Plan Review Details - Permit 11090826
Plan Review Stops For Permit 11090826
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-12-30 Cont ID  
Sent By shill Date 2011-12-30 Time 16:35 Rev Time 0.00
Received By shill Date 2011-12-30 Time 16:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-12-20 Cont ID  
Sent By shill Date 2011-12-20 Time 14:52 Rev Time 0.00
Received By shill Date 2011-12-14 Time 07:36 Sent To  
Notes
2011-12-20 14:52:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OK.
  
 2. WALL ORIENTATION AND FIRE RATING HAS BEEN CORRECTED,
 BUT NO INFORMATION PROVIDED REGARDING CUPOLA FIRE
 RESISTANCE, SEE FBC 704.11 AND EXCEPTIONS.
  
 COMPLIANCE WITH FBC TABLE 704.8 NOT CLEAR. IT IS NOT
 CLEAR WHAT PORTION OF THE ANGLED WALL IS LESS THAN 20?
 FROM THE PROPERTY LINE. PLEASE SHOW THE 20? LINE
 THROUGH THE EAST ELEVATION AND PROVIDE CALCULATION, 25
 PERCENT MAXIMUM OPENINGS PERMITTED FOR TYPE VA.
  
 3. OK
  
 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER
 COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED
 BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS
 THIS CORRECT AND DESIGNER'S INTENT?
  
 3RD REVIEW, NO RESPONSE LETTER PROVIDED. THE SECOND
 DOOR SHOWN IS NOT AN EXIT AS IT GOES THROUGH A KITCHEN.
  
 5. OK.
  
 6. A LIFE SAFETY PLAN WAS REQUESTED IN FIRST REVIEW,
 BUT NOT PROVIDED. HOWEVER, PLAN WAS REVISED TO INCLUDE
 BREAKDOWN BY AREA AND OCCUPANT LOAD. AS THE OCCUPANT
 LOAD EXCEEDS 49, TWO EXITS REQUIRED FBC TABLE 1015.1.
  
 3RD REVIEW, LIFE SAFETY PLAN PROVIDED, BUT SHOWS THE
 SECOND EXIT IN THE KITCHEN. SEE FBC 1014.2(2), THIS IS
 PROHIBITED.
  
 **COURTESY REVIEW** REVISED OCCUPANT LOAD SENT VIA
 EMAIL ON 12/15 SHOWS 1339 SF WITH AN OCCUPANT LOAD OF
 45. IF THE BUILDING IS 2505 SF (FROM SHEET A-1C AND
 OTHER SHEETS) AND THE COOLER IS 335 SF, THAT LEAVES
 2170 SF OF OCCUPIED SPACE. PLEASE INCLUDE OCCUPANTS FOR
 THE ADDITIONAL 831 SF WHICH APPEARS TO BE MISSING FROM
 THE CALCULATION.
  
 7. SEE ITEM 6.
  
 8. OK.
  
 9. OK.
  
 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND
 CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH
 WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS,
 ETC.).
  
 3RD REVIEW, SOME BUT NOT ALL PRODUCT APPROVALS WERE
 SUBMITTED. PLEASE NOTE THAT ANY PRODUCT APPROVALS WHICH
 HAVE NOT BEEN SUBMITTED PRIOR TO ISSUANCE WILL BE
 REQUIRED TO BE SUBMITTED AS A REVISION.
  
 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER
 ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703.
  
 2ND REVIEW, NOT ADDRESSED.
  
 3RD REVIEW, NOT ADDRESSED. AN INTERIOR FIRE RATED
 PARTITION WALL IS INCLUDED. I WAS UNABLE TO LOCATE THE
 FIRE RATING DETAILS FOR STRUCTURAL ELEMENTS. NOTE THAT
 THE FUEL CANOPY IS A PART OF THE BUILDING AND REQUIRES
 THE SAME FIRE RATING.
  
 IT IS NOT CLEAR WHY THIS BUILDING IS TYPE VA. IF YOU
 NEED ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME TO
 DISCUSS OPTIONS.
  
 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM
 BEACH COUNTY, 561 233 5025.
  
 3RD REVIEW, COULD NOT LOCATE IMPACT FEE STAMP (LOOKED
 IN BOTH SETS OF NEW PLANS) OR THE RECEIPT. PLEASE
 PROVIDE.
  
 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4.
  
 2ND & 3RD REVIEWS, NOT ADDRESSED.
  
 14. SEE FBC 11-4.7, CURB RAMP REQUIRED WHERE ACCESSIBLE
 ROUTE CROSSES A CURB.
  
 3RD REVIEW, NOT ADDRESSED.
  
