Plan Review Details - Permit 11090809
Plan Review Stops For Permit 11090809
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jgomez Date 2011-11-10 Time 11:00 Rev Time 0.00
Received By jgomez Date 2011-11-10 Time 11:00 Sent To  
Notes
2011-11-10 11:01:01BUILDING REVIEW APPROVED WITH PROVISO:
 1- SHEET S-2: TRUSS DESIGN CRITERIA NOTE #7 SAYS "NO
 ATTIC STORAGE IN THIS RESIDENCE". THEN, CLARIFY WHY
 ATTIC ACCESS HAS A PULL DOWN STAIR?. SEE FOOTNOTES B,G,
 AND H ON TABLE R301.5 AND REVISE DESIGN LOADS AS
 REQUIRED.
 ***NOTE: TRUSS DRAWINGS NEED TO BE REVISED ACCORDINGLY.
  
 2- REVISE THE ENERGY CALCULATIONS SUBMITTED: A) ATTIC
 IS VENTED, NOT UNVENTED. SEE PLANS. B) REVISE CEILING R
 VALUE TO MATCH PLANS. C) THERE ARE NOT INSULATED DOORS.
 SEE PLANS AND PRODUCT APPROVALS SUBMITTED AND REVISE AS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-12 Cont ID  
Sent By jgomez Date 2011-10-12 Time 16:43 Rev Time 0.00
Received By jgomez Date 2011-10-12 Time 16:43 Sent To  
Notes
2011-10-12 16:46:14NSF RESIDENCE (R3) BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE W/ 2009 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT.
  
 2- VALUED DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. IT WAS UPDATED AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC. REVISED PERMIT FEE BALANCE IS
 $6550.58.
  
 3- SOIL TEST REPORT SUBMITTED NEEDS TO HAVE THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 4- PROVIDE LOT DRAINAGE PLAN. SEC. R401.3.
  
 5- SHEET S-2:
 A) SPECIFY ALL LOADS AS REQUIRED BY SEC. R301.1 AND
 TABLE R301.5. INCLUDE ALL ATTIC LIVE LOADS REQUIRED BY
 TABLE R301.5 AND FOOTNOTES B, G, AND H. COORDINATE WITH
 ITEM #5D BELOW.
  
 B) REVISE CASCRETE UPLIFT CALCULATIONS. NEED TO USE
 EXPOSURE "C" NOT "B".
  
 C) REVISE TRUSS DESIGN CRITERIA. USE ASCE 7-05
 REFERENCE NOT ASCE 7-02.
  
 D) SPECIFY THE 30PSF LIVE LOAD ON THE TRUSS LOADS AS
 SPECIFIED ON NOTE #7 OF THE TRUSS DESIGN CRITERIA
 TABLE.
 ***NOTE: TRUSS DRAWINGS NEED TO BE REVISED ACCORDINGLY.
  
 E) FLORIDA PRODUCT APPROVAL NUMBERS LISTED ON THE
 CONNECTOR SCHEDULE NEED TO BE UPDATED USING 2007 CODE
 VERSION. VISIT DCA WEBSITE AND UPDATE ALL NUMBERS AS
 REQUIRED.
  
 F) REVISE DESIGN PARAMETERS NOTE #6. THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". AND, THERE IS NOT
 TABLE 1606.2D ON THE 2007 FBC.
  
 6- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) 18' WIDE GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON SHEET A-2. NOA 09-0128.06
 SUBMITTED DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) FLORIDA PRODUCT APPROVAL FL4760-R1 SUBMITTED IS FOR
 6'-8" DOORS. CLARIFY WHERE ARE THE 6'-8" DOORS GOING TO
 BE INSTALLED. PLANS CALL FOR 8'-0" DOORS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 8- REVISE THE ENERGY CALCULATIONS SUBMITTED:
 A) PLANS AND PRODUCT APPROVALS SUBMITTED ARE FOR
 CONCRETE TILE. ENERGY CALCULATIONS SPECIFY COMPOSITION
 SHINGLES. REVISE AS REQUIRED.
 B) THERE ARE NOT INSULATED DOORS. SEE PLANS AND PRODUCT
 APPROVALS SUBMITTED AND REVISE AS REQUIRED.
 C) THERE ARE NOT EXTERIOR WOOD DOORS. SEE PLANS AND
 PRODUCT APPROVALS SUBMITTED AND REVISE AS REQUIRED.
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM.
 INCLUDING THE NAME OF BUILDER.
  
