Plan Review Details - Permit 11100232
Plan Review Stops For Permit 11100232
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2011-10-19 Cont ID  
Sent By rferguso Date 2011-10-19 Time 12:33 Rev Time 0.00
Received By mgonzale Date 2011-10-19 Time 10:57 Sent To  
Notes
2011-10-19 12:31:20 
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-11-09 Cont ID  
Sent By wjolin Date 2011-11-09 Time 15:41 Rev Time 0.00
Received By wjolin Date 2011-11-09 Time 11:26 Sent To  
Notes
2011-11-09 15:41:311 NORTH CLEMATIS STREET - SUITE #110
 PERMIT #11100232
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT ACCURATE AS-BUILTS AND HYDRAULIC
 CALCULATIONS*****
  
 FIRE PUMP APPEARS TO BE 750 GPM AT 80 PSI, NOT 500 GPM
 AT 125 PSI AS INDICATED ON PLANS. FIELD VERIFY.
  
 PLANS SHOW ALL BRANCH LINE PIPES TO BE 1-INCH; HOWEVER
 HYDRAULIC CALCULATIONS INDICATE PIPE SIZES TO BE
 1-1/4".
  
 THE HYDRAULIC CALCULATIONS INDICATE THE CROSS MAIN SIZE
 TO BE 4"; HOWEVER, THE PLANS INDICATE THE MAIN SIZE TO
 BE 1-1/2" FOR NODES 3 TO 1 TO TOR.
  
 THE POINT TO POINT HYDRAULIC CONNECTIONS NEED TO
 CORRECTED. NODE 100 SHOULD NOT CONNECT TO NODE 103.
 NODE 1 IS NOT CONNECTED TO NODE 3.
  
 THE LOCATION OF THE NODES LABELING THE PUMP, TOP OF
 RISER AND BOTTOM OF RISER ARE NOT SHOWN IN THE ACCURATE
 LOCATION.
  
 THE EXISTING SPRINKLER DESIGN APPEARS TO BE A GRID
 SYSTEM. THE SUBMITTED PLAN SHOWS A TREE SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-11-03 Cont ID  
Sent By wjolin Date 2011-11-03 Time 14:54 Rev Time 0.00
Received By wjolin Date 2011-11-03 Time 13:24 Sent To M
Notes
2011-11-03 14:54:271 NORTH CLEMATIS STREET - SUITE #110
 PERMIT #11100232
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL OF THE HYDRAULIC NODES ARE LABELED AS NUMBER 1.
  
 THE MIDDLE BRANCH LINE IN THE MAIN SEATING AREA IS NOT
 CONNECTED TO THE CROSS MAIN.
  
 IT APPEARS A SPRINKLER IS NEEDED IN THE DROP SOFFIT
 LOCATED NEAR THE EAST EXIT DOOR AS THE UPPER CEILING
 SPRINKLER SPRAY WOULD BE OBSTRUCTED.
  
 THE DRAWING SCALE IS INDICATED AS 3/16" = 1'-0". THE
 ACTUAL SCALE APPEARS TO BE 1/4"=1'-0".
  
 A SIX-FOOT DIAMETER FIXTURE (X3) IS SHOWN ON THE PLANS.
 ADDITIONAL SPRINKLERS MAY BE REQUIRED AROUND THE
 FIXTURE TO ACCOUNT FOR OBSTRUCTED SPRAY. PROVIDE DETAIL
 OR ADD SPRINKLERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-19 Cont ID  
Sent By rferguso Date 2011-10-19 Time 12:39 Rev Time 0.00
Received By rferguso Date 2011-10-19 Time 12:38 Sent To M
Notes
2011-10-19 12:37:361 NORTH CLEMATIS STREET SUITE #110
 PERMIT #11100232
 FIRE DEPARTMENT
  
 1 *THE AHJ IS THE CITY OF WEST PALM BEACH.
  
 2 *INDICATE IN DETAIL THE SCOPE OF WORK BEING
 PERFORMED,
 *THE NUMBER OF NEW SPRINKLERS BEING INSTALLED.
 *THE NUMBER OF SPRINKLERS BEING RELOCATED.
 *THE DIFFERENT TYPES (PENDENTS/UPRIGHTS) AND NUMERS OF
 SPRINKLERS BEING INSTALLED.
 *INDICATE ON THE PLAN LEGEND THE NUMBER OF RELOCATIONS
 AND INSALLATIONS OF SPRINKLERS.
 *SHOW INSTALLATION OF NEW PIPING AND NEW CALCULATIONS
 FOR ADDED SPRINKLER HEADS.
 *SHOW LEGEND AND WORK OF ALL EXISTING SPRINKLERS THAT'S
 BEING REMOVED OR PLUGED.
 3 *THE ADDRESS INCLUDING SUITE NUMBER, IF APPLICABLE
 MUST BE INCLUDED ON THE PLANS.
  
 CAPTAIN RONALD E. FERGUSON
 ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 OFFICE: (561- 804-4756)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-11-09 Cont ID  
Sent By wjolin Date 2011-11-09 Time 15:41 Rev Time 0.00
Received By wjolin Date 2011-11-08 Time 14:08 Sent To  
Notes
2011-11-08 14:09:10SENT TO WESLEY
 *************EXPEDITED******************

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-08 Cont ID  
Sent By lmartine Date 2011-11-08 Time 14:08 Rev Time 0.00
Received By lmartine Date 2011-11-02 Time 09:33 Sent To  
Notes
2011-11-02 09:33:21TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-31 Cont ID  
Sent By hmoser Date 2011-10-31 Time 14:16 Rev Time 0.00
Received By hmoser Date 2011-10-12 Time 15:42 Sent To  
Notes
2011-10-12 15:42:17TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-08 Cont ID  
Sent By hmoser Date 2011-11-08 Time 14:32 Rev Time 0.00
Received By hmoser Date 2011-11-08 Time 14:10 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-10-31 Cont ID  
Sent By hmoser Date 2011-10-31 Time 14:12 Rev Time 0.00
Received By hmoser Date 2011-10-31 Time 14:12 Sent To  
Notes
2011-10-31 14:16:26PROVIDE SPRINKLER PIPE AND PIPE SIZE ON PLANS.
 PROVIDE ADDRESS AND SUITE NUMBER ON THE PLANS
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]