 15. (NEW COMMENT ON NEW DOCUMENTS) DELEGATED
 ENGINEERING TO BE REVIEWED BY ENGINEER OF RECORD,
 FAC61G.
  
 16. (NEW COMMENT ON NEW DETAIL) S1 SHOWS A HAND DRAWN
 ATM MACHINE BETWEEN THE BATHROOM AND THE WATER
 FOUNTAIN. SEE FBC 11 FIGURE 27 AND FIGURE 25 FOR CLEAR
 FLOOR SPACE AND MANEUVERING CLEARANCE REQUIREMENTS.
 ELECTRICAL SHEETS STILL SHOW ATM IN OLD LOCATION.
  
 ***WHEN RESUBMITTING, PLEASE INCLUDE A WRITTEN RESPONSE
 LETTER.***
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-11-30 Cont ID  
Sent By shill Date 2011-11-30 Time 10:35 Rev Time 0.00
Received By shill Date 2011-11-30 Time 09:15 Sent To  
Notes
2011-11-30 12:11:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OK.
  
 2. ORIENTATION OF NORTH APPEAR TO CONFLICT ON VARIOUS
 SHEETS; FOR INSTANCE, SEE U1 AND A 1A. DUE TO
 CONFLICTING INFORMATION IT IS UNCLEAR WHETHER THE 1
 HOUR RATED WALL SHOWN ON A1A IS THE WALL FACING THE
 EAST PROPERTY LINE OR THE STREET TO THE WEST. NOTE THAT
 THE WALL WHICH (BASED ON SHEET U1) SHOULD FACE THE
 PROPERTY LINE HAS A WINDOW IN THE WALL; WHEN SUBMITTING
 PRODUCT APPROVALS ADDRESS BOTH FIRE RESISTANCE AS WELL
 AS IMPACT PROTECTION FOR THE DRIVE THROUGH WINDOW. SEE
 ALSO FBC TABLE 704.8 (OPENINGS IN RATED WALLS). REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC TABLE 602 AND TABLE
 704.8.
  
 2ND REVIEW, NORTH ORIENTATION CORRECTED BUT INFORMATION
 REQUESTED REGARDING WALL WITHIN 20' OF THE PROPERTY
 LINE NOT PROVIDED. THE WALL REFERENCING FBC TABLE 602
 FACES THE STREET (WEST SIDE). THE EAST SIDE (LEFT SIDE
 OF THE PLAN AS NORTH NOW POINTS DOWN) IS TO SHOW
 COMPLIANCE WITH FBC TABLE 602, 704.8.
  
 3. OK
  
 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER
 COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED
 BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS
 THIS CORRECT AND DESIGNER'S INTENT?
  
 2ND REVIEW, NO RESPONSE LETTER PROVIDED.
  
 5. OK.
  
 6. A LIFE SAFETY PLAN WAS REQUESTED IN FIRST REVIEW,
 BUT NOT PROVIDED. HOWEVER, PLAN WAS REVISED TO INCLUDE
 BREAKDOWN BY AREA AND OCCUPANT LOAD. AS THE OCCUPANT
 LOAD EXCEEDS 49, TWO EXITS REQUIRED FBC TABLE 1015.1.
  
 7. BASED ON BUILDING AREA SHOWN ON SHEET 1, 2500 SF,
 AND FBC TABLE 1004.1.1 (30 SF PER OCCUPANT FOR
 MERCANTILE, GROSS FLOOR AREA), IT APPEARS THAT TWO
 EXITS MAY BE REQUIRED, FBC 1015. PROVIDE CALCULATIONS
 FOR OCCUPANT LOAD AND EXITING RATIONALE.
  
 2ND REVIEW, DESIGNER HAS STATED THAT OCCUPANT LOAD IS
 84 (A1B), BUT ONLY ONE EXIT IS PROVIDED. PLEASE
 ADDRESS.
  
 8. OK.
  
 9. OK.
  
 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND
 CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH
 WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS,
 ETC.).
  
 2ND REVIEW, NOT ADDRESSED. PRODUCT APPROVALS TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER
 ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703.
  
 2ND REVIEW, NOT ADDRESSED.
  
 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM
 BEACH COUNTY, 561 233 5025.
  
 2ND REVIEW, NOT ADDRESSED.
  
 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4.
  
 2ND REVIEW, NOT ADDRESSED.
  
 14. (NEW COMMENT) SEE FBC 11-4.7, CURB RAMP REQUIRED
 WHERE ACCESSIBLE ROUTE CROSSES A CURB.
  
