Plan Review Details - Permit 11100656
Plan Review Stops For Permit 11100656
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-20 Cont ID  
Sent By jwitmer Date 2011-12-20 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2011-12-20 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-11-15 Cont ID  
Sent By jwitmer Date 2011-11-15 Time 15:53 Rev Time 1.00
Received By jwitmer Date 2011-11-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-03-21 Cont ID  
Sent By rlecky Date 2012-03-21 Time 09:44 Rev Time 0.00
Received By rlecky Date 2012-03-21 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By rlecky Date 2011-12-28 Time 12:43 Rev Time 0.00
Received By rlecky Date 2011-12-28 Time 12:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-31 Cont ID  
Sent By jleahy Date 2011-10-31 Time 14:45 Rev Time 0.00
Received By jleahy Date 2011-10-31 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-01-03 Cont ID  
Sent By wjolin Date 2012-01-03 Time 14:02 Rev Time 0.00
Received By wjolin Date 2012-01-03 Time 13:55 Sent To  
Notes
2012-01-03 13:56:27222 LAKEVIEW AVENUE - 8TH FLOOR
 PERMIT #11100656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE VISUAL FIRE ALARM NOTIFICATION APPLIANCES IN
 FILE ROOM #818 AND PANTRY ROOM #802.
  
 REPEAT COMMENT: SHEET FP2: FOR SYSTEM PRESSURES
 EXCEEDING 100 PSI, ARMOVERS AND END OF BRANCH LINE
 PENDENT SPRINKLERS SHALL BE PROTECTED FROM UPWARD
 MOVEMENT. HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF
 THE DROP ELBOW. INDICATE THE HANGER TYPE OR METHOD TO
 BE USED FOR RESTRAINING UPWARD MOVEMENT. (NOTE: THE
 HINGED-SPLIT RING HANGER ON FP2 IS NOT LISTED FOR FIRE
 PROTECTION USE.)
  
 REPEAT COMMENT: SHEET FP2: PER NFPA 13, PIPING SHALL BE
 HYDROSTATICALLY TESTED AT 50 PSI ABOVE STATIC PRESSURE
 IN EXCESS OF 150 PSI. THIS BUILDING HAS A 1500 GPM FIRE
 PUMP THAT PRODUCES 165 PSI AT CHURN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-12-05 Cont ID  
Sent By wjolin Date 2011-12-05 Time 11:19 Rev Time 0.00
Received By wjolin Date 2011-12-05 Time 10:49 Sent To  
Notes
2011-12-05 11:18:53222 LAKEVIEW AVENUE - 8TH FLOOR
 PERMIT #11100656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: NO FIRE ALARM ENGINEERING DOCUMENTS
 SUBMITTED.
  
 REPEAT COMMENT: SHEET FP2: FOR SYSTEM PRESSURES
 EXCEEDING 100 PSI, ARMOVERS AND END OF BRANCH LINE
 PENDENT SPRINKLERS SHALL BE PROTECTED FROM UPWARD
 MOVEMENT. HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF
 THE DROP ELBOW. INDICATE THE HANGER TYPE OR METHOD TO
 BE USED FOR RESTRAINING UPWARD MOVEMENT. (NOTE: THE
 HINGED-SPLIT RING HANGER ON FP2 IS NOT LISTED FOR FIRE
 PROTECTION USE.)
  
 REPEAT COMMENT: SHEET FP2: PER NFPA 13, PIPING SHALL BE
 HYDROSTATICALLY TESTED AT 50 PSI ABOVE STATIC PRESSURE
 IN EXCESS OF 150 PSI. THIS BUILDING HAS A 1500 GPM FIRE
 PUMP THAT PRODUCES 165 PSI AT CHURN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-02 Cont ID  
Sent By wjolin Date 2011-11-02 Time 09:55 Rev Time 0.00
Received By wjolin Date 2011-11-02 Time 08:33 Sent To  
Notes
2011-11-02 09:55:30222 LAKEVIEW AVENUE - 8TH FLOOR
 PERMIT #11100656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE
 SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE - NFPA
 101.
  
 NO FIRE ALARM ENGINEERING DOCUMENTS SUBMITTED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION/MODIFICATION OF THE FIRE SPRINKLER SYSTEM,
 FIRE ALARM SYSTEM AND ACCESS CONTROL SYSTEM.
  
 SHEET A103: THE MANUAL PUSH TO EXIT BUTTON FOR THE MAIN
 ENTRY MAGNETIC DOOR LOCKS ARE REQUIRED TO BE LOCATED
 WITHIN 60-INCHES (HORIZONTALLY) OF THE DOOR LEVER.
  
 SHEET A103: CONFIRM THE SECONDARY EXIT DOOR LOCATED AT
 CORRIDOR 816 IS EQUIPPED WITH AN ELECTRIFIED HINGE AND
 NOT A MAGNETIC LOCK (WITH PUSH TO EXIT BUTTON).
  
 SHEET A106: THE FABRIC WALLCOVERINGS SHALL MEET THE
 SMOKE DEVELOPMENT (0-450) AND FLAME SPREAD (76-200)
 REQUIREMENTS FOR CLASS C INTERIOR FINISHES PER NFPA
 101.
  
 SHEET FP2: FOR SYSTEM PRESSURES EXCEEDING 100 PSI,
 ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS
 SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL
 BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 SHEET FP2: PER NFPA 13, PIPING SHALL BE HYDROSTATICALLY
 TESTED AT 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150
 PSI. THIS BUILDING HAS A 1500 GPM FIRE PUMP THAT
 PRODUCES 165 PSI AT CHURN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-21 Cont ID  
Sent By rlecky Date 2012-03-21 Time 09:45 Rev Time 0.00
Received By rlecky Date 2012-03-13 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-03 Cont ID  
Sent By wjolin Date 2012-01-03 Time 14:02 Rev Time 0.00
Received By wjolin Date 2011-12-01 Time 14:18 Sent To  
Notes
2011-12-01 14:26:25C5
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-16 Cont ID  
Sent By hmoser Date 2011-11-16 Time 11:58 Rev Time 0.00
Received By hmoser Date 2011-10-28 Time 13:44 Sent To  
Notes
2011-10-28 13:44:59INCOMING SENT TO C-1. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-03-19 Cont ID  
Sent By hmoser Date 2012-03-19 Time 15:19 Rev Time 0.00
Received By hmoser Date 2012-03-19 Time 15:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-16 Cont ID  
Sent By hmoser Date 2011-11-16 Time 11:58 Rev Time 0.00
Received By hmoser Date 2011-11-16 Time 09:43 Sent To  
Notes
2011-11-16 11:29:44PASS PROVISO
 REFER TO SECTION 603.8 CAVITIES OF THE BUILDING
 STRUCTURE. 2007 FBC (M)
 SMOKE CONTROL AND SMOKE EVACK MUST BE TESTED FOR FINAL
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-15 Cont ID  
Sent By lwagner Date 2011-12-15 Time 14:01 Rev Time 0.00
Received By lwagner Date 2011-12-15 Time 13:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-11-14 Cont ID  
Sent By lwagner Date 2011-11-14 Time 15:06 Rev Time 0.00
Received By lwagner Date 2011-11-14 Time 14:45 Sent To  
Notes
2011-11-14 14:56:52****PROVISO****
 HUMIDIFIER WATER SUPPLY TO HAVE AIR GAP OR APPROVED
 BACKFLOW PREVENTION DEVICE.

Review Stop Z ZONING
Rev No 1 Status N Date 2011-11-07 Cont ID  
Sent By aaponte Date 2011-11-07 Time 12:00 Rev Time 0.00
Received By aaponte Date 2011-11-07 Time 12:00 Sent To  
Notes
2011-11-07 12:00:28INTERIOR RENOVATION FOR OFFICE SPACE.