Plan Review Details - Permit 11100630
Plan Review Stops For Permit 11100630
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-11-07 Cont ID  
Sent By jwitmer Date 2011-11-07 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2011-11-07 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-31 Cont ID  
Sent By jleahy Date 2011-10-31 Time 14:35 Rev Time 0.00
Received By jleahy Date 2011-10-31 Time 14:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By wjolin Date 2011-11-01 Time 14:20 Rev Time 0.00
Received By wjolin Date 2011-11-01 Time 13:44 Sent To  
Notes
2011-11-01 14:18:232051 45TH STREET - SUITE #107
 PERMIT #11100630
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - ADDRESS*****
  
 THE PLANS INDICATE A CONGRESS AVENUE ADDRESS WHICH
 SHOULD ACTUALLY BE ADDRESSED 45TH STREET.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-11-08 Time   Rev Time 0.00
Received By jwitmer Date 2011-10-28 Time 13:41 Sent To  
Notes
2011-10-28 13:41:19INCOMING SENT TO B-20. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-08 Cont ID  
Sent By rregueir Date 2011-11-08 Time 13:22 Rev Time 0.00
Received By rregueir Date 2011-11-07 Time 16:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-11-02 Cont ID  
Sent By lwagner Date 2011-11-02 Time 14:18 Rev Time 0.00
Received By lwagner Date 2011-11-01 Time 15:27 Sent To  
Notes
2011-11-02 12:07:02***PROVISO***
 IF LOUNGE SINK IS FOR THE PURPOSE OF WASHING, HOT OR
 TEMPERED WATER IS REQUIRED.
 SECTION 607
 HOT WATER SUPPLY SYSTEM
 607.1 WHERE REQUIRED. IN NONRESIDENTIAL OCCUPANCIES,
 HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED FOR
 BATHING AND WASHING PURPOSES.
  