Plan Review Details - Permit 11110067
Plan Review Stops For Permit 11110067
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-11-07 Time 17:41 Rev Time 0.00
Received By shill Date 2011-11-03 Time 10:39 Sent To  
Notes
2011-11-03 10:39:21UNDER 5 K PLUMBING

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-11-07 Cont ID  
Sent By lwagner Date 2011-11-07 Time 15:03 Rev Time 0.00
Received By lwagner Date 2011-11-07 Time 14:54 Sent To  
Notes
2011-11-07 15:03:08FBC 2007 FUEL GAS REVIEW (REVISION)
 DENIED:
  
 PIPE SIZE IS INADEQUATE PER 2007 FUEL GAS TABLE
 402.4(19). GENERATOR 250,000 BTU @ 30' WOULD REQUIRE 1"
 PIPE OR 2LB METER.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  