| | IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK |
| | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |
| | PER LOCAL POLICY, FIRE DEPARTMENT CONNECTIONS SHALL |
| | HAVE A SIAMESE CONNECTION. |
| | |
| | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | INDICATE THE METHOD USED TO SUPPORT THE BACKFLOW |
| | PREVENTOR. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| | DEPARTMENT CONNECTION AND MAIN SPRINKLER CONTROL VALVE. |
| | |
| | THE SPRINKLER SPRAY IS OBSTRUCTED BY THE SOFFIT |
| | (6-INCHES LOWER) IN LARGE CONFERENCE ROOM #102. |
| | |
| | THE ONLY SPRINKLER PIPING PERMITTED IN THE ELECTRICAL |
| | ROOM IS THE BRANCH LINE SUPPLYING THE SPRINKLER. |
| | RELOCATE THE INSPECTOR'S TEST CONNECTION. |
| | |
| | THE HYDRAULIC AREA FOR DESIGN AREA #1 SHALL BE AT LEAST |
| | 36 FEET LONG WHEN USING 1.2 MULTIPLIED BY 900 SQUARE |
| | FEET. |
| | |
| | PROVIDE A SECTION DETAIL INDICATING THE SPRINKLER |
| | LOCATIONS IN THE COMBUSTIBLE CONCEALED ROOF SPACE WITH |
| | REGARDS TO THE SLOPED ROOF FRAMING MEMBERS. |
| | |
| | PROVIDE HYDRAULIC CALCULATIONS FOR THE SPRINKLERS |
| | PROTECTING THE COMBUSTIBLE CONCEALED SPACE. THE SYSTEM |
| | AREA OF OPERATION SHALL BE INCREASED BY 30 PERCENT WHEN |
| | THE CEILING PITCH EXCEEDS ONE IN SIX. |
| | |