 ***WHEN RESUBMITTING, PLEASE INCLUDE A WRITTEN RESPONSE
 LETTER.***
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-13 Cont ID  
Sent By shill Date 2011-10-13 Time 17:55 Rev Time 0.00
Received By shill Date 2011-10-13 Time 17:55 Sent To  
Notes
2011-10-14 13:27:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLANS APPEAR TO INCLUDE INCORRECT ADDRESS, CONFLICTS
 WITH APPLICATION, PLEASE CORRELATE.
  
 2. ORIENTATION OF NORTH APPEAR TO CONFLICT ON VARIOUS
 SHEETS; FOR INSTANCE, SEE U1 AND A 1A. DUE TO
 CONFLICTING INFORMATION IT IS UNCLEAR WHETHER THE 1
 HOUR RATED WALL SHOWN ON A1A IS THE WALL FACING THE
 EAST PROPERTY LINE OR THE STREET TO THE WEST. NOTE THAT
 THE WALL WHICH (BASED ON SHEET U1) SHOULD FACE THE
 PROPERTY LINE HAS A WINDOW IN THE WALL; WHEN SUBMITTING
 PRODUCT APPROVALS ADDRESS BOTH FIRE RESISTANCE AS WELL
 AS IMPACT PROTECTION FOR THE DRIVE THROUGH WINDOW. SEE
 ALSO FBC TABLE 704.8 (OPENINGS IN RATED WALLS). REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC TABLE 602 AND TABLE
 704.8.
  
 3. THERE APPEARS TO BE A CATCH BASIN IN THE ACCESSIBLE
 ROUTE, SEE GR1, SEE FBC 11 4.5.4, GRATINGS AND REVISE
 PLAN TO SHOW COMPLIANCE.
  
 4. ORIENTATION OF STRUCTURE IS NOT CLEAR, SEE OTHER
 COMMENTS, BUT IT APPEARS THAT THE ONLY EXIT IS COVERED
 BY THE SAME STRUCTURE AS THE PROPOSED FUEL CANOPY. IS
 THIS CORRECT AND DESIGNER'S INTENT?
  
 5. IT APPEARS THAT THE PROPOSED FUEL CANOPY COVERS HALF
 OF THE ACCESSIBLE PARKING SPACE. PROVIDE MORE
 INFORMATION REGARDING THE STRUCTURE AND HOW IT WILL
 AFFECT THE ACCESSIBLE ROUTE AND EXIT AS IT IS NOT CLEAR
 WHERE STRUCTURAL SUPPORTS WILL BE. SEE ALSO FBC 11
 4.6.5, VERTICAL CLEARANCE.
  
 6. PROVIDE A LIFE SAFETY PLAN WHICH INCLUDES THE
 FOLLOWING INFORMATION:
  
 OCCUPANCY CLASSIFICATION; THIS SHOULD BE EITHER ONE
 OCCUPANCY OR MIXED OCCUPANCY, AND IF MIXED OCCUPANCY,
 PLAN SHOULD DESIGNATE EACH OCCUPANCY WITH SQUARE FOOT
 AREA OF EACH. ALSO REVISE A1B WHICH SHOWS OCCUPANCY AS
 B M. IT APPEARS THAT THE PLAN INCLUDES MERCANTILE,
 BUSINESS, AND STORAGE; NOTE AREAS WITH OCCUPANT LOAD
 CALCULATIONS.
  
 OCCUPANT LOAD BASED ON SQUARE FOOT AREA AND USE, SEE
 FBC TABLE 1004.1.1.
  
 TRAVEL DISTANCES, INCLUDING COMMON PATH OF TRAVEL
  
 IN MAKING THE DECISION AS TO WHO WILL PREPARE THE LIFE
 SAFETY PLAN AND ADDRESS OTHER EXITING CONCERNS, PLEASE
 SEE:
  
 HTTP://WWW.FLENG.ORG/LEGAFF.CFM?PICKED=81 FOR A LINK TO
 A BUILDING OFFICIALS GUIDE TO DESIGN PROFESSIONAL
 PRACTICE OF ARCHITECTS & ENGINEERS IN FLORIDA, OR SEE
 THE FOLLOWING FOR A DIRECT LINK TO THE DOCUMENT:
  
 HTTP://WWW.FLENG.ORG/IMAGES/FILES/03012011%20PUBLISH%20
 -%20BUILDING_OFFICIALS_GUIDE_TO_DESIGN_PROFESSIONAL_PRA
 CTICE%20-.PDF
  
 7. BASED ON BUILDING AREA SHOWN ON SHEET 1, 2500 SF,
 AND FBC TABLE 1004.1.1 (30 SF PER OCCUPANT FOR
 MERCANTILE, GROSS FLOOR AREA), IT APPEARS THAT TWO
 EXITS MAY BE REQUIRED, FBC 1015. PROVIDE CALCULATIONS
 FOR OCCUPANT LOAD AND EXITING RATIONALE.
  
 8. DOOR 1 IS DEPICTED IN THE PLAN AS A SLIDING DOOR,
 SHEET A16 SCHEDULE CALLS FOR A SWING DOOR. SEE FBC
 1008.3.3 REGARDING REQUIREMENTS FOR SLIDING DOOR,
 REVISE PLAN TO SHOW COMPLIANCE AND SUBMIT PRODUCT
 APPROVAL IS DESIGN INTENT IS A SLIDING DOOR IN THIS
 LOCATION.
  
 9. DOOR 7 IS LOCATED IN A FIRE PARTITION, SEE FBC706.7,
 SPECIFY FIRE RATING FOR DOOR.
  
 10. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND
 CLADDING, FBC1609 (DOORS, STOREFRONT, DRIVE THROUGH
 WINDOW, BULLET PROOF/IMPACT WINDOWS, ROOF, ROOF STANDS,
 ETC.).
  
 11. PROVIDE DETAILS FOR THE FIRE RATED WALLS AND OTHER
 ELEMENTS REQUIRED FOR BUILDING TYPE VA, FBC 703.
  
 12. IMPACT FEE ASSESSMENT REQUIRED, PLEASE CONTACT PALM
 BEACH COUNTY, 561 233 5025.
  
 13. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.4.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2011-12-30 Cont ID  
Sent By rlecky Date 2011-12-30 Time 10:36 Rev Time 0.00
Received By rlecky Date 2011-12-30 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2011-12-14 Cont ID  
Sent By rlecky Date 2011-12-14 Time 18:23 Rev Time 0.00
Received By rlecky Date 2011-12-14 Time 17:39 Sent To  
Notes
2011-12-14 18:10:1511090826
 1270 PALM BEACH LAKES BLVD.
 NEW GASOLINE/ CONVENIENCE STORE
  
 THE FOLLOWING ITEMS HAVE NOT BEEN ADDRESSED FROM
 PREVIOUS ELECTRIC REVIEWS. PLEASE CALL ME TO DISCUSS
 FURTHER SO WE CAN EXPEDIATE THE REMAINING ITEMS.
  
 SPECIFY ON THE PLANS HOW THE INTERIOR LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. AUTOMATIC
 LIGHTING CONTROL FBC 13-415.ABC.1.1; AUTOMATIC SPACE
 CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS
 13-412.ABC.1.3
  
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. FPL, THE LOCAL ELECTRIC
 UTILITY, CAN PROVIDE THE AVAILABLE FAULT CURRENT AT
 THEIR POINT OF SERVICE. THE NEW SERVICE DISCONNECTS AND
 PANEL BOARDS MUST HAVE THE CAPABILITY TO INTERRRUPT THE
 AVAILABLE FAULT CURRENT. NEC 110.9
  
 THANK YOU
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-11-15 Cont ID  
Sent By rlecky Date 2011-11-15 Time 11:35 Rev Time 0.00
Received By rlecky Date 2011-11-15 Time 11:35 Sent To  
Notes
2011-11-15 11:38:14ELECTRIC PLAN REVIEW COMMENTS FROM PREVIOUS REVIEW OF
 10/3/11 AS NOTED BELOW WERE NOT ADDRESSED WITHIN THE
 RESUBMITTAL.
  
  
 11090826
 1270 PALM BEACH LAKES BLVD.
 NEW GASOLINE/ CONVENIENCE STORE
  
 SPECIFY ON THE PLANS HOW THE INTERIOR AND EXTERIOR
 LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR
 SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING
 CODE. AUTOMATIC LIGHTING CONTROL FBC 13-415.ABC.1.1;
 AUTOMATIC SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL
 CONTROLS 13-412.ABC.1.3
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. FPL, THE LOCAL ELECTRIC
 UTILITY, CAN PROVIDE THE AVAILABLE FAULT CURRENT AT
 THEIR POINT OF SERVICE. NEC 110.9
 PROVIDE A DEDICATED SPACE FOR THE SERVICE PANEL BOARDS.
 NEC 110. 26 (F)
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-03 Cont ID  
Sent By rlecky Date 2011-10-03 Time 14:45 Rev Time 0.00
Received By rlecky Date 2011-10-03 Time 12:12 Sent To  
Notes
2011-10-03 14:46:1311090826
 1270 PALM BEACH LAKES BLVD.
 NEW GASOLINE/ CONVENIENCE STORE
  
