Plan Review Details - Permit 11100690
Plan Review Stops For Permit 11100690
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-29 Cont ID  
Sent By shill Date 2011-11-29 Time 17:08 Rev Time 0.00
Received By shill Date 2011-11-29 Time 17:08 Sent To  
Notes
2011-11-29 17:18:19****PROVISOS****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****REVISION REQUIRED PRIOR TO ELECTRICAL
 INSPECTION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISION REQUIRED FOR FRAME SECTION BETWEEN THE
 EXISTING HOUSE AND PROPOSED NEW. PROVIDE ENGINEERING
 FOR THE PROPOSED FRAME ADDITION INCLUDING ATTACHMENT TO
 THE EXISTING STRUCTURE AND ATTACHMENT TO THE PROPOSED
 NEW METAL STRUCTURE.
  
 2. FP1, STATE WIND DESIGN CRITERIA FBC R 301.2.1. IT
 APPEARS THAT PRESSURES STATED ARE FOR EXPOSURE B. THIS
 PARCEL APPEARS TO BE LOCATED IN EXPOSURE C.
  
 3. FP1, PLEASE REVISE ACI 318 83 REFERENCE TO CURRENT,
 FBC R CHAPTER 43.
  
 4. PLEASE DETERMINE WHICH STRUCTURAL ENGINEER IS THE
 ENGINEER OF RECORD AND HAVE THE DELEGATED ENGINEERING
 REVIEWED BY THE ENGINEER OF RECORD, FAC61G15-31.001.
  
 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE WALL AND ROOF PANELS, STRUCTURAL COMPONENTS, FAC 9N
 3.
  
 6. THIS PERMIT IS ISSUED AS UNINHABITABLE STORAGE
 SPACE.
  
 7. PROVIDE A STRUCTURAL DETAIL FOR THE ATTACHMENT OF
 THE SOLAR PANELS TO SHOW HOW THEY WILL RESIST WIND
 LOADS FBC R 301.2.1.
  
 8. SMOKE ALARMS AND CARBON MONOXIDE ALARMS REQUIRED FBC
 R313, FS553.885.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-03 Cont ID  
Sent By shill Date 2011-11-03 Time 10:37 Rev Time 0.00
Received By shill Date 2011-11-02 Time 07:11 Sent To Z
Notes
2011-11-03 10:37:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SURVEY SHOWS STRUCTURES NOT LOCATED ON THE SURVEY.
 PLEASE INCLUDE THE FOLLOWING INFORMATION ON THE SURVEY:
 TYPE OF STRUCTURE, DISTANCE FROM STRUCTURE TO PROPOSED
 ADDITION FBC R TABLE 302.1.
  
 2. SITE PLAN SHOWS THAT THIS IS A PROPOSED ADDITION,
 WITH A FRAME SECTION BETWEEN THE EXISTING HOUSE AND
 PROPOSED NEW. PROVIDE ENGINEERING FOR THE PROPOSED
 FRAME ADDITION INCLUDING ATTACHMENT TO THE EXISTING
 STRUCTURE AND ATTACHMENT TO THE PROPOSED NEW METAL
 STRUCTURE. IF THE TWO STRUCTURES ARE NOT CONNECTED, SEE
 FBC R TABLE 302.1 REGARDING SEPARATION.
  
 3. FP1, STATE WIND DESIGN CRITERIA FBC R 301.2.1. IT
 APPEARS THAT PRESSURES STATED ARE FOR EXPOSURE B. THIS
 PARCEL APPEARS TO BE LOCATED IN EXPOSURE C.
  
 4. FP1, PLEASE REVISE ACI 318 83 REFERENCE TO CURRENT,
 FBC R CHAPTER 43.
  
 5. FP1 DOES NOT INCLUDE ANY INFORMATION FOR THE WOOD
 FRAME PORTION OF THE PROPOSED ADDITION.
  
 6. PLEASE DETERMINE WHICH STRUCTURAL ENGINEER IS THE
 ENGINEER OF RECORD AND HAVE THE DELEGATED ENGINEERING
 REVIEWED BY THE ENGINEER OF RECORD, FAC61G15-31.001.
  
 7. PLAN IS NOT CLEAR AS TO WHAT WILL BE DONE WITH THE
 OPENINGS. DOES THE SCOPE OF THIS PERMIT PROPOSE THAT
 THEY REMAIN OPEN, OR WILL DOORS/WINDOWS BE PUT IN THE
 OPENINGS?
  
 IF THEY ARE TO REMAIN OPEN, ENGINEER IS TO CONFIRM THAT
 ENCLOSED STILL APPLIES (RATHER THAN PARTIALLY
 ENCLOSED), SEE FBC R 301.2.1.1(8), FBC 1609, ASCE7-05.
  
 IF THE OPENINGS ARE TO HAVE DOORS AND WINDOWS
 INSTALLED, PROVIDE PRODUCT APPROVALS FOR THE COMPONENTS
 AND CLADDING (DOORS, WINDOWS), FAC9N 3.
  
 8. IF DOORS AND WINDOWS ARE TO BE INSTALLED, PROVIDE A
 BUCK ATTACHMENT DETAIL, FBC 106.1.
  
 9. DESIGN PRESSURES FOR ZONES 1, 2, AND 3 FOR THE ROOF
 TO BE SPECIFIED ON THE METAL BUILDING ENGINEERING, SEE
 FBC R 301.2(2) AND (3).
  
 10. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE WALL AND ROOF PANELS, STRUCTURAL COMPONENTS,
 FAC 9N 3.
  
