Plan Review Details - Permit 11100141
Plan Review Stops For Permit 11100141
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-03-14 Cont ID  
Sent By jwitmer Date 2012-03-14 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2012-03-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-11-28 Cont ID  
Sent By jwitmer Date 2011-11-28 Time 14:48 Rev Time 0.55
Received By jwitmer Date 2011-11-28 Time 11:16 Sent To  
Notes
2011-11-28 14:52:22BUILDING PLAN REVIEW
 PERMIT: 11100141
 ADD: 4275 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)743-8066
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW PLEASE SEE FIRST REVIEW NO NEW COMMENTS> JW
 ACTION: DENIED
  
 1) SHEET S2 INDICATES A "B" EXPOSURE AND ASSOCIATED
 PRESSURES, FBC-B 1609.4.3 PLEASE SEE THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF
 EXPOSURE C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET
 (182.9 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 PRESSURES ARE LOW FOR "C" TYPE TERRAIN.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-07 Cont ID  
Sent By jwitmer Date 2011-10-18 Time 16:56 Rev Time 0.77
Received By jwitmer Date 2011-10-18 Time 15:03 Sent To  
Notes
2011-10-18 15:27:39BUILDING PLAN REVIEW
 PERMIT: 11100141
 ADD: 4275 45TH ST
 CONT: TBD
 TEL: (561)743-8066
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) A LICENSED CONTRACTOR IN THE CORRECT DISCIPLINES
 WILL NEED TO SIGN ONTO THE PERMIT LICENSURE AND
 INSURANCE VERIFIED BEFORE ISSUANCE OF THE PERMIT CAN
 OCCUR.
  
 2) SHEET A2.0 WIND DESIGN CRITERIA IS INDICATED AS A
 "C" EXPOSURE AND A MEAN ROOF HEIGHT OF 17.92 FT. THE
 PRESSURES ARE LOW, THEY APPEAR TO BE "B" ZONE
 PRESSURES.
 NOTE THE B ZONE PRESSURES HAVE MULTIPLIERS @ 15 FT=
 1.21 AND @ 20 FT= 1.29. ONCE PRESSURES ARE CORRECT A
 PERMIT MAY BE ISSUED WITHOUT THE PRODUCT APPROVALS.
 NOTE!!!!!!! WHEN PRODUCT APPROVALS ARE NOT SUBMITTED AS
 PART OF THE MAIN PERMIT PACKAGE AND THE PERMIT IS
 ISSUED, SEPARATE PERMITS WILL BE REQUIRED WITH
 ASSOCIATED
 REVIEWS AND FEES.
  
 3) MISSING PRODUCT APPROVALS:FL BLD CODE 1609.6.2.2
 COMPONENTS & CLADDING OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
 3A) ROOFING ASSEMBLIES,11/9/11NOTE, SPOKE WITH THE
 DESIGN TEAM TODAY (MIKE MUROFF & SCOTT PURDY, THE
 CARLISLE SURE WELD SYSTEM WILL COME IN UNDER A SEPERATE
 ROOFING PERMIT WITH ENHANCED FASTENING AND ENGINNERED
 PLANS.
 3B) GLAZED EXTERIOR DOORS & TRANSOM
 3C) STOREFRONT
 3D) DRIVE THRU WINDOW
 3E) EFIS WALL SYSTEMS
 3F)
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-15 Cont ID  
Sent By rlecky Date 2012-03-15 Time 09:11 Rev Time 0.00
Received By rlecky Date 2012-03-15 Time 08:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-19 Cont ID  
Sent By rlecky Date 2011-10-19 Time 13:48 Rev Time 0.00
Received By rlecky Date 2011-10-19 Time 12:10 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-03-26 Cont ID  
Sent By mgonzale Date 2012-03-26 Time   Rev Time 1.00
Received By mgonzale Date 2012-03-26 Time   Sent To  
Notes
2012-03-26 10:39:45PASSED WITH PROVISO:
  
 #1 DUMPSTER REVISION AND MODIFICATIONS TO ALLOW CITY OF
 WPB SANITATION TO CONTINUE SERVICE.
 UNDERSTANDING THIS WORK WILL BE PERFORMED UNDER A
 SEPARATE PERMIT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-12-13 Cont ID  
Sent By mgonzale Date 2011-12-13 Time   Rev Time 1.00
Received By mgonzale Date 2011-12-13 Time   Sent To  
Notes
2011-12-13 15:04:12RESPOND TO COMMENTS IN WRITING:
  
 #1 CITY OF WPB HAS A WM THAT RUNS THRU SITE
 (NORTH-SOUTH) PARALLEL TO THE THE EAST ROW LINE.
 PROVIDE LOCATION AND EASEMENT INFORMATION TO AVOID ANY
 CONFLICTS.
 CONTACT CITY OF WPB CAD GROUP - JANICE TARBILL FOR
 AS-BUILT PLANS.
  
 #2 PROVIDE ACCESSABLE ROUTE FOR SANITATION TRUCK
 ACCESSING DUMSPTER. (SEE NOTE 4)
 SANITATION:
 1. INTERIOR DIMENSIONS OF THE ENCLOSURE MUST BE A
 MINIMUM OF 12'-6" WIDE AND 12' DEEP. A CONCRETE PARKING
 STOP BAR 10' LONG MUST BE CENTERED (FROM GATES) AND
 INSTALLED 18" FROM THE BACK WALL. STEEL BARS WILL NEED
 TO BE DRILLED THRU THE STOP BAR AND INTO THE INTERIOR
 FLOOR OF THE ENCLOSURE TO STOP THE STOP BAR FROM MOVING
 WHEN THE DUMPSTER IS SET INSIDE.
 2. DUMPSTER ENCLOSURE MUST HAVE A MINIMUM OF 12'-6"
 OPENING BETWEEN THE GATE POSTS.
 3. IT IS STRONGLY SUGGESTED THAT YOU ADD A RECYCLING
 CENTER TO YOUR DUMPSTER ENCLOSURE, ESPECIALLY SINCE YOU
 WILL BE CHARGED FOR RECYCLING, WHETHER YOU USE IT OR
 NOT. A RECYCLING CENTER WILL CALL FOR A LARGER
 ENCLOSURE.
 4. THE OPENING OF THE DUMPSTER ENCLOSURE MUST BE ANGLED
 SO THAT A 40' LONG TRUCK WITH THE FORKS EXTENDED CAN
 APPROACH THE OPENING AND PICK UP THE DUMPSTER WITHOUT
 MAKING A SHARP TURN OR A THREE POINT TURN.
 5. THE TRUCK NEEDS TO HAVE NO LESS THAN A 26' HIGH
 VERTICAL CLEARANCE AREA FOR THE TRUCK TO PICK UP THE
 DUMPSTER. THIS IS THE CLEAR AREA OVER THE DUMPSTER AND
 WHERE THE TRUCK WILL BE STOPPED TO UNLOAD THE DUMPSTER.
 6. THE TRUCK NEEDS TO HAVE NO LESS THAN 14' HIGH
 VERTICAL CLEARANCE AND 12' HORIZONTAL CLEARANCES FOR
 THE TRUCK TO DRIVE THROUGH.
 7. NO FLOOR DRAIN TO THE SANITARY SEWER CAN BE
 INSTALLED IN THE DUMPSTER ENCLOSURE, UNLESS IT IS
 ROOFED SO NO RAIN WATER WILL GET INTO THE DRAIN.
 8. THE DUMPSTER ENCLOSURE MUST BE LOCATED TO ALLOW THE
 DUMP TRUCK TO BACK UP NO MORE THAN 50' STRAIGHT BACK
 AFTER RESETTING THE DUMPSTER IN THE ENCLOSURE.
  
 #3 PROVIDE DIMENSIONS TO EXISTING ENTRANCE AND EXIT
 DRIVEWAYS.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-10-17 Cont ID  
Sent By wjolin Date 2011-10-17 Time 13:24 Rev Time 0.00
Received By wjolin Date 2011-10-17 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-26 Cont ID  
Sent By jwitmer Date 2012-03-26 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2012-02-28 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-27 Cont ID  
Sent By shill Date 2011-12-21 Time 09:33 Rev Time 0.00
Received By shill Date 2011-10-12 Time 11:06 Sent To  
Notes
2011-10-12 11:06:42C--12

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-26 Cont ID  
Sent By ajones Date 2012-03-26 Time 10:45 Rev Time 0.00
Received By ajones Date 2012-03-26 Time 10:45 Sent To  
Notes
2012-03-26 10:50:013-26-12- THIS APPROVAL IS ONLY FOR THE ANY INTERIOR AND
 EXTERIOR IMPROVEMENTS TO THE BUILDING ONLY. A SEPARATE
 PERMIT MUST BE APPLIED FOR, FOR THE SITE WORK AND
 LANDSCAPING PRIOR TO FINAL BUILDING INSPECTION.
  
 ANGELLA VANN
 PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2011-12-21 Cont ID  
Sent By lfranco Date 2011-12-21 Time 17:55 Rev Time 1.25
Received By lfranco Date 2011-12-21 Time 17:55 Sent To  
Notes
2011-12-21 18:03:38PLANNING: **** FAILED ****
  
 1. RESPOND TO COMMENT IN WRITING.
  
 2. THE PROJECT IS UNDER REVIEW WITH THE PLANNING
 DIVISION FOR A MINOR PD AMENDMENT, FINAL APPROVAL OF
 THE MINOR AMENDMENT IS REQUIRED, PRIOR TO REVIEW AND
 APPROVAL OF THE BUILDING PERMIT.
  
 3. COMMENTS MADE BY THE ENGINEERING REVIEW SHALL BE
 ADDRESSED AND REVISIONS OF DUMPSTER ENCLOSURE AND AREA
 SHALL BE REFLECTED ON THE SITE PLANS UNDER REVIEW FOR
 THE MINOR PD AMENDMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  