Plan Review Details - Permit 11100171
Plan Review Stops For Permit 11100171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-15 Cont ID  
Sent By shill Date 2011-11-15 Time 09:34 Rev Time 0.00
Received By shill Date 2011-11-15 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-21 Cont ID  
Sent By shill Date 2011-10-21 Time 15:17 Rev Time 0.00
Received By shill Date 2011-10-21 Time 15:17 Sent To Z
Notes
2011-11-01 17:32:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 ***COURTESY RE-REVIEW AFTER OBTAINING MORE INFORMATION
 FROM OWNER AND ENGINEER***
  
 1. REVISE PLAN TO CLARIFY SCOPE OF WORK. SEE FBC
 EXISTING BUILDING, CLASSIFY WORK, SEE FBC101.5.
  
 2. REVISE APPLICATION TO INCLUDE STRUCTURAL WORK AND
 PLUMBING, OR HAVE PLUMBING CONTRACTOR APPLY FOR
 SEPARATE PERMIT WITH DRAINAGE CALCS (SEE FIRST COMMENT
 LIST REGARDING DRAINAGE CALCS).
  
 3. PANIC HARDWARE REQUIRED FOR ASSEMBLY OCCUPANCY, SEE
 FBC EXISTING BUILDING 302.1, 705.4.4, 705.4.4.1. A
 COMPREHENSIVE CHECKLIST CANNOT BE PROVIDED AT THIS TIME
 DUE TO INSUFFICIENT INFORMATION ON THE PLAN. THE DOOR
 PRODUCT APPROVALS DO NOT INCLUDE PANIC HARDWARE, PLEASE
 ADDRESS.
  
  
  
  
2011-10-21 16:29:09****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE CLARIFY SCOPE OF WORK. APPLICATION STATES
 THAT THIS PERMIT IS FOR DOORS AND WINDOWS, BUT THE
 PLANS SHOW ROOF DRAINS, NEW SCUPPERS, ETC. REVISE
 PERMIT APPLICATION AND/OR PLAN TO CLEARLY SHOW SCOPE.
  
 2. SEE FBC PLUMBING TABLE 1106.7 (PER FBC 1503.4) AND
 SHEET A1, ROOF STORM DRAIN CHART. SIZING APPEARS
 INCORRECT. NOTE THAT "HEAD" IN THE CHART REFERS TO
 HYDRAULIC HEAD, TO BE MEASURED 6' FROM THE SCUPPER, PER
 PLUMBING CODE COMMENTARY.
  
 3. OUR RECORDS SHOW THAT THIS ROOF HAS OBTAINED A
 CERTIFICATE OF COMPLETION FOR A REROOF WITH PROVISO
 THAT SCUPPERS AND ROOF DRAINS TO BE ON SEPARATE PERMIT,
 BUT ENGINEER OF RECORD STATED THAT THE ROOF WAS
 PATCHED. PLEASE ADDRESS ROOF DRAINAGE AND CONFIRM THAT
 THE ROOF CURRENTLY HAS POSITIVE DRAINAGE.
  
 4. APPLICATION STATES THAT FOUR 52" COLUMNS ARE TO BE
 INSTALLED, NOTHING WHICH FITS THIS DESCRIPTION IS ON
 THE PLAN.
  
 5. MORE INFORMATION REGARDING THE PROPOSED OCCUPANCY
 AND OCCPUANT LOAD IN ORDER TO DETERMINE WHETHER OR NOT
 PANIC DEVICES ARE REQUIRED ON THE DOORS. EITHER PROVIDE
 A LIFE SAFETY PLAN OR, ALTERNATIVELY, INCLUDE PANIC
 DEVICES ON THE DOOR SCHEDULE AND PRODUCT APPROVALS
 WHICH INCLUDE PANIC DEVICES.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-09 Cont ID  
Sent By wjolin Date 2011-11-09 Time 11:23 Rev Time 0.00
Received By wjolin Date 2011-11-09 Time 11:22 Sent To B
Notes
2011-11-09 11:23:21NOTE: BUILDING WILL BE AN EMPTY SHELL SPACE; OWNER TO
 SUBMIT SEPARATE PLANS FOR FUTURE TENANT BUILD-OUT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-03 Cont ID  
Sent By wjolin Date 2011-11-03 Time 11:18 Rev Time 0.00
Received By wjolin Date 2011-11-03 Time 10:54 Sent To  
Notes
2011-11-03 11:18:151600 NORTH DIXIE HIGHWAY
 PERMIT #11100171
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE ADDITIONAL INFORMATION AS REQUESTED IN THE BLDG
 DEPARTMENT COMMENTS. AT THIS TIME A COMPLETE REVIEW
 CANNOT BE CONDUCTED.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 NOTE: THERE IS AN EXISTING OPEN PERMIT (#10090416) FOR
 A POOL HALL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-15 Cont ID  
Sent By shill Date 2011-11-15 Time 09:34 Rev Time 0.00
Received By shill Date 2011-11-04 Time 15:34 Sent To  
Notes
2011-11-04 15:34:42TO LW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-04 Cont ID  
Sent By shill Date 2011-11-03 Time 15:13 Rev Time 0.00
Received By shill Date 2011-10-12 Time 10:01 Sent To  
Notes
2011-11-01 14:57:3611/1 TO FIRE
  
2011-10-24 10:18:4210/24 TO ZONING
  
2011-10-12 10:03:43MISC. #1

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-11-08 Cont ID  
Sent By lwagner Date 2011-11-08 Time 14:58 Rev Time 0.00
Received By lwagner Date 2011-11-08 Time 14:46 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-10-28 Cont ID  
Sent By lwagner Date 2011-10-28 Time 10:54 Rev Time 0.00
Received By lwagner Date 2011-10-28 Time 09:34 Sent To  
Notes
2011-10-28 10:48:53FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. PLANS ARE UNCLEAR AS TO THE ROOF DRAINS. IF THEY ARE
 NOT EXISTING, PLUMBING DRAWINGS WILL BE REQUIRED TO
 SHOW PIPEING FOR ROOF DRAINS.
  
 2. SEE FBC PLUMBING TABLE 1106.7 , ROOF STORM DRAIN
 CHART. SIZING APPEARS
 INCORRECT. NOTE THAT "HEAD" IN THE CHART REFERS TO
 HYDRAULIC HEAD, TO BE MEASURED 6' FROM THE SCUPPER, PER
 PLUMBING CODE COMMENTARY.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2011-10-27 Cont ID  
Sent By astelly Date 2011-10-27 Time 14:52 Rev Time 0.00
Received By astelly Date 2011-10-27 Time 14:52 Sent To  
Notes
***NONE***