Plan Review Details - Permit 11100211
Plan Review Stops For Permit 11100211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-13 Cont ID  
Sent By jwitmer Date 2012-07-13 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2012-07-13 Time 11:37 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-12-28 Cont ID  
Sent By jwitmer Date 2011-12-28 Time 14:47 Rev Time 0.55
Received By jwitmer Date 2011-12-28 Time 14:47 Sent To  
Notes
2011-12-28 14:55:44BUILDING PLAN REVIEW
 PERMIT: 11100211
 ADD: 1256 PALM BEACH LAKES BLVD
 CONT: GADSEN PROPERTY INVESTMENTS
 TEL: (800)294-5339
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) WAITING FOR DCA APPROVED PLANS, M. RUTLEDGE, INC
 RECEIVED LETTER HAS RECEIVED APPROVAL TO TAKE PART IN
 MANUFACTURED BUILDING PROGRAM.
 CONSTRUCTION OR MODIFICATION ON A MANUFACTURED BUILDING
 CAN NOT BEGIN UNTIL THE THIRD PARTY AGENCY HAS APPROVED
 THE PLANS IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE., STATEMENT FROM WITHIN
 APPROVAL LETTER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-18 Cont ID  
Sent By jwitmer Date 2011-10-18 Time 13:44 Rev Time 1.50
Received By jwitmer Date 2011-10-18 Time 12:07 Sent To  
Notes
2011-10-18 14:44:47BUILDING PLAN REVIEW
 PERMIT: 11100211
 ADD: 1256 PALM BEACH LAKES BLVD
 CONT: GADSEN PROPERTY INVESTMENTS
 TEL: (800)294-5339
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) 1805.2 DEPTH OF FOOTINGS. THE MINIMUM DEPTH OF
 FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE SHALL BE
 12 INCHES (305 MM).
  
 2) PLANS INDICATE THE USAGE OF PIER
 CONSTRUCTION1805.5.7 IS A PRESCRIPTIVE SECTION OF THE
 CODE THAT DOES ALLOW FOR NON-REINFORCED PIER
 CONSTRUCTION WITH LIMITATIONS TO 100 MPH OR LESS. THIS
 STRUCTURE IS LOCATED WITHIN A 140 MPH WIND ZONE.
  
 3) PLANS ARE DEFICIENT IN PROVIDING EVIDENCE HOW THE
 SOIL ANCHORS WILL RESIST THE MOMENT OF OVERTURNING.
 FBC-B 1604.4 ANALYSIS. EVERY STRUCTURE SHALL BE
 DESIGNED TO RESIST THE OVERTURNING EFFECTS CAUSED BY
 THE LATERAL FORCES SPECIFIED IN THIS CHAPTER. SEE
 SECTION 1609 FOR WIND LOADS, AND SECTION 1610 FOR
 LATERAL SOIL LOADS. NO SOILS REPORTS WERE SUBMITTED
 INDICATING A SOILS ANALYSIS OF HOW LARGE THE SOILS
 ANCHOR FLUKES WOULD NEED TO BE OR THE DEPTH AT WHICH
 THE FLUKE WOULD NEED TO BE UNDER GROUND TO RESIST THE
 MOMENT OF OVERTURNING.
  
 4) THE PLANS DO NOT INDICATE IF THIS IS A MODULAR OR
 PREMANUFACTRUED BUILDING REGISTERED IN FLORIDA'S
 MANUFACTURED (MODULAR) BUILDING PROGRAM? THE REMAINDER
 OF THIS REVIEW WILL TAKE THE ASSUMPTION THIS STRUCTURE
 IS NOT REGISTERED AS PART OF THE DCA MANUFACTURED
 BUILDING PROGRAM.
  
 5) THIS STRUCTURE BEING A EXTERIOR COOLER-FREEZER WILL
 ALSO NEED TO PROVIDE PRODUCT TESTING REPORT AS PER RULE
 9N-3 (31)(G). TESTING REPORTS CAN EITHER BE A STATE
 WIDE APPROVAL OF A PRODUCT, MATERIAL OR SYSTEMOF
 CONSTRUCTION BY THE COMMISSION FOR ACCEPTANCE OF A
 PRODUCT ON A STATEWIDE OR REGIONAL BASIS CONSISTANT
 WITH AN EVALUATION CONDUCTED PURSUANT TO RULE
 9B-72.070. A LOCAL APPROVAL CAN ALSO BE OBTAINED IF NO
 STATE APPROVAL HAS BEEN ACHIEVED.
  
 6) PLANS DO NOT INDICATE ANY STAIRS TO GAIN ACCESS INTO
 THE STRUCTURE ITSELF, PLEASE REVIEW SECTION 1009.3
 EXCEPTION # 6 AND REQUIREMENTS THERE OF.
  
