| 2011-10-25 15:38:00 | BUILDING PLAN REVIEW |
| | PERMIT: 11100408 |
| | ADD: 601 CLEARWATER PARK |
| | CONT: TURNER CONSTRUCTION |
| | TEL: (305)219-9689 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW FLORIDA SPECIFIC REQUIREMENTS FOR |
| | ACCESSIBILITY 2007/09 FBC-B 11-4.1.6(2) |
| | LTERATIONS TO AN AREA CONTAINING A PRIMARY FUNCTION. IN |
| | ADDITION TO THE REQUIREMENTS OF SECTION 11-4.1.6(1), AN |
| | ALTERATION THAT AFFECTS OR COULD AFFECT THE USABILITY |
| | OF OR ACCESS TO AN AREA CONTAINING A PRIMARY FUNCTION |
| | SHALL BE MADE SO AS TO ENSURE THAT, TO THE MAXIMUM |
| | EXTENT FEASIBLE, THE PATH OF TRAVEL TO THE ALTERED AREA |
| | AND THE RESTROOMS, TELEPHONES, AND DRINKING FOUNTAINS |
| | SERVING THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND |
| | USABLE BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH |
| | ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL |
| | ALTERATIONS TIN TERMS OF COST AND SCOPE. |
| | |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION |
| | TO THE PRIMARY FUNCTION AREA. |
| | |
| | DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | |
| | (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE |
| | PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. |
| | |
| | (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | |
| | (I) AN ACCESSIBLE ENTRANCE; |
| | |
| | (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| | |
| | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM: |
| | |
| | (IV) ACCESSIBLE TELEPHONES; |
| | |
| | (V) ACCESSIBLE DRINKING FOUNTAINS; AND |
| | |
| | (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH |
| | AS PARKING, STORAGE, AND ALARMS. |
| | |
| | 1A) IN THE MEETING WITH THE DESIGN TEAM AND THE |
| | BUILDING DEPARTMENT AN ACCESSIBLE ENTRANCE WAS |
| | DISCUSSED. SHEET A0.10 SITE PLAN DOES SHOW A NEWLY |
| | DESIGNED EGRESS RAMP FROM THE ACCESSIBLE PARKING ACCESS |
| | AISLE. THE BOTTOM LANDING OF THE RAMP IS INDICATED AS A |
| | 5'-0" AS REQUIRED FOR 90 DEGREE TURNS BUT IS NOT IN |
| | COMPLIANCE WITH 11-4.8.4 (2) THAT REQUIRES THE BOTTOM |
| | LANDING TO BE 72 INCHES OF STRAIGHT AND LEVEL |
| | CLEARENCE. |
| | |
| | 1B) THE OTHER ISSUE IN AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREAS PLEASE REVIEW SHEET A.100 DOOR # 22 TO |
| | TTHE LEFT OF ROOM 01-01 (RECEPTION) IS MISSING THE |
| | REQUIRED 18 INCHES ON THE LEFT SIDE OF THE DOOR LATCH, |
| | PLEASE REVIEW 11-4.13.6 MANEUVERING CLEARENCES AT |
| | DOORS. |
| | |
| | 2A) SHEET A.100 & A.301 THE LIFE SAFETY PLAN INDICATE |
| | TWO STAIRWAYS FROM THE SECOND STORY A REAR STAIRWAY |
| | THAT IS ENCLOSED AND A MONUMENTAL STAIR IN THE FRONT OF |
| | THE BUILDING NOT ENCLOSED. THIS BUILDING WAS BUILT IN |
| | 1982 UNDER THE 1978 STANDARD BUILDING CODE IN REVIEWING |
| | THE CODE REQUIREMENTS THEN AND NOW THERE SHOULD HAVE |
| | BEEN TWO ENCLOSED EXIT STAIRS LEADING TO THE EXTERIOR |
| | OF THE BUILDING. THE 1978 CODE (1103.2(2) DID ALLOW FOR |
| | A SINGLE ENCLOSED STAIR FOR 2 STORY BUSINESS |
| | OCCUPABNCIES FOR 3500 SQ FT AND OCCUPANT LOAD NOT MORE |
| | THAN 40 OCCUPANTS. THIS BUILDING DID NOT MEET THIS |
| | EXCEPTION IN AREA NOR OCCUPANT LOAD. THE MONUMENTAL |
| | STAIR UNDER THE 1978 SBC SECTION 1107.1 ALSO REQUIRED |
| | THAT SUCH STAIR WAS NOT PART OF A REQUIRED PART OF THE |
| | BUILDING EXIT FACILITIES AND SUCH STAIRS ARE NOT |
| | CONNECTED WITH CORRIDORS PROVIDING ACCESS TO EXITS. |
| | |
| | 2B) THE SECOND ISSUE IS WITH THE ELEVATOR LANDS IN THE |
| | LOBBY OR RECEPTION AREA WHICH IS STILL WITHIN THE |
| | PROPOSED EXIT. THE 1987 CODE 1106(F) EXIT ENCLOSURES |
| | ARE TO HAVE ONLY THE NECCESSAARY OPENINGS SUCH AS |
| | DOORWAYS TO PROTECT THE STAIRWAY FROM THE REMANDER OF |
| | THE BUILDING. TODAYS CODE LANGUAGE IS QUITE CLEAR: |
| | 2007/09 FBC-B 1020.1.1 ELEVATORS SHALL NOT OPEN INTO AN |
| | EXIT ENCLOSURE. |
| | |
| | 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS |
| | THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR |
| | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY |
| | FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 712. THERE SHALL BE NO PENETRATIONS OR |
| | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | NOTE: IT IS NOTED BY E-MAILS THEIR IS A WINDOW BETWEEN |
| | THE LOBBY AREA AND RECEPTIONIST DESK WITH A FIRE |
| | SHUTTER. PLEASE NOTE ON PLANS, IS THE FIRE SHUTTER |
| | CONTROLED BY A FUSABLE LINK OR ENGAGED BY THE FIRE |
| | ALARM? |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |