Plan Review Details - Permit 11100384
Plan Review Stops For Permit 11100384
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 10:03 Rev Time 0.33
Received By jwitmer Date 2011-11-14 Time 10:03 Sent To  
Notes
2011-11-14 10:20:24BUILDING PROVISO:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT
 OF RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 REVISION REQUIRED FOR TRAY CEILING:
 1) THE DETAIL SHOWN ( TRAY AT RIGHT ANGLE TO BAR JOIST)
 VERTICAL LEG OF THE TRAY CEILING TO
 BE EVERY 24 INCHES ON CENTER, WHAT IS THE ATTACHMENT TO
 THE BAR JOIST.
  
 2) WHEN THE TRAY CEILING FRAMING IS RUNNING PARALLEL TO
 THE BAR JOIST WHICH ARE SPACED
 ANYWHERE FROM 4'-0" TO 6'-0" ON CENTER, HOW WILL THE
 TRAY CEILING MEMBERS BE
 ATTACHED IF THERE IS NO BAR JOIST DIRECTLY ABOVE, THERE
 IS NO STRUCTURAL SUPPORT?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-10-19 Cont ID  
Sent By jwitmer Date 2011-10-19 Time 09:04 Rev Time 0.70
Received By jwitmer Date 2011-10-19 Time 09:04 Sent To  
Notes
2011-10-19 09:18:14BUILDING PROVISO:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT
 OF RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 REVISION REQUIRED FOR TRAY CEILING:
 1) THE DETAIL SHOWN ( TRAY AT RIGHT ANGLE TO BAR JOIST)
 VERTICAL LEG OF THE TRAY CEILING TO
 BE EVERY 24 INCHES ON CENTER, WHAT IS THE ATTACHMENT TO
 THE BAR JOIST.
  
 2) WHEN THE TRAY CEILING FRAMING IS RUNNING PARALLEL TO
 THE BAR JOIST WHICH ARE SPACED
 ANYWHERE FROM 4'-0" TO 6'-0" ON CENTER, HOW WILL THE
 TRAY CEILING MEMBERS BE
 ATTACHED IF THERE IS NO BAR JOIST DIRECTLY ABOVE, THERE
 IS NO STRUCTURAL SUPPORT?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-27 Cont ID  
Sent By rlecky Date 2011-10-27 Time 09:20 Rev Time 0.00
Received By rlecky Date 2011-10-27 Time 09:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-15 Cont ID  
Sent By wjolin Date 2011-11-15 Time 11:17 Rev Time 0.00
Received By wjolin Date 2011-11-15 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-25 Cont ID  
Sent By wjolin Date 2011-10-25 Time 10:16 Rev Time 0.00
Received By wjolin Date 2011-10-25 Time 09:50 Sent To  
Notes
2011-10-25 10:16:332021 PALM BEACH LAKES BOULEVARD
 PERMIT #11100384
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL STORAGE ROOMS SHALL BE PROTECTED WITH A 1-HOUR
 FIRE RATED ENCLOSURE OR AUTOMATIC FIRE SPRINKLERS PER
 LIFE SAFETY CODE SECTION 37.3.2 AND SECTION 8.7 OF NFPA
 101 WITH FLORIDA AMENDMENTS.
  
 EXIT ACCESS IN CLASS B MERCATILE OCCUPANCIES IS
 PERMITTED TO PASS THROUGH STOREROOMS PROVIDED THE
 STOREROOM DOOR IS NOT SUBJECT TO LOCKING AND A 44-INCH
 WIDE AISLE IS PROVIDED FROM THE ROOM ENTRANCE DOOR TO
 THE EXIT DOOR. THE AISLE SHALL BE IDENTIFIED WITH FIXED
 BARRIERS TO MAINTAIN AN UNOBSTRUCTED EGRESS PATH.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-15 Cont ID  
Sent By wjolin Date 2011-11-15 Time 11:17 Rev Time 0.00
Received By wjolin Date 2011-11-08 Time 16:55 Sent To  
Notes
2011-11-08 16:55:32SENT TO B2 SHELF FOR REVIEWS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-08 Cont ID  
Sent By jgomez Date 2011-11-01 Time 16:33 Rev Time 0.00
Received By jgomez Date 2011-10-18 Time 16:03 Sent To  
Notes
2011-11-08 16:34:36LAST REVIEW DONE ON 11/01/11 BY ZONING. JG.
2011-10-18 16:10:20****************EXPEDITED********************
 B--3

Review Stop Z ZONING
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By jroach Date 2011-11-01 Time 09:25 Rev Time 0.00
Received By jroach Date 2011-11-01 Time 09:25 Sent To  
Notes
***NONE***