 7) SHEET S1 OF 4 FRONT ELEVATION PLEASE PROVIDE
 COMPLIANCE WITH 11-4.27 (1-4) CONTROLS AND OPERATING
 MECHANISMS.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-01-04 Cont ID  
Sent By rlecky Date 2012-01-04 Time 09:50 Rev Time 0.00
Received By rlecky Date 2012-01-04 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-18 Cont ID  
Sent By rlecky Date 2011-10-18 Time 08:19 Rev Time 0.00
Received By rlecky Date 2011-10-17 Time 16:59 Sent To  
Notes
2011-10-18 08:20:43PLEASE SUBMIT AN ELECTRIC PLAN FOR CONNECTION OF THE
 EQUIPMENT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-12-19 Cont ID  
Sent By wjolin Date 2011-12-19 Time 15:09 Rev Time 0.00
Received By wjolin Date 2011-12-19 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-17 Cont ID  
Sent By wjolin Date 2011-10-17 Time 14:37 Rev Time 0.00
Received By wjolin Date 2011-10-17 Time 13:58 Sent To  
Notes
2011-10-17 14:37:411256 PALM BEACH LAKES BOULEVARD
 PERMIT #11100211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ONE SET OF PLANS IS NOT SEALED BY THE ENGINEER.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER. EXTINGUISHER SHALL
 HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY
 A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE STAIR AND HANDRAIL DETAILS/INFORMATION.
  
 IS ANY INTERNAL LIGHTING BEING PROVIDED TO SERVICE THE
 EQUIPMENT?
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2012-07-23 Time   Rev Time 0.00
Received By rlecky Date 2012-07-11 Time 07:21 Sent To  
Notes
2012-07-12 07:24:13JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-31 Cont ID  
Sent By shill Date 2012-01-19 Time 12:39 Rev Time 0.00
Received By shill Date 2011-12-14 Time 13:45 Sent To  
Notes
2011-12-14 13:46:07C--24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-04 Cont ID  
Sent By lmartine Date 2011-11-02 Time 09:58 Rev Time 0.00
Received By lmartine Date 2011-10-12 Time 17:04 Sent To  
Notes
2011-10-12 17:04:34C24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-12-28 Cont ID  
Sent By jwitmer Date 2011-12-28 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2011-12-28 Time 14:48 Sent To  
Notes
2011-12-28 14:49:40MU-2011-20812 $36.01 EXISTING CREDIT USE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-10-18 Cont ID  
Sent By jwitmer Date 2011-10-18 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2011-10-18 Time 13:38 Sent To  
Notes
2011-10-18 13:38:41BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10/19/11 SPOKE WITH MICHELLE AT THE PROPERTY APPRAISERS
 OFFICE AND FEES WILL BE ASSESSED ON THE 8X18 STRUCTURE
 THAT PRODUCES AND SELLS ICE, MICHELLE INDICATED THE
 IMPACT FEES WILL BE $1,509.91DUE BEFORE THE ISSUANCE OF
 THE PERMIT.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-10-27 Cont ID  
Sent By lwagner Date 2011-10-27 Time 10:26 Rev Time 0.00
Received By lwagner Date 2011-10-27 Time 10:11 Sent To  
Notes
2011-10-27 10:27:08BACKFLOW PROTECTION REQUIRED

Review Stop Z ZONING
Rev No 3 Status P Date 2012-07-23 Cont ID  
Sent By eschneid Date 2012-07-23 Time   Rev Time 0.00
Received By mdekle Date 2012-07-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2012-01-19 Cont ID  
Sent By astelly Date 2012-01-19 Time 11:58 Rev Time 0.00
Received By astelly Date 2012-01-19 Time 11:58 Sent To  
Notes
2012-01-19 12:00:43AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 ADDITIONAL PARKING BAYS WILL HAVE TO BE RE-STRIPED TO
 ACHIEVE THE REQUIRED 89 PARKING SPACES FOR THE COMPLEX.
 PLEASE REVISE THE SITE PLAN ACCORDINGLY.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-11-02 Cont ID  
Sent By astelly Date 2011-11-02 Time 16:33 Rev Time 0.00
Received By astelly Date 2011-11-02 Time 16:33 Sent To  
Notes
2011-11-02 16:34:32AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 THE VENDING MACHINE CANNOT BE CONSTRUCTED IN THE
 PROPOSED LOCATION. THE EXISTING RETAIL USES REQUIRE 87
 PARKING SPACES AND THE ICE VENDING MACHINE WILL REQUIRE
 TWO (2) ADDITIONAL SPACES. THE SITE PLAN SHOWS A TOTAL
 OF 84 SPACES. SO THE VENDING MACHINE WILL HAVE TO BE
 RELOCATED ELSEWHERE ON THE PROPERTY; AND THE ADDITIONAL
 PARKING WILL HAVE TO BE CONSTRUCTED.
  
 SEPARATE PERMITS WILL HAVE TO BE OBTAINED FOR THE
 CONSTRUCTION OF THE ADDITIONAL PARKING AND THE PROPOSED
 SIGNAGE FOR THE VENDING MACHINE.
  