Plan Review Details - Permit 11100139
Plan Review Stops For Permit 11100139
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 11:20 Rev Time 0.25
Received By jwitmer Date 2011-11-14 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-12 Cont ID  
Sent By jwitmer Date 2011-10-12 Time 14:02 Rev Time 0.33
Received By jwitmer Date 2011-10-12 Time 14:02 Sent To  
Notes
2011-10-12 14:34:59BUILDING PLAN REVIEW
 PERMIT: 11100139
 ADD: 1691- B FORUM PLACE
 CONT: DIG IT BUILD IT INC
 TEL: (941)725-1562
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE IN MASSAGE ROOM #2 A 36'' X 36"
 SHOWER. THE PLANS ARE DEFICIENT IN PROVIDING DETAILS
 FOR AN ACCESSIBLE SHOWER. PLEASE PROVIDE COMPLIANCE
 WITH:
 1-4.21.2 SIZE AND CLEARANCES. EXCEPT AS SPECIFIED IN
 SECTION 11-9.1.2, SHOWER STALL SIZE AND CLEAR FLOOR
 SPACE SHALL COMPLY WITH FIGURE 35(A) OR FIGURE 35(B).
 THE SHOWER STALL IN FIGURE 35(A) SHALL BE 36 INCHES BY
 36 INCHES (915 MM BY 915 MM). SHOWER STALLS REQUIRED BY
 SECTION 11-9.1.2 SHALL COMPLY WITH FIGURE 57(A) OR
 FIGURE 57(B). THE SHOWER STALL IN FIGURE 35(B) WILL FIT
 INTO THE SPACE REQUIRED FOR A BATHTUB.
  
 11-4.21.3 SEAT. A SEAT SHALL BE PROVIDED IN SHOWER
 STALLS 36 INCHES BY 36 INCHES (915 MM BY 915 MM) AND
 SHALL BE AS SHOWN IN FIGURE 36. THE SEAT SHALL BE
 MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM) FROM
 THE BATHROOM FLOOR AND SHALL EXTEND THE FULL DEPTH OF
 THE STALL. IN A 36-INCH BY 36-INCH (915 MM BY 915 MM)
 SHOWER STALL, THE SEAT SHALL BE ON THE WALL OPPOSITE
 THE CONTROLS. WHERE A FIXED SEAT IS PROVIDED IN A
 30-INCH BY 60-INCH MINIMUM (760 MM BY 1525 MM) SHOWER
 STALL, IT SHALL BE A FOLDING TYPE AND SHALL BE MOUNTED
 ON THE WALL ADJACENT TO THE CONTROLS AS SHOWN IN FIGURE
 57. THE STRUCTURAL STRENGTH OF SEATS AND THEIR
 ATTACHMENTS SHALL COMPLY WITH SECTION 11-4.26.3.
 PLEASE BE AWARE OF FIGURE 35(A) WHERE A WHEEL CHAIR
 WILL NEED A ONE FOOT ADDITIONAL WAL SPACE PASSED THE
 END OF THE SEAT.
  
 11-4.21.4 GRAB BARS. GRAB BARS COMPLYING WITH SECTION
 11-4.26 SHALL BE PROVIDED AS SHOWN IN FIGURE 37.
  
 11-4.21.5 CONTROLS. FAUCETS AND OTHER CONTROLS
 COMPLYING WITH SECTION 11-4.27.4 SHALL BE LOCATED AS
 SHOWN IN FIGURE 37. IN SHOWER STALLS 36 INCHES BY 36
 INCHES (915 MM BY 915 MM), ALL CONTROLS, FAUCETS, AND
 THE SHOWER UNIT SHALL BE MOUNTED ON THE SIDE WALL
 OPPOSITE THE SEAT.
  
 11-4.21.6 SHOWER UNIT. A SHOWER SPRAY UNIT WITH A HOSE
 AT LEAST 60 INCHES (1525 MM) LONG THAT CAN BE USED BOTH
 AS A FIXED SHOWER HEAD AND AS A HAND-HELD SHOWER SHALL
 BE PROVIDED.
  
 EXCEPTION: IN UNMONITORED FACILITIES WHERE VANDALISM IS
 A CONSIDERATION, A FIXED SHOWER HEAD MOUNTED AT 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR MAY BE USED IN
 LIEU OF A HAND-HELD SHOWER HEAD.
  
 11-4.21.7 CURBS. IF PROVIDED, CURBS IN SHOWER STALLS 36
 INCHES BY 36 INCHES (915 MM BY 915 MM) SHALL BE NO
 HIGHER THAN 1/2 INCH (13 MM). SHOWER STALLS THAT ARE 30
 INCHES BY 60 INCHES (760 MM BY 1525 MM) MINIMUM SHALL
 NOT HAVE CURBS.
  
 11-4.21.8 SHOWER ENCLOSURES. IF PROVIDED, ENCLOSURES
 FOR SHOWER STALLS SHALL NOT OBSTRUCT CONTROLS OR
 OBSTRUCT TRANSFER FROM WHEELCHAIRS ONTO SHOWER SEATS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-18 Cont ID  
Sent By rlecky Date 2011-10-18 Time 11:15 Rev Time 0.00
Received By rlecky Date 2011-10-18 Time 10:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-10-13 Cont ID  
Sent By wjolin Date 2011-10-13 Time 15:39 Rev Time 0.00
Received By wjolin Date 2011-10-13 Time 15:35 Sent To  
Notes
2011-10-13 15:39:231691 FORUM PLACE - SUITE "B"
 PERMIT #11100139
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND/OR FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-18 Cont ID  
Sent By jwitmer Date 2011-11-18 Time 11:33 Rev Time 0.00
Received By jwitmer Date 2011-11-03 Time 15:19 Sent To  
Notes
2011-11-04 15:27:55B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-01 Cont ID  
Sent By hmoser Date 2011-11-01 Time 12:50 Rev Time 0.00
Received By hmoser Date 2011-10-11 Time 10:07 Sent To  
Notes
2011-10-11 10:10:39B--7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 11:19 Rev Time 0.20
Received By jwitmer Date 2011-11-14 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By hmoser Date 2011-11-01 Time 12:50 Rev Time 0.00
Received By hmoser Date 2011-11-01 Time 12:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-11-16 Cont ID  
Sent By lwagner Date 2011-11-16 Time 09:36 Rev Time 0.00
Received By lwagner Date 2011-11-16 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-10-13 Cont ID  
Sent By lwagner Date 2011-10-13 Time 11:41 Rev Time 0.00
Received By lwagner Date 2011-10-11 Time 14:52 Sent To  
Notes
2011-10-13 11:50:18FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 PLEASE SHOW COMPLIANCE WITH FBC 11-4.21 SHOWER STALLS:
 11-4.21.2 SIZE AND CLEARANCES
 11-4.21.3 SEAT
 11-4.21.4 GRAB BARS
 11-4.21.5 CONTROLS
 11-4.21.6 SHOWER UNIT
 11-4.21.7 CURBS
 11-4.21.8 SHOWER ENCLOSURES
  
 ***NOTE***
 PLUMBING DRAWINGS OK