| 2011-10-14 12:41:37 | BUILDING PLAN REVIEW |
| | PERMIT: 110908259 (REV) / 11080026 (PER) |
| | ADD: 1901 N FLAGLER |
| | CONT: IBIS BUILD. CORP. |
| | TEL: (561)568-2570 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING PROVISO: |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. CONTRACTOR |
| | CONTINUING WORK AT OWN RISK! |
| | |
| | 1) SHEET A3.1 DETAIL 03 (NEW SHEET/ NEW WORK) |
| | 1A) MISSING PRODUCT APPROVALS NEW SOLAR INOVATIONS INC |
| | OUTFOLDING SERIES 5000 ST. ALUM DOOR SYSTEMS |
| | 1B) MISSING PRODUCT APPROVAL FOR NEW ALUMINUM |
| | STOREFRONT DOORS. |
| | 1C) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 2) NEW WORK SHEET A5.6 |
| | 2A) MISSING PRODUCT APPROVAL FOR 42" X 42" ACCESS DOOR. |
| | 2B) PRE-MANUFACTURED STANDING SEAM METAL ROOFING |
| | 2C) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3) S-2.1 MISSING WIND DESIGN CRITERIA FOR THE NEW |
| | SLOPED ROOF, NO PRESSURES FOR ROOF ZONES SLOPED ROOF |
| | 8/12 PITCH. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |