Plan Review Details - Permit 11100025
Plan Review Stops For Permit 11100025
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-28 Cont ID  
Sent By wjolin Date 2011-10-28 Time 13:13 Rev Time 0.00
Received By wjolin Date 2011-10-28 Time 13:12 Sent To M
Notes
2011-10-28 13:13:07410 EVERNIA STREET - SUITE #108
 PERMIT #11100025
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPRINKLER PROTECTION IS REQUIRED IN ALL CLOSET SPACES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-05 Cont ID  
Sent By wjolin Date 2011-10-05 Time 13:40 Rev Time 0.00
Received By wjolin Date 2011-10-05 Time 12:18 Sent To M
Notes
2011-10-05 13:39:51410 EVERNIA STREET - SUITE #108
 PERMIT #11100025
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE HYDRAULIC CALCULATIONS TO VERIFY THE EXISTING
 PIPE SIZES ARE SUFFICIENT FOR THE NEW LARGER K-FACTOR
 COMMERCIAL STYLE SPRINKLERS.
  
 THE COLUMN NEAR THE FIRST FLOOR BATHROOM OBSTRUCTS THE
 SPRAY OF THE EXTENDED COVERAGE SIDEWALL SPRINKLER.
  
 SPRINKLER PROTECTION IS REQUIRED IN ALL THREE CLOSET
 SPACES ON THE MEZZANINE LEVEL.
  
 BOTH FLOOR PLANS ON THE DRAWING ARE INDICATED AS BEING
 THE MEZZANINE LEVEL.
  
 INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS
 FLOOR TO BE UTILIZED FOR THE 2-HOUR PRESSURE TEST.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-02 Cont ID  
Sent By hmoser Date 2011-11-02 Time 08:20 Rev Time 0.00
Received By hmoser Date 2011-10-24 Time 16:03 Sent To  
Notes
2011-10-24 16:03:40SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-14 Cont ID  
Sent By hmoser Date 2011-10-14 Time 16:56 Rev Time 0.00
Received By hmoser Date 2011-10-03 Time 15:17 Sent To  
Notes
2011-10-03 15:17:54SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-02 Cont ID  
Sent By hmoser Date 2011-11-02 Time 08:20 Rev Time 0.00
Received By hmoser Date 2011-11-02 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-10-14 Cont ID  
Sent By hmoser Date 2011-10-14 Time 16:56 Rev Time 0.00
Received By hmoser Date 2011-10-14 Time 16:42 Sent To  
Notes
2011-10-14 16:49:48PLANS DENIED
 PROVIDE PIPE SIZE FOR UNISEX BATHROOM
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]