 SPECIFY ON THE PLANS HOW THE INTERIOR AND EXTERIOR
 LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR
 SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING
 CODE. AUTOMATIC LIGHTING CONTROL FBC 13-415.ABC.1.1;
 AUTOMATIC SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL
 CONTROLS 13-412.ABC.1.3
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. NEC 110.9
 PROVIDE A DEDICATED SPACE FOR THE SERVICE PANEL BOARDS.
 NEC 110. 26 (F)
 A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE SITE
 LIGHTING. THE PLAN SHOULD INCLUDE PHOTO METRICS, AN
 ELECTRIC POWER PLAN, THE DESIGN WIND LOAD WITH
 ENGINEERING FOR THE LIGHT POLES, FIXTURES AND FOOTINGS.
 NEC 215-5
 GENERAL PURPOSE RECEPTACLES LOCATED WITHIN 6 FEET OF
 SINKS MUST BE GFCI PROTECTED. NEC 210.8 (B)
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2011-12-30 Cont ID  
Sent By shill Date 2011-12-08 Time 15:23 Rev Time 0.00
Received By bmoree Date 2011-12-08 Time   Sent To  
Notes
2011-12-08 14:46:58OWNER HAS MADE APPLICATION WITH ENGINEERING SERVICES
 FOR A SITE DEVELOPMENT PERMIT.
 NO FURTHER ACTION REQUIRED BY ENGINEERING SERVICES ON
 THIS PERMIT.
  
 BRIAN R. MOREE
 ENGINEERING CONSTRUCTION MANAGER
 ENGINEERING SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-644-7270

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-10-26 Cont ID  
Sent By bmoree Date 2011-10-26 Time 16:34 Rev Time 0.00
Received By bmoree Date 2011-10-26 Time 16:33 Sent To  
Notes
2011-10-26 16:41:11PER COMMENTS SUBMITTED WITH CASE NUMBER Z11070025,
 APPLICANT MUST SUBMIT SITE CIVIL DRAWING TO ENGINEERING
 SERVICES. ENGINEERING SERVICES SITE DEVELOPMENT PERMIT
 APPLICATION IS AVAILABLE ONLINE AT
 HTTP://WWW.WPB.ORG/ENGINEERING/ THE APPLICATION
 INCLUDES A CHECKLIST TO ASSIST WITH PREPARING THE
 NECESSARY DOCUMENTATION.
  
 THE APPLICATION MAY BE MAILED TO:
  
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 CONSTRUCTION ADMINISTRATION
 PO BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 OR APPLICATIONS MAY BE DELIVERED TO:
  
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 CONSTRUCTION ADMINISTRATION
 FOURTH FLOOR
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
  
  
 BRIAN R. MOREE
 CONSTRUCTION MANAGER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-644-7270
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-15 Cont ID  
Sent By wjolin Date 2011-11-15 Time 11:11 Rev Time 0.00
Received By wjolin Date 2011-11-15 Time 10:35 Sent To  
Notes
2011-11-15 11:01:151270 PALM BEACH LAKES BOULEVARD
 PERMIT #11090826
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WORKING AND TESTED WET FIRE HYDRANT REQUIRED PRIOR TO
 CONSTRUCTION.
  
 COMMERCIAL COOKING EQUIPMENT AND EXHAUST HOOD REQUIRED
 TO BE PROTECTED BY A UL 300 LISTED SUPPRESSION SYSTEM.
 SEPARATE PLANS AND PERMITS NEEDED FOR HOOD AND
 SUPPRESSION SYSTEM.
  
 PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 SHEET LS-1: THE FIRE HYDRANT SHALL BE PROVIDED WITH
 CLEARANCES OF THE 7'-6" TO THE SIDES/FRONT AND 4'-0" TO
 THE REAR. THE LANDSCAPE PLAN APPEARS TO HAVE A FLORIDA
 ROYAL PALM IN FIRE HYDRANT CLEARANCE AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-04 Cont ID  
Sent By wjolin Date 2011-10-04 Time 13:20 Rev Time 0.00
Received By wjolin Date 2011-10-04 Time 11:10 Sent To  
Notes
2011-10-04 13:20:201270 PALM BEACH LAKES BOULEVARD
 PERMIT #11090826
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WORKING AND TESTED WET FIRE HYDRANT REQUIRED PRIOR TO
 CONSTRUCTION.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE WEATHERPROOF NO SMOKING OR OPEN FLAME SIGNS AT
 EACH FUEL STATION ISLAND.
  
 COMMERCIAL COOKING EQUIPMENT AND EXHAUST HOOD REQUIRED
 TO BE PROTECTED BY A WET CHEMICAL SUPPRESSION SYSTEM.
 SEPARATE PLANS AND PERMITS NEEDED FOR HOOD AND
 SUPPRESSION SYSTEM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 SHEET 1: THE CURBING LOCATED FROM THE NORTH ENTRANCE TO
 THE WEST ENTRANCE SHALL BE DESIGNATED AS A FIRE LANE.
 ALSO THE CURBING IN FRONT OF THE NEW FIRE HYDRANT SHALL
 BE DESIGNATED AS A FIRE LANE. THE FIRE LANE SHALL BE
 MARKED WITH PAINTED CURBS AND FREE-STANDING SIGNS. FIRE
 LANES SHALL INDICATE NO PARKING - FIRE LANE.
  
 SHEET LS-1: THE FIRE HYDRANT SHALL BE PROVIDED WITH
 CLEARANCES OF THE 7'-6" TO THE SIDES/FRONT AND 4'-0" TO
 THE REAR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-12-30 Cont ID  
Sent By shill Date 2011-12-30 Time 16:35 Rev Time 0.00
Received By shill Date 2011-12-30 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-12-30 Cont ID  
Sent By shill Date 2011-12-30 Time 15:23 Rev Time 0.00
Received By shill Date 2011-12-12 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-08 Cont ID  
Sent By shill Date 2011-12-08 Time 12:08 Rev Time 0.00
Received By shill Date 2011-11-08 Time 16:26 Sent To  
Notes
2011-12-08 12:15:09REMOVED FROM BOARD, ONE SET AT FRONT COUNTER FOR IMPACT
 FEES
 EMAILED ZONING AND ENGINEERING - PROJECT GOING THROUGH
 SEPARATE PROCESSES, REQUESTED THAT THEY ENTER THEIR
 REVIEWS
  
2011-11-09 16:26:40****************EXPEDITED******************
 C--3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-18 Cont ID  
Sent By shill Date 2011-10-18 Time 10:56 Rev Time 0.00
Received By shill Date 2011-09-30 Time 14:15 Sent To  
Notes
2011-09-30 14:19:29********************EXPEDITED***********************
 C--8

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2011-12-30 Cont ID  
Sent By shill Date 2011-12-30 Time 13:48 Rev Time 0.00
Received By shill Date 2011-12-30 Time 13:48 Sent To  
Notes
2011-12-30 13:48:56RECEIPT # 2011-1230-95
 MU 2011 21816
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2011-12-29 Cont ID  
Sent By shill Date 2011-12-29 Time 09:59 Rev Time 0.00
Received By shill Date 2011-12-29 Time 09:59 Sent To  
Notes
2011-12-29 09:59:38SEE BUILDING REVIEW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2011-11-30 Cont ID  
Sent By shill Date 2011-11-30 Time 14:10 Rev Time 0.00
Received By shill Date 2011-11-30 Time 14:10 Sent To  
Notes
2011-11-30 14:11:08CONTACT 561-233-5025 FOR MORE INFORMATION

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-10-13 Cont ID  
Sent By shill Date 2011-10-13 Time 17:58 Rev Time 0.00
Received By shill Date 2011-10-13 Time 17:58 Sent To  
Notes
2011-10-13 17:59:14IMPACT FEE ASSESSMENT REQUIRED, 233-5025 FOR MORE
 INFORMATION

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2011-12-30 Cont ID  
Sent By hmoser Date 2011-12-30 Time 15:15 Rev Time 0.00
Received By hmoser Date 2011-12-30 Time 15:15 Sent To  
Notes
2011-12-30 15:55:09SEPARATE PERMITS AND REVIEWS REQUIRED FOR REFRIGERATION
 EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL REQUIRED PRIOR
 TO SUBMITTAL FOR FUEL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2011-12-20 Cont ID  
Sent By hmoser Date 2011-12-20 Time 15:38 Rev Time 0.00
Received By hmoser Date 2011-12-20 Time 15:38 Sent To  
Notes
2011-12-20 15:53:14****CORRECTIONS****
 11090826
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL
 REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT.
  
 ADVISORY ONLY.
  
 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC
 13.409.AB.3.3.
  
 2ND REVIEW, MOTORIZED DAMPERS REQUIRED.
  
 3RD REVIEW, M2, PLAN SHOWS GRAVITY DAMPERS FOR OUTSIDE
 AIR, NOTE 14. SHEET M2 SHOWS 1000 CFM OUTSIDE AIR.
 PLEASE SEE:
  
 13-409.AB.3.3 SHUTOFF DAMPER CONTROLS. BOTH OUTDOOR AIR
 SUPPLY AND EXHAUST SYSTEMS SHALL BE EQUIPPED WITH
 MOTORIZED DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS OR SPACES SERVED ARE NOT IN USE. VENTILATION
 OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY
 SHUTTING OFF DURING PREOCCUPANCY BUILDING WARMUP,
 COOLDOWN, AND SETBACK, EXCEPT WHEN VENTILATION REDUCES
 ENERGY COSTS (E.G., NIGHT PURGE) OR WHEN VENTILATION
 MUST BE SUPPLIED TO MEET CODE REQUIREMENTS.
  
