| 2011-11-03 10:37:42 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. SURVEY SHOWS STRUCTURES NOT LOCATED ON THE SURVEY. |
| | PLEASE INCLUDE THE FOLLOWING INFORMATION ON THE SURVEY: |
| | TYPE OF STRUCTURE, DISTANCE FROM STRUCTURE TO PROPOSED |
| | ADDITION FBC R TABLE 302.1. |
| | |
| | 2. SITE PLAN SHOWS THAT THIS IS A PROPOSED ADDITION, |
| | WITH A FRAME SECTION BETWEEN THE EXISTING HOUSE AND |
| | PROPOSED NEW. PROVIDE ENGINEERING FOR THE PROPOSED |
| | FRAME ADDITION INCLUDING ATTACHMENT TO THE EXISTING |
| | STRUCTURE AND ATTACHMENT TO THE PROPOSED NEW METAL |
| | STRUCTURE. IF THE TWO STRUCTURES ARE NOT CONNECTED, SEE |
| | FBC R TABLE 302.1 REGARDING SEPARATION. |
| | |
| | 3. FP1, STATE WIND DESIGN CRITERIA FBC R 301.2.1. IT |
| | APPEARS THAT PRESSURES STATED ARE FOR EXPOSURE B. THIS |
| | PARCEL APPEARS TO BE LOCATED IN EXPOSURE C. |
| | |
| | 4. FP1, PLEASE REVISE ACI 318 83 REFERENCE TO CURRENT, |
| | FBC R CHAPTER 43. |
| | |
| | 5. FP1 DOES NOT INCLUDE ANY INFORMATION FOR THE WOOD |
| | FRAME PORTION OF THE PROPOSED ADDITION. |
| | |
| | 6. PLEASE DETERMINE WHICH STRUCTURAL ENGINEER IS THE |
| | ENGINEER OF RECORD AND HAVE THE DELEGATED ENGINEERING |
| | REVIEWED BY THE ENGINEER OF RECORD, FAC61G15-31.001. |
| | |
| | 7. PLAN IS NOT CLEAR AS TO WHAT WILL BE DONE WITH THE |
| | OPENINGS. DOES THE SCOPE OF THIS PERMIT PROPOSE THAT |
| | THEY REMAIN OPEN, OR WILL DOORS/WINDOWS BE PUT IN THE |
| | OPENINGS? |
| | |
| | IF THEY ARE TO REMAIN OPEN, ENGINEER IS TO CONFIRM THAT |
| | ENCLOSED STILL APPLIES (RATHER THAN PARTIALLY |
| | ENCLOSED), SEE FBC R 301.2.1.1(8), FBC 1609, ASCE7-05. |
| | |
| | IF THE OPENINGS ARE TO HAVE DOORS AND WINDOWS |
| | INSTALLED, PROVIDE PRODUCT APPROVALS FOR THE COMPONENTS |
| | AND CLADDING (DOORS, WINDOWS), FAC9N 3. |
| | |
| | 8. IF DOORS AND WINDOWS ARE TO BE INSTALLED, PROVIDE A |
| | BUCK ATTACHMENT DETAIL, FBC 106.1. |
| | |
| | 9. DESIGN PRESSURES FOR ZONES 1, 2, AND 3 FOR THE ROOF |
| | TO BE SPECIFIED ON THE METAL BUILDING ENGINEERING, SEE |
| | FBC R 301.2(2) AND (3). |
| | |
| | 10. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | FOR THE WALL AND ROOF PANELS, STRUCTURAL COMPONENTS, |
| | FAC 9N 3. |
| | |
| | 11. PROVIDE A DESIGNATION FOR THE PROPOSED ADDITION. |
| | PLANS DO NOT STATE USE OF THE ADDITION; IS THIS |
| | HABITABLE, STORAGE, GARAGE? PROVIDE A FLOOR PLAN |
| | SHOWING ALL DOORS ON THE PROPOSED ADDITION (EGRESS FOR |
| | THE PROPOSED ADDITION FBC106.3.5.4(5) AND SHOW HOW |
| | EGRESS FOR THE EXISTING BUILDING IS AFFECTED BY THE |
| | PROPOSED ADDITION (SHOW DOORS AND WINDOWS ON THE |
| | CURRENT BUILDING AFFECTED BY THE PROPOSED ADDITION, |
| | ROOM DESIGNATION IF APPLICABLE). PLAN IS TO INCLUDE THE |
| | NAME AND SIGNATURE OF THE INDIVIDUAL TAKING |
| | RESPONSIBILITY FOR THE DESIGN, FS481, FBC106.2, |
| | 106.3.15. |
| | |
| | HABITABLE SPACE REQUIRES ENERGY CALCS AND IMPACT FEE |
| | ASSESSMENT. |
| | |
| | 12. DUE TO THE PROXIMITY OF THE GARAGE DOOR SIZED |
| | OPENINGS AND LOCATION OF THOSE DOORS IN RELATION TO THE |
| | DRIVEWAY, SHOW COMPLIANCE WITH FBC R 309 (GARAGE AND |
| | RESIDENCE SEPARATION). |
| | |
| | 13. SHEET CS1 STATES THAT BUILDING USE IS BUSINESS. |
| | THIS WOULD BE REGULATED BY THE FLORIDA BUILDING CODE. |
| | PLEASE CLARIFY. |
| | |
| | 14. PROVIDE A STRUCTURAL DETAIL FOR THE ATTACHMENT OF |
| | THE SOLAR PANELS TO SHOW HOW THEY WILL RESIST WIND |
| | LOADS FBC R 301.2.1. |
| | |
| | 15. SMOKE ALARMS AND CARBON MONOXIDE ALARMS REQUIRED |
| | FBC R313, FS553.885. |
| | |
| | |
| | |