Plan Review Details - Permit 11100120
Plan Review Stops For Permit 11100120
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-06 Cont ID  
Sent By jwitmer Date 2011-10-06 Time 10:43 Rev Time 0.25
Received By jwitmer Date 2011-10-06 Time 10:43 Sent To  
Notes
2011-10-06 10:48:30REPAIRS AS REQUIRED FROM RED TAG:
 1) REPAIR WIRES TO PANEL, TO SMALL, WAS SPLICED WITH
 #6, NEEDS TO BE SPLICED WITH #4
 2) ADD SMOKE DETECTORS
 3) 4 WIRES TO RANGE, REPLACE 8/2 TO 8/3 WITH FOUR
 PROUNG OUTLET
 4) WIRES TO WATER HEATER ARE TO SMALL FOR ELEMENT:
 CONTRACTOR INDICATES THAT PLUMBING CONTRACTOR WILL COME
 IN TO CHANGE THE ELEMENTS TO THE CORRCT SIZE FOR
 EXISTING WIRING AS STATED ON PLANS.