 EXCEPTIONS:
  
 1. GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN
 BUILDING EXHAUST AIR SYSTEMS.
  
 2. GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN
 SYSTEMS WITH A DESIGN OUTSIDE AIR INTAKE OR EXHAUST
 CAPACITY OF 300 CFM (.14 M3/S) OR LESS.
  
 3. OK.
  
 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609.
  
 2ND & 3RD REVIEW, CURB DETAIL DOES NOT INCLUDE ANY
 FASTENING INFORMATION. SHOW HOW THE CURB WILL RESIST
 WIND LOADS.
  
 5. AN ELECTRIC ROOM WITH A 1 HOUR FIRE RATED WALL HAS
 BEEN ADDED ON A SHEETS BUT NOT SHOWN ON M SHEETS.
 PLEASE SHOW FIRE RATED WALL ON M SHEETS AND FIRE
 DAMPERS FBC MECHANICAL TABLE 607.3.1. FLEXIBLE DUCT AND
 AIR CONNECTORS SHALL NOT PASS THROUGH ANY FIRE
 RESISTANCE RATED ASSEMBLY.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-12-08 Cont ID  
Sent By hmoser Date 2011-12-08 Time 08:11 Rev Time 0.00
Received By hmoser Date 2011-12-08 Time 08:11 Sent To  
Notes
2011-12-08 10:39:01****CORRECTIONS****
 11090826
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL
 REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT.
  
 ADVISORY ONLY.
  
 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC
 13.409.AB.3.3.
  
 2ND REVIEW, MOTORIZED DAMPERS REQUIRED.
  
 3. SHOW CONDENSATE DISCHARGE, FBC MECHANICAL 307.2.1.
  
 2ND REVIEW, CONDENSATE CANNOT DISCHARGE INTO SANITARY,
 CITY OF WEST PALM BEACH MUNICIPAL CODE 90-125.
  
 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609.
  
 2ND REVIEW, CURB DETAIL DOES NOT INCLUDE ANY FASTENING
 INFORMATION. SHOW HOW THE CURB WILL RESIST WIND LOADS.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-10-14 Cont ID  
Sent By shill Date 2011-10-14 Time 15:19 Rev Time 0.00
Received By hmoser Date 2011-10-14 Time 13:29 Sent To  
Notes
2011-10-14 16:07:48****CORRECTIONS****
 11090826
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD, AND FUEL. FDEP APPROVAL
 REQUIRED PRIOR TO SUBMITTAL FOR FUEL PERMIT.
  
 2. OUTSIDE AIR DUCT REQUIRES A DAMPER, FBC
 13.409.AB.3.3.
  
 3. SHOW CONDENSATE DISCHARGE, FBC MECHANICAL 307.2.1.
  
 4. PROVIDE A DETAIL FOR THE CURB, FBC 1609.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-12-16 Cont ID  
Sent By lwagner Date 2011-12-16 Time 11:07 Rev Time 0.00
Received By lwagner Date 2011-12-16 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-11-18 Cont ID  
Sent By lwagner Date 2011-11-18 Time 14:28 Rev Time 0.00
Received By lwagner Date 2011-11-18 Time 14:25 Sent To  
Notes
2011-11-18 14:41:03FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. 403.1 MINIMUM NUMBER OF FIXTURES - MERCANTILE -
 RETAIL STORES, SERVICE STATIONS, SHOPS, SALESROOMS,
 MARKETS AND SHOPPING CENTERS - 1 DRINKING FOUNTAIN
 REQUIRED PER 1,000
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-10-07 Cont ID  
Sent By lwagner Date 2011-10-07 Time 16:35 Rev Time 0.00
Received By lwagner Date 2011-10-07 Time 15:20 Sent To  
Notes
2011-10-07 16:15:07****PROVISO****
 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
 ****NOTE****
 NOT INCLUDED IN THIS REVIEW :
 GREASE TRAP
 IRRIGATION
 FUEL GAS
 SEPARATE APPLICATION, DRAWING, AND PERMIT REQUIRED
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-12-30 Cont ID  
Sent By lfranco Date 2011-12-30 Time 16:33 Rev Time 0.00
Received By lfranco Date 2011-12-30 Time 16:33 Sent To  
Notes
2011-12-30 16:36:19PLANNING: *** PASSED WITH PROVISO, ALL OUTSTANDING
 COMMENTS AND CONDITIONS PER ISPR 11-06 LETTER SHALL BE
 ADDRESSED PRIOR TO FINAL APPROVAL AND SIGN-OFF OF
 CERTIFICATE OF OCCUPANCY BY ZONING. ****
  
