Plan Review Details - Permit 11100001
Plan Review Stops For Permit 11100001
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-10-03 Cont ID  
Sent By rmcdouga Date 2011-10-03 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2011-10-03 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-12-05 Cont ID  
Sent By rmcdouga Date 2011-12-05 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2011-12-02 Time 10:47 Sent To  
Notes
2011-12-05 15:55:07SEE NOTES ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-04 Cont ID  
Sent By rmcdouga Date 2011-10-04 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2011-10-04 Time 08:03 Sent To  
Notes
2011-10-04 09:17:212007 FBC W/2009 REVISIONS
 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE LOAD CALCULATIONS FOR ARE NOT IN COMPLIANCE WITH
 NEC 220. THE LOAD CALCULATIONS SPECIFY A 40 AMP SUB
 PANEL "B", WHICH IS TOO SMALL FOR THE LOAD OF THE
 DETACHED STORAGE ROOM. SEE NEC 220.83 (A)
  
 2) THE RISER DIAGRAM SHOWS SUB-PANEL "B" AS 25 AMPS.
 COORDINATE THE RISER DIAGRAM WITH THE CORRECTED
 CALCULATED LOADS.
  
 3) SHOW THE BREAKER THAT FEEDS SUB-PANEL "B" IN THE
 SCHEDULE FOR MAIN PANEL "A".
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-05 Cont ID  
Sent By rmcdouga Date 2011-12-05 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2011-11-30 Time 13:43 Sent To  
Notes
2011-11-30 13:44:05GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-04 Cont ID  
Sent By rmcdouga Date 2011-10-04 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2011-10-03 Time 11:08 Sent To  
Notes
2011-10-03 11:08:57SENT TO ROBERT'S DESK FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-10-03 Cont ID  
Sent By rmcdouga Date 2011-10-03 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2011-10-03 Time 16:01 Sent To  
Notes
***NONE***