 11. PROVIDE A DESIGNATION FOR THE PROPOSED ADDITION.
 PLANS DO NOT STATE USE OF THE ADDITION; IS THIS
 HABITABLE, STORAGE, GARAGE? PROVIDE A FLOOR PLAN
 SHOWING ALL DOORS ON THE PROPOSED ADDITION (EGRESS FOR
 THE PROPOSED ADDITION FBC106.3.5.4(5) AND SHOW HOW
 EGRESS FOR THE EXISTING BUILDING IS AFFECTED BY THE
 PROPOSED ADDITION (SHOW DOORS AND WINDOWS ON THE
 CURRENT BUILDING AFFECTED BY THE PROPOSED ADDITION,
 ROOM DESIGNATION IF APPLICABLE). PLAN IS TO INCLUDE THE
 NAME AND SIGNATURE OF THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE DESIGN, FS481, FBC106.2,
 106.3.15.
  
 HABITABLE SPACE REQUIRES ENERGY CALCS AND IMPACT FEE
 ASSESSMENT.
  
 12. DUE TO THE PROXIMITY OF THE GARAGE DOOR SIZED
 OPENINGS AND LOCATION OF THOSE DOORS IN RELATION TO THE
 DRIVEWAY, SHOW COMPLIANCE WITH FBC R 309 (GARAGE AND
 RESIDENCE SEPARATION).
  
 13. SHEET CS1 STATES THAT BUILDING USE IS BUSINESS.
 THIS WOULD BE REGULATED BY THE FLORIDA BUILDING CODE.
 PLEASE CLARIFY.
  
 14. PROVIDE A STRUCTURAL DETAIL FOR THE ATTACHMENT OF
 THE SOLAR PANELS TO SHOW HOW THEY WILL RESIST WIND
 LOADS FBC R 301.2.1.
  
 15. SMOKE ALARMS AND CARBON MONOXIDE ALARMS REQUIRED
 FBC R313, FS553.885.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2011-11-29 Cont ID  
Sent By shill Date 2011-11-29 Time 17:07 Rev Time 0.00
Received By shill Date 2011-11-29 Time 17:07 Sent To  
Notes
2011-11-29 17:07:27ELECTRICAL CONTRACTOR APPLIED FOR SEPARATE PERMIT
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-31 Cont ID  
Sent By jleahy Date 2011-10-31 Time 10:23 Rev Time 0.00
Received By jleahy Date 2011-10-31 Time 10:23 Sent To  
Notes
2011-10-31 10:34:44ELECTRIC PLAN IS MISSING INFORMATION
  
 WHAT SIZE IS SYSTEM?
  
 NO WIRE SIZES SHOWN AT ALL
  
 DISCONNECT OFF MAIN WHAT SIZE
  
 HOW MANY MODULES ARE YOU PUTTING UP IN SERIES,
 PARALLEL? NEED DIAGRAM OF TOTAL JOB THE SOLAR PANELS
 (ARRAYS)
  
 HOW IS EACH WIRED FROM PANELS TO INVETERS
  
 WHAT IS EACH GROUP CAPABLE OF TOTAL VOLAGE
  
 MAXIMUM VOLTAGE OF SYSTEM AND MAXIMUM AMPERAGE OF EACH
 GROUP AND TOTAL
  
 TYPES OF WIRES USED
  
 HOW ARE THEY GOING TO BE GROUNDED
  
 SONNY BOY 3000 IS IT LISTED?
  
 I DON'T SEE A COMBINER BOX
  
 DC DISCONNECT
  
 PLANS ARE SO VAGUE THERE COULD BE MORE INFORMATION
 REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-11-03 Time 17:16 Rev Time 0.00
Received By shill Date 2011-10-31 Time 08:02 Sent To  
Notes
2011-10-31 08:07:12**EXPEDITED**
 10/31 ROUTED TO JL DESK SH
 11/3 ROUTED TO AV DESK SH
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-11-29 Cont ID  
Sent By shill Date 2011-11-29 Time 17:19 Rev Time 0.00
Received By shill Date 2011-11-29 Time 17:18 Sent To  
Notes
2011-11-29 17:19:20UNINHABITABLE STORAGE SPACE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-11-03 Cont ID  
Sent By shill Date 2011-11-03 Time 10:39 Rev Time 0.00
Received By shill Date 2011-11-03 Time 10:38 Sent To  
Notes
2011-11-03 10:39:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PLAN TO SHOW USE OF PROPOSED ADDITION. IF
 HABITABLE SPACE, IMPACT FEE ASSESSMENT BY PALM BEACH
 COUNTY IS REQUIRED. THE PLANS ARE TO BE STAMPED AND THE
 RECEIPT SHOWING THAT FEES DUE (IF APPLICABLE) IS TO BE
 PROVIDED. 561-233-5025 FOR MORE INFORMATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2011-11-28 Cont ID  
Sent By ajones Date 2011-11-28 Time 14:25 Rev Time 0.00
Received By ajones Date 2011-11-28 Time 14:25 Sent To  
Notes
2011-11-28 14:26:15CURB CUT ALONG FLORAL AVENUE SHALL BE A MAX OF 10 FEET
 WIDE.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-11-03 Cont ID  
Sent By ajones Date 2011-11-03 Time 15:00 Rev Time 0.00
Received By ajones Date 2011-11-03 Time 15:00 Sent To  
Notes
2011-11-03 15:06:441. HEIGHT DIMENSIONS NEED TO BE PROVIDED.
 2. THE PROPOSED CURB CUT ON FLORAL AVENUE IS TO WIDE.
 THE REGULAIONS PERMIT EITHER 2 10-FOOT WIDE ACCESS
 POINTS OR 1 20-FOOT WIDE ONE. BOTHER EXISTING CURB CUTS
 ALREADY EXCEEDS THIS REQIREMENT.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  