Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-21 Cont ID  
Sent By rmcdouga Date 2011-10-21 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2011-10-20 Time 10:37 Sent To  
Notes
2011-10-20 10:40:15*****************EXPEDITED****************
 GAVE TO ROBBIE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-10-21 Cont ID  
Sent By rmcdouga Date 2011-10-21 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2011-10-21 Time 08:06 Sent To  
Notes
2011-10-21 08:24:03MECHANICAL PROVISO
  
 1) PLENUM AT MECHANICAL CLOSET IS REQUIRED BY FBCM
 602.2.1 TO HAVE A PLENUM RATED NON-COMBUSTIBLE DOOR.
  
 2) DUCT SMOKE DETECTORS ARE REQUIRED ON SUPPLY AIR
 SYSTEMS IN ACCORDANCE WITH FBCM 602.
  
 3) ACCESS SHALL BE PROVIDED TO DUCT SMOKE DETECTORS FOR
 INSPECTION AND MAINTENANCE PER FBCM 606.3.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE ROOF MOUNTED ACU
 STANDS. PROVIDE ENGINEERING FOR THE ANCHORING OF THE
 STANDS INCLUDING THE SUBSTRATE TO WHICH THE STANDS ARE
 ATTACHED IN COMPLIANCE WITH FBCM 301.12.