| Plan Review Stops For Permit 11100290 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2011-11-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-11-14 |
Time |
11:47 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2011-11-14 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2011-11-14 11:47:24 | BUILDING PROVISO: | | | 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE | | | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL | | | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE | | | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY | | | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE | | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE | | | AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-11-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-11-14 |
Time |
11:36 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2011-11-14 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2011-10-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-10-17 |
Time |
14:37 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2011-10-17 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2011-10-17 14:37:34 | 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE | | | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL | | | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE | | | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY | | | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE | | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE | | | AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-10-19 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-10-19 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-10-19 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-11-14 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-11-14 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-11-14 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2011-11-14 09:01:16 | 2275 PALM BEACH LAKES BOULEVARD - SUITE "A" | | | PERMIT #11100290 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | FRONT ENTRY THUMB-TURN LOCK TO BE EQUIPPED WITH A | | | LOCK/UNLOCK INDICATOR. | | | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | | FEET ON CENTER. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-10-26 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-10-26 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-10-26 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2011-10-26 13:17:01 | 2275 PALM BEACH LAKES BOULEVARD - SUITE "A" | | | PERMIT #11100290 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER TABLE 6.1.14.4.1(B) OF NFPA 101 - FLORIDA EDITION, | | | THE FIRE RATED SEPARATION BETWEEN BUSINESS USE AND | | | MERCANTILE USE SHOULD BE 2-HOURS. | | | | | | VERIFY HOW DOOR LOCKS/LATCHES ON EXISTING ENTRY | | | DOORS.THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN | | | THE DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. | | | THE RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF | | | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING | | | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF | | | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE | | | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST | | | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA | | | EDITION 2007. | | | | | | NOTE: THE PROPOSED ASSEMBLY USE IN PHASE II WILL | | | REQUIRE A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND | | | AN AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-11-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-11-14 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-11-09 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-11-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-11-01 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-11-01 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2011-10-14 10:23:53 | INCOMING SENT TO B-5 BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2011-11-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-11-01 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-11-01 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-10-25 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-10-25 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-10-25 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2011-10-24 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2011-10-24 |
Time |
16:06 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2011-10-24 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|