASE PROVIDE ON THE LIFE SAFETY PLAN THE
 LOCATION FOR TABLE & CHAIRS, IF BLEACHERS WILL BE
 INSTALLED? IF SO OF WHAT TYPE MATERIALS? HOW HIGH OF
 TIERS? ACCESSIBILITY?
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2011-12-21 Cont ID  
Sent By jleahy Date 2011-12-21 Time 16:20 Rev Time 0.00
Received By jleahy Date 2011-12-21 Time 16:07 Sent To  
Notes
2011-12-21 16:20:20LIGHTING CONTROL SHALL BE SHOWN ON DRAWINGS AS TO HOW
 IT WILL BE DONE. (NOTE NOT ACCEPTABLE)
  
 LIGHTING DENSITY CALCULATION REQUIRED TO BE SHOWN ON
 DRAWINGS TO COMPLY WITH THE FBC 13.415.ABC.5
  
 A/C EQUIPMENT LOCATION TO BE SHOWN ON DRAWINGS,
 LOCATION, LOCATION, LOCATION
  
 PANELS SHOWN ARE ON THE PLAYING FIELD?????
  
 SEE 410.10E FOR PROTECTION OF LIGHTING FIXTURES.
  
 JAKE LEAHY
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-12-12 Cont ID  
Sent By rlecky Date 2011-12-12 Time 11:06 Rev Time 0.00
Received By rlecky Date 2011-12-12 Time 10:44 Sent To  
Notes
2011-12-12 11:06:2111110076
 1016 CLARE AVE #7
 INTERIOR BUILD OUT
  
 THE FOLLOWING ITEMS FROM THE FIRST REVIEW HAVE NOT BEEN
 ADEQUATELY ADDRESSED.
  
 GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN
 BATHROOMS, OUTDOORS, AND ADJACENT TO SINKS. NEC 210.8
 PROVIDE SPECIFICATIONS ON LIGHT FIXTURES SHOWING
 PROTECTION AGAINST DAMAGE. LUMINAIRES SUBJECT TO
 PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS AND
 SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM DAMAGE.
 NEC 410.10(E)
 SHOW SERVICE LOCATION ON THE PLAN. NEC 230.72
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
 PROVIDE A MECHANISM TO GUARD THE PANEL BOARDS TO
 PREVENT PHYSICAL DAMAGE. NEC 110.27
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-11-08 Cont ID  
Sent By rlecky Date 2011-11-08 Time 09:41 Rev Time 0.00
Received By rlecky Date 2011-11-07 Time 17:00 Sent To  
Notes
2011-11-08 09:40:2111110076
 1016 CLARE AVE #7
 INTERIOR BUILD OUT
  
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING 711.1
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 ELECTRICAL FEEDERS TO BAY 1 AND 2 IMPROPERLY SIZED. NEC
 TABLE 310-16, 215.5
 PROVIDE AN ELECTRICAL LOAD CALCULATION FOR BOTH PANELS.
 NEC 215.5
 GFCI PROTECTION REQUIRED FOR RECEPTACLES IN BATHROOMS,
 OUTDOORS, ROOFTOPS AND ADJACENT TO SINKS. NEC 210.8
 PROVIDE SPECIFICATIONS ON LIGHT FIXTURES. LUMINAIRES
 SUBJECT TO PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS
 AND SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM
 DAMAGE. NEC 410.10(E)
 VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN
 ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC
 230.72
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT. NEC 110.26,
 240.24, 408.17\
 LOCATE THE AIR CONDITIONING EQUIPMENT ON THE PLAN.
 PROVIDE A GFCI PROTECTED RECEPTACLE WITHIN 25 FEET OF
 ALL HEATING, AND AIR CONDITIONING FOR SERVICING OF THE
 EQUIPMENT. NEC 210.63
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By wjolin Date 2011-12-28 Time 10:31 Rev Time 0.00
Received By wjolin Date 2011-12-28 Time 10:01 Sent To  
Notes
2011-12-28 10:31:121016 CLARE AVENUE - SUITE #7
 PERMIT #11110076
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE TOTAL OCCUPANT LOAD NEEDS TO BE LESS THAN 300
 PERSONS, OTHERWISE A FIRE ALARM SYSTEM IS REQUIRED AND
 THE MAIN ENTRANCE (DOUBLE DOORS) WOULD NEED TO BE
 EQUIPPED WITH PANIC HARDWARE.
  
 PROVIDE ADDITIONAL PORTABLE FIRE EXTINGUISHERS AS
 TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75
 FEET.
  