 8- ENGINEER OF RECORD NEED TO UPDATE THE CERTIFICATE OF
 AUTHORIZATION FOR "THE ERNING CORPORATION". SEC.
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 471 FLORIDA STATUTE . CONTACT DBPR AND UPDATE AS
 REQUIRED.
  
 9- SHEET A-1: FLOOR PLAN IS MISSING THE WALL BETWEEN
 THE DINING ROOM AND GARAGE. REVISE AS REQUIRED. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 10 - SHEET S-3: REVISE THE ROOF SHEATHING NOTES ON THE
 TYPICAL WALL SECTIONS. RING SHANK NAILS AT 4"O.C. ARE
 REQUIRED ON ROOF ZONE #3 ALSO. NOT ONLY ON GABLE ENDS.
 SEE SEC. R803.2.3.1 AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-05 Cont ID  
Sent By rlecky Date 2011-10-05 Time 15:00 Rev Time 0.00
Received By rlecky Date 2011-10-05 Time 13:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-14 Cont ID  
Sent By jgomez Date 2011-11-14 Time 11:22 Rev Time 0.00
Received By jgomez Date 2011-11-02 Time 10:36 Sent To  
Notes
2011-11-02 10:36:41SENT TO R7 FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-02 Cont ID  
Sent By jgomez Date 2011-10-19 Time 10:35 Rev Time 0.00
Received By jgomez Date 2011-10-03 Time 11:03 Sent To  
Notes
2011-11-02 10:35:51LAST REVIEW DONE BY ZONING ON 10/19/11
2011-10-03 11:03:55SENT TO R4 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jgomez Date 2011-11-10 Time 11:01 Rev Time 0.00
Received By jgomez Date 2011-11-10 Time 11:01 Sent To  
Notes
2011-11-10 11:04:34TRACKING NO MU-2011-018585.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-10-12 Cont ID  
Sent By jgomez Date 2011-10-12 Time 09:39 Rev Time 0.00
Received By jgomez Date 2011-10-12 Time 09:39 Sent To  
Notes
2011-10-12 09:40:40BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jgomez Date 2011-11-14 Time 10:29 Rev Time 0.00
Received By jgomez Date 2011-11-14 Time 10:28 Sent To  
Notes
2011-11-14 10:34:45MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS:
 A) EQUIPMENT SIZING CALCULATIONS WERE DONE FOR WORST
 CASE SCENARIO. EQUIPMENT SIZING CAN'T BE DONE FOR WORST
 CASE. ACTUAL HOUSE DIRECTIONAL ORIENTATION NEED TO BE
 USED FOR THE CALCULATIONS. REVISE CALCULATIONS AND
 EQUIPMENT SIZING AS REQUIRED. SEC. N1107.AB.1.
  
 B) REVISE DOOR TYPE AND CEILING VENTILATION AND R VALUE
 TO MATCH REVISED ENERGY CALCULATIONS.
  
 C) REVISE EQUIPMENT SPECIFICATIONS ON A/C PLAN TO
 REFLECT REVISED CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-10-14 Cont ID  
Sent By jgomez Date 2011-10-14 Time 13:15 Rev Time 0.00
Received By jgomez Date 2011-10-14 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-11-14 Cont ID  
Sent By jgomez Date 2011-11-14 Time 11:21 Rev Time 0.00
Received By jgomez Date 2011-11-14 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-10-14 Cont ID  
Sent By jgomez Date 2011-10-14 Time 15:56 Rev Time 0.00
Received By jgomez Date 2011-10-14 Time 15:56 Sent To  
Notes
2011-10-14 16:25:54NSR RESIDENCE (R3) PLUMBING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLUMBING RISER DIAGRAM ON SHEET S-4 SHOWS OUTDOOR
 SHOWER CONNECTED TO THE SANITARY DRAINAGE. THIS IS NOT
 ALLOWED BY CITY ORDINANCE 90-125. REVISE AS REQUIRED.
  
 2- KITCHEN SINK AND DISHWASHER AREA SHOW 2" VENT TO
 ROOF. PLANS SHOW THAT THE KITCHEN SINK IS LOCATED ON AN
 ISLAND COUNTER. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 3- REVISE PLUMBING RISER DIAGRAM TO MATCH ACTUAL LAYOUT
 AND LOCATION OF FIXTURES AS SHOWN ON FLOOR PLANS. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 4- PER BUILDING OFFICIAL, PLUMBING RISER DIAGRAM MAY BE
 DRAWN BY THE LICENSED PLUMBER CONTRACTOR DOING THE JOB
 AS LONG AS HE/SHE PROVIDES THE NAME, LICENSE NUMBER AND
 SIGN THE DIAGRAM.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2011-11-09 Cont ID  
Sent By jroach Date 2011-11-09 Time 16:27 Rev Time 0.00
Received By jroach Date 2011-11-09 Time 16:27 Sent To  
Notes
2011-11-09 16:28:24ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.09.2011
 PERMIT NO.: 11090809
 ADDRESS: 3300 EMBASSY DRIVE
 CONTRACTOR/CONTACT: GAIL ANDERSON
 TELEPHONE NO.: 561.578.9826
 SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. MECHANICAL EQUIPMENT SHALL NOT ENCROACH MORE THAN
 FOUR (4) FEET INTO ANY REQUIRED SETBACK.
 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 SEPARATE PERMITS WILL BE REQUIRED FOR THE FOLLOWING:
 A. DRIVEWAY AND APPROACH
 B. LANDSCAPING
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2011-10-19 Cont ID  
Sent By jroach Date 2011-10-19 Time 13:45 Rev Time 0.00
Received By jroach Date 2011-10-19 Time 13:45 Sent To  
Notes
2011-10-19 13:45:38ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.19.2011
 PERMIT NO.: 11090809
 ADDRESS: 3300 EMBASSY DRIVE
 CONTRACTOR/CONTACT: GAIL ANDERSON
 TELEPHONE NO.: 561.578.9826
 SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE THE DIMENSIONS FROM THE PROPOSED
 MECHANICAL EQUIPMENT TO THE ADJACENT PROPERTY LINES.
 EQUIPMENT SHALL NOT ENCROACH MORE THAN FOUR (4) FEET
 INTO THE REQUIRED SETBACK.
  
 2. THE FLOOR PLAN INDICATES POOL EQUIPMENT?IS A POOL
 BEING PROPOSED AS PART OF THE NEW CONSTRUCTION?
  
 3. A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 DRIVEWAY/APRON. PLEASE NOTE THAT 75 PERCENT, OR 1,000
 SQUARE FEET (WHICHEVER IS LESS) OF THE FRONT YARD SHALL
 CONSIST OF LANDSCAPE MATERIAL.
  
 4. A SEPARATE LANDSCAPE PERMIT WILL BE REQUIRED. THE
 LANDSCAPE PERMIT APPLICATION SHALL INCLUDE PLANS
 INDICATING COMPLIANCE WITH ARTICLE XIV OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS AND A CERTIFIED
 COST ESTIMATE. THE PERMIT APPLICATION FOR THE
 LANDSCAPING SHALL AT LEAST BE SUBMITTED PRIOR TO THE
 ISSUANCE OF A PERMIT FOR THE RESIDENCE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved