Plan Review Details - Permit 11110070
Plan Review Stops For Permit 11110070
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-30 Cont ID  
Sent By jwitmer Date 2011-12-30 Time 10:24 Rev Time 0.75
Received By jwitmer Date 2011-12-29 Time 15:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 14:19 Rev Time 1.33
Received By jwitmer Date 2011-11-14 Time 13:45 Sent To  
Notes
2011-11-14 14:51:11BUILDING PLAN REVIEW
 PERMIT: 11110070
 ADD: 509 NORTHWOOD ROAD
 CONT: SHELL RAZOR'S INC.
 TEL: (561)251-9718
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) IS THIS A CHANGE OF OCCUPANCY?
  
 2) SHEET S-1 SECTION A-A INDICATES THE REMOVAL OF A
 BLOCK WALL, SHORING UP A 8X12 4 BAR BEAM AND APPLYING A
 4X6 ANGLE TO THE BOTTOM OF THE BEAM. NOTES ALSO
 INDICATE THE USE OF A 4"X4" STEEL COLUMN WITH A TOP AND
 BOTTOM PLATE 7"X7". THE PLANS ARE NOT CLEAR AS TO HOW
 THE STEEL ANGLE AND COLUMN ARE TO BE JOINED TOGETHER BY
 BOLTING OR WELDING THE COLUMN TO THE STEEL ANGLE? IF
 THE TWO ARE TO BE WELDED WHAT IS THE TYPE OF WELD, THIS
 IS NOT KNOWN OF THE BOTTOM WELD? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 3) FOR THE SAME CONCRETE BEAM AND STEEL COLUMN
 CONFIGURATION, WHERE THE BLOCK WALL WALL IS REMOVED, IS
 THERE ANY PROVISIONS TO BE MADE HOW THE WEIGHT WILL BE
 TRANSFERRED TO THE FOUNDATION BELOW? ARE THE BLOCK
 CAVITIES TO BE FILLED ? ADDITIONAL INFORMATION
 REQUIRED?
  
 4) THE OTHER SECTION B-B IS FOR THE RAFTERS AND OR
 CEILING JOIST. ARE THE EXISTING ROOF FRAMING MEMBERS
 SPANNING THE 18'-2" CLEAR OR IS THERE A SPLICE OVER THE
 EXISTING BEARING WALL THAT IS BEING REMOVED? IF THERE
 IS A SPLICE OVER THE EXISTING BEARING WALL THE NEW
 GLULAM BEAM IS OVER 3'-6" AWAY FROM THE SPLICE POINT?
 ADDITIONAL INFORMATION REQUIRED?
  
 5) THE NEW GLULAM BEAM IS TO BE 5 1/2"X 12" PLEASE
 PROVIDE PRODUCT REPORT FOR WHICH HGUS HANGER YOU ENTEND
 ON INSTALLING AND TO WHAT TYPE OF MATERIALS THIS HANGER
 WILL BE ATTACHED TO. IT APPEARS THAT THE ONE END WILL
 BE ATTACHING INTO THE 4X6 STEEL ANGLE. NOTE MOST
 MANUFACTURERS OF HANGERS WILL VOID THE APPROVALS IF
 THEY ARE WELDED AT ALL.
  
 6) ARE THERE ANY FINSIHES BEING REPLACED, WALLS AND OR
 CEILING?
  
 7) S-1 INDICATES A NEW REAR DOOR LOCATION BUT THERE ARE
 NO STRUCTURAL DETAILS INDICATING HOW THE MWFRS WILL
 REMAIN , NO COLUMN, LENTAL DETAILS. MISSING WIND DESIGN
 CRITERIA.FBC-B 1609.
  
 8) EXISTING BUILDING CODE 808 MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITTH
 THE REQUIREMENTS OF CHAPTER 13 FOR THE FBC-B.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-01-05 Cont ID  
Sent By rlecky Date 2012-01-05 Time 14:22 Rev Time 0.00
Received By rlecky Date 2012-01-05 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-11-07 Cont ID  
Sent By rlecky Date 2011-11-07 Time 16:56 Rev Time 0.00
Received By rlecky Date 2011-11-07 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-01-05 Cont ID  
Sent By wjolin Date 2012-01-05 Time 14:15 Rev Time 0.00
Received By wjolin Date 2012-01-05 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-11-08 Cont ID  
Sent By wjolin Date 2011-11-08 Time 13:01 Rev Time 0.00
Received By wjolin Date 2011-11-08 Time 12:30 Sent To  
Notes
2011-11-08 12:59:28509 NORTHWOOD ROAD
 PERMIT #11110070
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-05 Cont ID  
Sent By lmartine Date 2012-01-05 Time 15:53 Rev Time 0.00
Received By lmartine Date 2011-12-22 Time 10:27 Sent To  
Notes
2011-12-22 10:28:43INCOMING SENT TO B12. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-05 Cont ID  
Sent By hmoser Date 2011-12-05 Time 15:40 Rev Time 0.00
Received By hmoser Date 2011-11-04 Time 14:29 Sent To  
Notes
2011-11-04 14:37:15B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-12-30 Cont ID  
Sent By jwitmer Date 2011-12-30 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2011-12-30 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-12-05 Cont ID  
Sent By hmoser Date 2011-12-05 Time 15:35 Rev Time 0.00
Received By hmoser Date 2011-12-05 Time 15:14 Sent To  
Notes
2011-12-05 15:40:21TALKED TO CONTRACTOR NO MECHANICAL ON THIS JOB.
 SEPARATE PERMITS REQUIRED FOR COOLERS IF NEEDED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By lwagner Date 2011-12-28 Time 13:09 Rev Time 0.00
Received By lwagner Date 2011-12-28 Time 08:13 Sent To  
Notes
2011-12-28 13:01:45*****PROVISO*****
 903.1 REQUIRED VENT EXTENSION. THE VENT SYSTEM SERVING
 EACH BUILDING DRAIN SHALL HAVE AT LEAST ONE VENT PIPE
 THAT EXTENDS TO THE OUTDOORS.
  
 *****NOTE*****
 DBPR HEALTH OR OTHER MAY HAVE SEPARATE FIXTURE
 REQUIREMENTS
 DIVISION OF HOTELS AND RESTAURANTS
 1940 NORTH MONROE STREET
 TALLAHASSEE, FL 32399-1011
  
 PHONE: 850.487.1395
 FAX: 850.921.8267
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/FORMS/PLANREVIE
 WFORMS.HTML

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-11-18 Cont ID  
Sent By lwagner Date 2011-11-18 Time 10:47 Rev Time 0.00
Received By lwagner Date 2011-11-16 Time 14:35 Sent To  
Notes
2011-11-17 15:30:12FBC 2007 PLUMBING PLAN REVIEW #1
 DENIED:
  
 1. A COFFEE LOUNGE WITH OVER 10 SEATS WOULD REQUIRE
 SEPERATE FACILITIES FOR MEN AND WOMEN. ALSO, A SERVICE
 SINK WOULD BE REQUIRED.
 FBC 2007 PLUMBING 403.1.1.1
  
 1A. FBC PLUMBING 2007 403.1.1.1 DEFINITIONS:
 ASSEMBLY OCCUPANCY. THE USE OF A BUILDING OR STRUCTURE,
 OR ANY PORTION THEREOF, FOR THE GATHERING TOGETHER OF
 PEOPLE FOR PURPOSES SUCH AS CIVIC, SOCIAL OR RELIGIOUS
 FUNCTIONS OR FOR RECREATION, OR FOR FOOD OR DRINK
 CONSUMPTION, OR AWAITING TRANSPORTATION.
  
 1B......403.2 SEPARATE FACILITIES. WHERE PLUMBING
 FIXTURES ARE REQUIRED, SEPARATE FACILITIES SHALL BE
 PROVIDED FOR EACH SEX.
 EXCEPTIONS:
 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 DWELLING UNITS AND SLEEPING UNITS.
 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR
 AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 1C. FOR MORE INFORMATION PLEASE SEE DCA09-DEC-130
  
 2. BACKFLOW PREVENTION, ALSO A HOT AND COLD WATER
 DIAGRAM, INCLUDING WATER HEATER WILL BE REQUIRED.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 PLUMBING
  2. WATER SUPPLY PIPING
  5. WATER HEATERS
  8. BACK FLOW PREVENTION
  
 *****NOTE*****
 DBPR HEALTH OR OTHER MAY HAVE SEPARATE FIXTURE
 REQUIREMENTS
 DIVISION OF HOTELS AND RESTAURANTS
 1940 NORTH MONROE STREET
 TALLAHASSEE, FL 32399-1011
  
 PHONE: 850.487.1395
 FAX: 850.921.8267
  
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/FORMS/PLANREVIE
 WFORMS.HTML
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2011-12-22 Cont ID  
Sent By astelly Date 2011-12-22 Time 10:24 Rev Time 0.00
Received By jwitmer Date 2011-12-22 Time 10:24 Sent To  
Notes
***NONE***