 REPEAT COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT
 HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE
 ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT
 FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 REPEAT COMMENT: PROVIDE BUILDING ADDRESS VISIBLE FROM
 THE STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING
 AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE
 AND SHALL CONTRAST THE BACKGROUND.
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: SEPARATE PLANS AND PERMITS ARE REQUIRED
 FOR THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM. FIRE
 SPRINKLER SYSTEM TO BE SUPERVISED BY A MONITORING
 COMPANY. SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW
 CEILING SPACES THAT ARE NOT CONCEALED.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-08 Cont ID  
Sent By wjolin Date 2011-11-08 Time 13:19 Rev Time 0.00
Received By wjolin Date 2011-11-08 Time 13:01 Sent To  
Notes
2011-11-08 13:19:141016 CLARE AVENUE - SUITE #7
 PERMIT #11110076
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 INDICATE NEW AND EXISTING EMERGENCY LIGHTING.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM. FIRE
 SPRINKLER SYSTEM TO BE SUPERVISED BY A MONITORING
 COMPANY. SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW
 CEILING SPACES THAT ARE NOT CONCEALED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-12-28 Cont ID  
Sent By wjolin Date 2011-12-28 Time 10:31 Rev Time 0.00
Received By wjolin Date 2011-12-09 Time 11:29 Sent To  
Notes
2011-12-16 11:23:31THIRD ELECTRICAL SUBMITTAL RECEIVED ON 12/15/16. SENT
 TO B13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-16 Cont ID  
Sent By jgomez Date 2011-12-13 Time 11:20 Rev Time 0.00
Received By jgomez Date 2011-12-09 Time 16:58 Sent To  
Notes
2011-12-16 11:21:02LAST REVIEW DONE BY PLUMBING ON 12/13/11. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-30 Cont ID  
Sent By shill Date 2011-11-29 Time 16:44 Rev Time 0.00
Received By shill Date 2011-11-03 Time 16:12 Sent To  
Notes
2011-11-10 15:12:46****************EXPEDITED******************
 11/10/11
2011-11-03 16:22:48B--13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2011-12-22 Cont ID  
Sent By jwitmer Date 2011-12-22 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2011-12-22 Time 10:46 Sent To  
Notes
2011-12-22 10:48:16BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-11-10 Cont ID  
Sent By jwitmer Date 2011-11-10 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2011-11-10 Time 14:22 Sent To  
Notes
2011-11-10 14:23:07BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-16 Cont ID  
Sent By lwagner Date 2011-12-16 Time 11:17 Rev Time 0.00
Received By lwagner Date 2011-12-13 Time 14:49 Sent To  
Notes
2011-12-14 10:47:16****PROVISO****
 FIXTURE COUNT GOOD FOR UP TO 195 WOMEN.

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-11-16 Cont ID  
Sent By lwagner Date 2011-11-16 Time 09:17 Rev Time 0.00
Received By lwagner Date 2011-11-15 Time 10:04 Sent To  
Notes
2011-11-15 10:49:28FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. OCCUPANCY GROUP AND OCCUPANT COUNT NEED TO BE
 DETERMINED SO THAT A FIXTURE COUNT CAN BE DETERMINED.
 1A. IF OCCUPANCY IS ASSEMBLY A SERVICE SINK WILL BE
 REQUIRED. PLUMBING TABLE 403.1
 1B. SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT
 INDICATE COMPLIANCE WITH 11-4.21 SHOWER STALLS.
 1C. SHEET A-2 THE ADA TOILET STALLS DO NOT APPEAR TO
 COMPLY WITH 11-4.17.3 SIZE AND ARRANGEMENT (EXCEPTION)
 SEE FIGURE 30(E) THE REQUIRED WIDTH WOULD BE A MINIMUM
 OF 7'-1" CLEAR.
  
 2. FLOOR DRAINS REQUIRE TRAP PRIMERS. PLUMBING 1002.4
  
 3. PLEASE INCLUDE IN THE WATER PIPE DRAWING THE WATER
 HEATER RELIEF AND PAN DRAIN PIPE AND TERMINATION PER
 504.6 AND 504.7.2
 3A PLEASE INCLUDE THE REQUIRED WATER SHUTOFF VALVES ON
 THE WATERPIPE DRAWING. 606.1 LOCATION OF FULL-OPEN
 VALVES. FULL-OPEN VALVES SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE
 INTO THE STRUCTURE.
 ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER.
  
 4. PER CITY OF WEST PALM BEACH BACKFLOW AND
 CROSS-CONNECTION CONTROL POLICY AN RPZ BACKFLOW
 PREVENTER IS REQUIRED AS CLOSE AS POSSIBLE TO THE WATER
 METER ON PRIVATE PROPERTY.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-12-16 Cont ID  
Sent By astelly Date 2011-12-16 Time 15:39 Rev Time 0.00
Received By astelly Date 2011-12-16 Time 15:39 Sent To  
Notes
2011-12-16 15:43:50AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 DETAILS FOR THE SCREENING OF THE AC EQUIPMENT AND
 SUPPORTING RACK MUST BE SUBMITTED FOR REVIEW.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-11-29 Cont ID  
Sent By astelly Date 2011-11-29 Time 16:32 Rev Time 0.00
Received By astelly Date 2011-11-29 Time 16:31 Sent To  
Notes
2011-11-29 16:40:56AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 THE LOCATION OF THE NEW AC EQUIPMENT IS NOT SHOWN ON
 THE DRAWINGS.
  
 PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 EQUIPMENT ON THE PROPERTY AND THE SETBACKS FROM ALL
 PROPERTY LINES.
  
 IF THE EQUIPMENT WILL BE LOCATED ON THE ROOF,
 ELEVATIONS OF THE BUILDINGS MUST BE SUBMITTED FOR
 REVIEW.
  
 THE OVERALL HEIGHT OF THE BUILDING AND ANY MECHANICAL
 EQUIPMENT MUST BE SHOWN.
  
 ADDITIONALLY, A SITE PLAN MUST BE SUBMITTED SHOWING THE
 LOCATION OF THE DUMPSTER ENCLOSURE.
  
 THE PARKING SHOULD ALSO BE SHOWN ON THE SITE PLAN.
  
 YOUR REVIEW MAY GENERATE ADDITIONAL COMMENTS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved