Plan Review Details - Permit 11100320
Plan Review Stops For Permit 11100320
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-26 Cont ID  
Sent By jgomez Date 2011-10-26 Time 11:54 Rev Time 0.00
Received By jgomez Date 2011-10-26 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-18 Cont ID  
Sent By jgomez Date 2011-10-18 Time 16:46 Rev Time 0.00
Received By jgomez Date 2011-10-14 Time 16:44 Sent To  
Notes
2011-10-14 16:44:46GAVE TO JULIO

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-10-26 Cont ID  
Sent By jgomez Date 2011-10-26 Time 11:54 Rev Time 0.00
Received By jgomez Date 2011-10-26 Time 11:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-10-18 Cont ID  
Sent By jgomez Date 2011-10-18 Time 16:46 Rev Time 0.00
Received By jgomez Date 2011-10-18 Time 16:08 Sent To  
Notes
2011-10-18 16:51:25MECHANICAL (A/C) REVISION CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- REVISE EQUIPMENT SCHEDULE SHOWN ON PLANS SUBMITTED:
  
 A) AHU MODEL AND CONDITIONER MODEL SHOWN ON SCHEDULE
 DON'T CORRESPOND TO 1 TON UNIT.
  
 B) COMPLETE ALL THE INFORMATION ON THE SCHEDULE.
  
 C) REVISE THE HEAT CAPACITY ACCORDING TO THE UNIT SIZE.
  
 D) REVISE THE LINE SIZES ACCORDING TO THE UNIT SIZE.
 SEC. 106.1.1 CITY AMENDMENTS TO FBC.
  
 2- REVISE THE EQUIPMENT SIZING CALCULATIONS TO SHOW NEW
 A/C SIZE. SEC. N1107.AB.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712