Plan Review Details - Permit 11100290
Plan Review Stops For Permit 11100290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 11:47 Rev Time 0.50
Received By jwitmer Date 2011-11-14 Time 11:46 Sent To  
Notes
2011-11-14 11:47:24BUILDING PROVISO:
 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 11:36 Rev Time 0.55
Received By jwitmer Date 2011-11-14 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-10-17 Cont ID  
Sent By jwitmer Date 2011-10-17 Time 14:37 Rev Time 0.77
Received By jwitmer Date 2011-10-17 Time 14:00 Sent To  
Notes
2011-10-17 14:37:34712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-19 Cont ID  
Sent By rlecky Date 2011-10-19 Time 09:13 Rev Time 0.00
Received By rlecky Date 2011-10-19 Time 08:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By wjolin Date 2011-11-14 Time 09:05 Rev Time 0.00
Received By wjolin Date 2011-11-14 Time 08:48 Sent To  
Notes
2011-11-14 09:01:162275 PALM BEACH LAKES BOULEVARD - SUITE "A"
 PERMIT #11100290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FRONT ENTRY THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-26 Cont ID  
Sent By wjolin Date 2011-10-26 Time 13:21 Rev Time 0.00
Received By wjolin Date 2011-10-26 Time 11:59 Sent To  
Notes
2011-10-26 13:17:012275 PALM BEACH LAKES BOULEVARD - SUITE "A"
 PERMIT #11100290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER TABLE 6.1.14.4.1(B) OF NFPA 101 - FLORIDA EDITION,
 THE FIRE RATED SEPARATION BETWEEN BUSINESS USE AND
 MERCANTILE USE SHOULD BE 2-HOURS.
  
 VERIFY HOW DOOR LOCKS/LATCHES ON EXISTING ENTRY
 DOORS.THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN
 THE DOOR WITH NOT MORE THAN ONE RELEASING OPERATION.
 THE RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 NOTE: THE PROPOSED ASSEMBLY USE IN PHASE II WILL
 REQUIRE A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND
 AN AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2011-11-09 Time 09:26 Sent To  
Notes
2011-11-09 09:26:33B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-01 Cont ID  
Sent By hmoser Date 2011-11-01 Time 13:16 Rev Time 0.00
Received By hmoser Date 2011-11-01 Time 13:16 Sent To  
Notes
2011-10-14 10:23:53INCOMING SENT TO B-5 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By hmoser Date 2011-11-01 Time 13:15 Rev Time 0.00
Received By hmoser Date 2011-11-01 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-10-25 Cont ID  
Sent By lwagner Date 2011-10-25 Time 12:48 Rev Time 0.00
Received By lwagner Date 2011-10-25 Time 12:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-10-24 Cont ID  
Sent By eschneid Date 2011-10-24 Time 16:06 Rev Time 0.50
Received By eschneid Date 2011-10-24 Time 16:06 Sent To  
Notes
***NONE***