| 2011-11-04 17:34:55 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | **NOTE: THIS MAY BE RECORDED A TIME OF PERMIT PICK UP. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL EXTERIOR DOORS AS SHOWN ON PLANS, INCLUDING THE |
| | SHED DOUBLE DOORS. |
| | |
| | B) ALL WINDOWS AS SHOWN ON PLANS. INCLUDING THE LARGE |
| | FIXED WINDOW SHOWN ON WEST ELEVATION ON SHEET A-1. |
| | |
| | C) ALL STRUCTURAL DOOR/WINDOW MULLIONS AS SHOWN ON |
| | PLANS. AND, CLEARLY SELECT MULLION SIZE FOR WINDOW AND |
| | DOOR TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF |
| | SEC. R301.2.1.4.3. SEE LARGE FIXED WINDOW ON WEST |
| | ELEVATION. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS/DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER |
| | PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. THIS |
| | APPLIES TO STRUCTURAL CONNECTORS ONLY. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 4- DEMOLITION NOTE #3 ON THE COVER SHEET CALLS FOR |
| | REMOVAL OF SCREEN AT CRAWL SPACE. NOTE #9 ON SHEET A-1 |
| | CALLS FOR NEW CRAWL SPACE OPENING ON NORTH WALL. |
| | PROVIDE COMPLETE INFORMATION SHOWING HOW COMPLYING WITH |
| | THE UNDER FLOOR SPACE VENTILATION REQUIREMENTS AS |
| | REQUIRED BY SEC. R408. SEE SEC. R408.1 FOR VENTILATION |
| | CALCULATIONS AND LOCATION OF OPENINGS. REVISE PLANS AS |
| | REQUIRED. |
| | |
| | ***NOTE: REVISE/COORDINATE WITH MECHANICAL PLAN. |
| | EXISTING A/C CONDENSER UNITS WILL BLOCK THE VENTILATION |
| | OPENING. |
| | |
| | 5- PROVIDE COMPLETE INFORMATION FOR FIREPLACE UNDER A |
| | SEPARATE PERMIT. SEE NOTE #15 ON SHEET A-1. THIS WORK |
| | IS NOT INCLUDED ON THIS PLANS. |
| | |
| | 6- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC. |
| | R313.4. |
| | |
| | 7- ENGINEER SIGNING AND SEALING THE STRUCTURAL DRAWINGS |
| | TO PROVIDE HIS NAME AND LICENSE NUMBER AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |