Plan Review Details - Permit 11100057
Plan Review Stops For Permit 11100057
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-04 Cont ID  
Sent By jgomez Date 2011-10-04 Time 15:11 Rev Time 0.00
Received By jgomez Date 2011-10-04 Time 15:11 Sent To  
Notes
2011-10-04 15:14:10BUILDING REVIEW PROVISO:
  
 1- FAXED CALCULATIONS ARE OK. PROVIDE ORIGINAL WITH
 ENGINEER'S SEAL AND SIGNATURE FOR THE CITY FILE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-04 Cont ID  
Sent By jgomez Date 2011-10-04 Time 14:05 Rev Time 0.00
Received By jgomez Date 2011-10-04 Time 13:54 Sent To  
Notes
2011-10-04 14:15:32BUILDING REVISION CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER TO REVISE THE ATTACHMENT REQUIREMENTS FOR
 ROOF IN THE FIELD AREA (ROOF ZONE #1). ACCORDING TO THE
 NOA SUBMITTED THE BASE SHEET FASTENING OPTION #3 STATES
 TWO ROWS IN THE FIELD AT 9"O.C. ENGINEER STATES TWO
 ROWS AT 12" O.C. REVISE AS REQUIRED. DESIGN PRESSURES
 SHOWN ON THE NOA ARE APPLICABLE TO THE FIELD OF THE
 ROOF AREA (ROOF ZONE #1). SEE SEC. 8.1 OF RAS 117
 CALCULATIONS.
  
 2- ENGINEER NEEDS TO REVISE THE FASTENER SPACING FOR
 THE PERIMETER AND CORNER AREAS. ACCORDING TO SEC. 10 OF
 THE RAS 117 CALCULATIONS ALL FRACTIONS SHALL BE ROUNDED
 DOWN TO THE NEXT WHOLE NUMBER. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-04 Cont ID  
Sent By jgomez Date 2011-10-04 Time 15:11 Rev Time 0.00
Received By jgomez Date 2011-10-04 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-04 Cont ID  
Sent By jgomez Date 2011-10-04 Time 13:54 Rev Time 0.00
Received By jgomez Date 2011-10-04 Time 13:54 Sent To  
Notes
***NONE***