  
 1. WHEEL STOPS ARE TO HAVE 2 FEET BETWEEN BACK OF WHEEL
 STOP AND CURBING/SIDEWALK, ETC. REVISE PLANS
 ACCORDINGLY WHEN RESUBMITTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL. (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2011-12-08 Cont ID  
Sent By lfranco Date 2011-12-08 Time 14:21 Rev Time 0.00
Received By lfranco Date 2011-12-08 Time 14:21 Sent To  
Notes
2011-12-08 14:21:23PLANNING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROJECT UNDER AN INFORMAL SITE PLAN REVIEW ("ISPR")
 WITH THE PLANNING DIVISION. PLANNING CAN NOT
 REVIEW/APPROVE PERMIT UNTIL ISPR HAS BEEN COMPLETED BY
 ALL DISCIPLINES THAT REVIEWED THE PROJECT UNDER THE
 PPRC REVIEW PROCESS AND ALL COMMENTS HAVE BEEN
 ADDRESSED.
  
 RE-SUBMITTAL: A CONDITIONAL APPROVAL OF THE ISPR HAS
 BEEN ISSUED. HOWEVER, THE PLANS SUBMITTED DO NOT
 REFLECT THE PLANS THAT WERE REVIEWED AND APPROVED BY
 PLANNING. REVISE ACCORDINGLY AND RESUBMIT. ALSO,
 ADDRESS THE COMMENTS BELOW.
  
 3. SEPARATE LANDSCAPE AND IRRIGATION PERMITS ARE
 REQUIRED. TWO COPIES OF THE LANDSCAPE PLAN AND A COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST SHALL
 BE SUBMITTED WITH THE LANDSCAPE PERMIT APPLICATION.
  
 4. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 5. SUBMIT TWO COPIES OF THE IRRIGATION PLAN WITH THE
 IRRIGATION PERMIT APPLICATION.
  
 6. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. PLEASE SHOW
 SOD IN THE RIGHT-OF-WAY, ADJACENT TO OLIVE AVENUE
  
 7. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE ELEMENTS ENUMERATED IN
 THIS SECTION, INCLUDING BUT NOT LIMITED TO
 IDENTIFICATION OF ALL AIR CONDITIONING UNITS,
 GENERATORS AND ALL OTHER MECHANICAL EQUIPMENT. PLEASE
 PROVIDE THE LOCATION OF THESE ITEMS AND THE MANNER IN
 WHICH THEY WILL BE SCREENED.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-10-18 Cont ID  
Sent By lfranco Date 2011-10-18 Time 10:48 Rev Time 0.00
Received By lfranco Date 2011-10-18 Time 10:48 Sent To  
Notes
2011-10-18 10:52:40PLANNING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROJECT UNDER AN INFORMAL SITE PLAN REVIEW ("ISPR")
 WITH THE PLANNING DIVISION. PLANNING CAN NOT
 REVIEW/APPROVE PERMIT UNTIL ISPR HAS BEEN COMPLETED BY
 ALL DISCIPLINES THAT REVIEWED THE PROJECT UNDER THE
 PPRC REVIEW PROCESS AND ALL COMMENTS HAVE BEEN
 ADDRESSED.
  
 3. SEPARATE LANDSCAPE AND IRRIGATION PERMITS ARE
 REQUIRED. TWO COPIES OF THE LANDSCAPE PLAN AND A COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST SHALL
 BE SUBMITTED WITH THE LANDCAPE PERMIT APPLICATION.
  
 4. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 5. SUBMIT TWO COPIES OF THE IRRIGATION PLAN WITH THE
 IRRIGATION PERMIT APPLICATION.
  
 6. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. PLEASE SHOW
 SOD IN THE RIGHT-OF-WAY, ADJACENT TO OLIVE AVENUE
  
 7. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE ELEMENTS ENUMERATED IN
 THIS SECTION, INCLUDING BUT NOT LIMITED TO
 IDENTIFICATION OF ALL AIR CONDITIONING UNITS,
 GENERATORS AND ALL OTHER MECHANICAL EQUIPMENT. PLEASE
 PROVIDE THE LOCATION OF THESE ITEMS AND THE MANNER IN
 WHICH THEY WILL BE SCREENED.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  