Plan Review Details - Permit 11100606
Plan Review Stops For Permit 11100606
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-11-15 Cont ID  
Sent By jwitmer Date 2011-11-15 Time 13:56 Rev Time 0.77
Received By jwitmer Date 2011-11-15 Time 13:56 Sent To  
Notes
2011-11-15 14:16:06BUILDING PROVISO:
 SHEET S-1 SECTION 1 GARAGE DOOR INFILE.
 2304.11.2.6 WOOD SIDING. CLEARANCE BETWEEN WOOD SIDING
 AND EARTH ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM) EXCEPT WHERE SIDING,
 SHEATHING AND WALL FRAMING ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-11-03 Cont ID  
Sent By rlecky Date 2011-11-03 Time 11:59 Rev Time 0.00
Received By rlecky Date 2011-11-03 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-15 Cont ID  
Sent By wjolin Date 2011-11-15 Time 08:57 Rev Time 0.00
Received By wjolin Date 2011-11-15 Time 08:54 Sent To  
Notes
2011-11-15 08:56:00429 PARK PLACE
 PERMIT #11100606
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTERS "RF" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  
 INDICATE WHAT TYPES OF MATERIALS OR COMMODITIES WILL BE
 STORED. INDICATE ON THE PLANS THAT THE MAXIMUM
 PERMITTED STORAGE HEIGHT IS 12 FEET.
  
 CONFIRM THE EXISTING SPRINKLER SYSTEM WAS DESIGNED FOR
 ORDINARY HAZARD GROUP II DENSITY (0.20 GPM/SQ.FT.) AND
 NOT ORDINARY HAZARD GROUP I DENSITY (0.15 GPM/SQ.FT.).
 PROVIDE EXISTING HYDRAULIC NAMEPLATE DESIGN DATA ON
 PLANS.
  
 SHEET FP-01 INDICATES A DESIGN AREA OF 1500 SQUARE
 FEET. THE ROOF SECTION ON SHEET FP-02 APPEARS TO HAVE A
 PITCH GREATER THAN 1 IN 6 AND WOULD REQUIRE THE DESIGN
 AREA TO BE INCREASED BY 30 PERCENT TO 1950 SQUARE FEET.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-01 Cont ID  
Sent By wjolin Date 2011-11-01 Time 13:28 Rev Time 0.00
Received By wjolin Date 2011-11-01 Time 11:58 Sent To  
Notes
2011-11-01 13:28:33429 PARK PLACE
 PERMIT #11100606
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTERS "RF" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  
 SECTION 42.3.1 OF NFPA 101 (FLORIDA) DOES NOT ALLOW THE
 MEZZANINE STAIR TO BE OPEN AN UNPROTECTED. ALSO SECTION
 8.6.8.2(4) CONFIRMS VERTICAL OPENINGS SHALL NOT SERVE
 AS A REQUIRED MEANS OF EGRESS.
  
 INDICATE WHAT TYPES OF MATERIALS OR COMMODITIES WILL BE
 STORED. INDICATE ON THE PLANS THAT THE MAXIMUM
 PERMITTED STORAGE HEIGHT IS 12 FEET.
  
 CONFIRM THE EXISTING SPRINKLER SYSTEM WAS DESIGNED FOR
 ORDINARY HAZARD GROUP II DENSITY (0.20 GPM/SQ.FT.) AND
 NOT ORDINARY HAZARD GROUP I DENSITY (0.15 GPM/SQ.FT.).
 PROVIDE EXISTING HYDRAULIC NAMEPLATE DESIGN DATA ON
 PLANS.
  
 SHEET FP-01 INDICATES A DESIGN AREA OF 1500 SQUARE
 FEET. THE ROOF SECTION ON SHEET FP-02 APPEARS TO HAVE A
 PITCH GREATER THAN 1 IN 6 AND WOULD REQUIRE THE DESIGN
 AREA TO BE INCREASED BY 30 PERCENT TO 1950 SQUARE FEET.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-05 Cont ID  
Sent By jwitmer Date 2011-12-05 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2011-10-26 Time 08:12 Sent To  
Notes
2011-10-27 08:13:50C8

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-10-28 Cont ID  
Sent By lwagner Date 2011-10-28 Time 14:10 Rev Time 0.00
Received By lwagner Date 2011-10-28 Time 13:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-12-02 Cont ID  
Sent By astelly Date 2011-12-02 Time 15:04 Rev Time 0.00
Received By astelly Date 2011-12-02 Time 15:04 Sent To  
Notes
***NONE***