| Plan Review Stops For Permit 11100420 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2012-02-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-27 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-27 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2012-02-27 14:23:39 | SCOPE OF WORK WAS CHANGED TO REPLACEMNET OF THE NEW | | | EXTERIOR DOOR ONLY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2012-02-13 08:08:29 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | | THE EXTERIOR DOOR AS REQUIRED BY DCA RULE 9N-3. THE | | | ONES THAT WERE SUBMITTED HAVE BEEN SUPERSEDED. SEE | | | COMMENT NUMBER 2 FROM FIRST REVIEW. THE CURRENT | | | MIAMI-DADE NOA CAN BE DOWNLOADED AT THIS WEBSITE | | | HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP | | | | | | 2) SPECIFY THE SIZE AND LOCATION OF THE NEW DOOR. FBC | | | R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-11-14 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-11-14 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2011-11-14 15:01:42 | 2007 FBC W/2009 REVISIONS | | | REBUILD AND ENCLOSE EXISTING OPEN PORCH | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | | THE WINDOWS, STORM PANELS AND ROOFING MATERIAL AS | | | REQUIRED BY DCA RULE 9N-3. | | | | | | 2) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | | THE EXTERIOR DOOR AS REQUIRED BY DCA RULE 9N-3. THE | | | ONES THAT WERE SUBMITTED HAVE BEEN SUPERSEDED. | | | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 106.3.3 | | | | | | 4) ON SHEET A-2 THE ROOF AND WALL COMPONENT AND | | | CLADDING PRESSURES ARE TOO LOW FOR EXPOSURE CATEGORY C. | | | SEE ASCE7-05 AND FBCR TABLES R301.2(2) & R301.2(3). | | | PLEASE CORRECT. | | | | | | 5) THE DRYER IS REQUIRED TO BE VENTED TO THE OUTSIDE OF | | | THE BUILDING PER FBCR M1502.1. | | | | | | 6) SPECIFY THE UNDER FLOOR INSULATION REQUIRED BY FBCR | | | N1105.AB.1. | | | | | | 7) INDICATE ON THE PLANS HOW COMPLIANCE WITH FBC R408.1 | | | FOR UNDER-FLOOR SPACE VENTILATION IS ACHIEVED. | | | | | | 8) INDICATE ON THE PLANS HOW COMPLIANCE WITH FBC R | | | 408.4 FOR ACCESS TO UNDER-FLOOR SPACE IS ACHIEVED. | | | | | | 9) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | | BATHROOM ADDITION AS REQUIRED BY FBCR N1100.03. | | | | | | 10) PLEASE SUBMIT A RESPONSE LETTER SPECIFYING HOW THE | | | PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-10-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-10-27 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-10-27 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2011-10-27 16:18:35 | INTERCONNECTED SMOKE AND CARBON MONOXIDE ALARMS ARE | | | REQUIRED WITHIN THE EXISTING RESIDENCE AS NOTED ON THE | | | PLANS. SEE FLORIDA BUILDING CODE RESIDENTIAL SECTION | | | R313. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-02-08 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2012-02-08 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2012-02-08 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2012-02-08 15:33:20 | REVISION (2/8/12) TO PREVIOUS SCOPE OF WORK. NO LONGER | | | REMODELING BATHROOM, NEW SCOPE OF WORK ONLY INCLUDES | | | REPLACEMENT OF EXTERIOR DOOR. | | | | | | QUESTIONS/COMMENTS, CONTACT FRIEDERIKE MITTNER, | | | 561.822.1457. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-10-31 |
|
|
Cont ID |
|
| Sent By |
jpapa |
Date |
2011-10-31 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
jpapa |
Date |
2011-10-31 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2011-10-31 15:49:08 | FAILED. | | | | | | THE SUBJECT PROPERTY IS LOCATED ON THE WEST PALM BEACH | | | REGISTER OF HISTORIC PLACES. THEREFORE, A CERTIFICATE | | | OF APPROPRIATENESS IS REQUIRED FOR ANY EXTERIOR | | | MODIFICATIONS. PLEASE CONTACT JILLIAN PAPA, HISTORIC | | | PRESERVATION PLANNNER AT 561-822-1454 FOR APPLICATION | | | REQUIREMENTS. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-02-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-27 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-22 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2012-02-23 08:16:07 | SENT TO R MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-11-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-11-14 |
Time |
16:55 |
Rev Time |
|
| Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2012-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2012-02-13 08:05:14 | THE SCOPE OF WORK WAS CHANGED TO ONLY REPLACING AN | | | EXTERIOR DOOR. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2011-11-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-11-08 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-11-08 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2011-11-08 16:56:04 | THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM BEACH | | | COUNTY FOR IMPACT FEES BEFORE THE PERMIT IS ISSUED. THE | | | PLANS WILL BE STAMPED BY THE COUNTY AND RETURNED TO THE | | | CITY OF WEST PALM BEACH WITH A COPY OF THE PAID IMPACT | | | FEE RECEIPT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2011-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-11-14 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-11-14 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2011-11-14 14:18:18 | NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL | | | CONTRACTOR WAS SIGNED ON TO PERMIT APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2012-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-13 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2012-02-13 08:06:40 | SCOPE OF WORK WAS CHANGED TO ONLY REPLACING AN EXTERIOR | | | DOOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2011-11-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-11-08 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-11-08 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2011-11-08 16:55:03 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) PROVIDE PROPER VENTING FOR SHOWER AND LAVATORY. FBCR | | | P3101.2 & P3108.2 | | | | | | 2) ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. THE | | | TOILET CAN NOT BE WET-VENTED BY THE WASHING MACHINE | | | VENT. SEE FBCR P3108.1 AND P3108.2. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-02-08 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2012-02-08 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2012-02-08 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-10-31 |
|
|
Cont ID |
|
| Sent By |
jpapa |
Date |
2011-10-31 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
jpapa |
Date |
2011-10-31 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2011-10-31 15:45:04 | FAILED. | | | | | | PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY?S ADDRESS AND LEGAL DESCRIPTION. | | | FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA, | | | HISTORIC PRESERVATION PLANNER AT 561-822-1454. |
|
|