Plan Review Details - Permit 11090776
Plan Review Stops For Permit 11090776
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-26 Cont ID  
Sent By jwitmer Date 2011-10-26 Time 16:46 Rev Time 0.55
Received By jwitmer Date 2011-10-26 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-03 Cont ID  
Sent By jwitmer Date 2011-10-03 Time 15:34 Rev Time 0.75
Received By jwitmer Date 2011-10-03 Time 15:34 Sent To  
Notes
2011-10-03 16:37:09BUILDING PLAN REVIEW
 PERMIT: 11090776
 ADD: 2260 PALM BEACH LAKES # 201
 CONT: LTL BUILDERS, INC
 TEL: (561)628-9753
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) OPERATING ROOM # 1, THE LAB AND LUNCH ROOM DOORS
 NEED TO COMPLY WITH:
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2007 EXISTING BUILDING CODE: 706.1
 GENERAL. A BUILDING, FACILITY, OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH CHAPTER 11 OF THE FLORIDA
 BUILDING CODE, BUILDING .
 FBC-B 11-4.13.6 MANEUVERING CLEARANCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE
 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR. 18 INCHES AT LATCH
 FOR A PULL DOOR.
  
 2) PLEASE REVIEW SECTION FBC-B 11-4.13.7 TWO DOORS IN
 SERIES. 11-4.13.7 TWO DOORS IN SERIES. THE MINIMUM
 SPACE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES
 SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH OF ANY DOOR
 SWINGING INTO THE SPACE. DOORS IN SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE
 BETWEEN THE DOORS [SEE FIGURE 26(A)].
  
 3) LUNCH ROOM SINK WILL NEED TO COMPLY WITH SECTIONS:
 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE
 THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT
 LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE,
 AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS.
 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK (SEE FIGURE 32).
 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT.
 THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-11-02 Cont ID  
Sent By rlecky Date 2011-11-02 Time 14:25 Rev Time 0.00
Received By rlecky Date 2011-11-02 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-05 Cont ID  
Sent By rlecky Date 2011-10-05 Time 13:35 Rev Time 0.00
Received By rlecky Date 2011-10-05 Time 11:28 Sent To  
Notes
2011-10-05 13:41:29SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 FBC EXISTING BUILDING 711.1
  
 WIRING METHODS IN THE X-RAY AND OPERATING ROOMS (
 PATIENT CARE AREAS) MUST USE A METAL RACEWAY WITH AN
 INSULATED GROUNDING CONDUCTOR OR LISTED CABLE WHICH
 PROVIDES AN EFFECTIVE GROUND FAULT CURRENT PATH. NEC
 517.13(A) AND (B)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-26 Cont ID  
Sent By wjolin Date 2011-10-26 Time 13:58 Rev Time 0.00
Received By wjolin Date 2011-10-26 Time 13:37 Sent To  
Notes
2011-10-26 13:58:342260 PALM BEACH LAKES BOULEVARD - SUITE #201
 PERMIT #11090776
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-26 Cont ID  
Sent By wjolin Date 2011-10-26 Time 13:37 Rev Time 0.00
Received By wjolin Date 2011-10-04 Time 10:42 Sent To  
Notes
2011-10-04 11:04:002260 PALM BEACH LAKES BOULEVARD - SUITE #201
 PERMIT #11090776
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS ON THE COVER SHEET DOES NOT MATCH THE
 ADDRESS SHOWN IN THE TITLEBLOCK INFORMATION.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 NO DOOR SCHEDULE PROVIDED.
  
 PLANS INDICATE TWO EMERGENCY LIGHTING FIXTURES.
 ADDITIONAL FIXTURES MAY BE NEEDED TO ACHIEVE 1-FOOT
 CANDLE OF LIGHT ALONG THE ENTIRE PATHS OF EGRESS.
  
 PLANS INDICATE SMOKE DETECTORS; HOWEVER, NO ELECTRICAL
 CIRCUIT IS INDICATED TO POWER THESE DEVICES. INDICATE
 IF THESE DETECTORS ARE SINGLE STATION OR MULTISTATION
 AND IF THEY ARE PART OF A FIRE ALARM SYSTEM. PROVIDE
 ADDITIONAL INFORMATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-02 Cont ID  
Sent By lwagner Date 2011-11-02 Time 15:07 Rev Time 0.00
Received By lwagner Date 2011-10-24 Time 14:02 Sent To  
Notes
2011-10-24 14:10:59SENT TO B4 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-13 Cont ID  
Sent By shill Date 2011-10-13 Time 16:35 Rev Time 0.00
Received By shill Date 2011-09-29 Time 08:48 Sent To  
Notes
2011-09-30 08:53:17B5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-10-26 Cont ID  
Sent By jwitmer Date 2011-10-26 Time 16:53 Rev Time 0.44
Received By jwitmer Date 2011-10-26 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-10-12 Cont ID  
Sent By hmoser Date 2011-10-12 Time 15:20 Rev Time 0.00
Received By hmoser Date 2011-10-12 Time 15:20 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2011-11-02 Cont ID  
Sent By lwagner Date 2011-11-02 Time 15:19 Rev Time 0.00
Received By lwagner Date 2011-11-02 Time 15:19 Sent To  
Notes
2011-11-02 15:20:16SEPARATE MED GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-11-02 Cont ID  
Sent By lwagner Date 2011-11-02 Time 14:23 Rev Time 0.00
Received By lwagner Date 2011-10-28 Time 13:36 Sent To  
Notes
2011-11-02 14:26:56***PROVISO***
 REVISION REQUIRED
 DRINKING FOUNTAIN REQUIRED 403.1
 SEPARATE MED GAS APPLICATION, AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-10-05 Cont ID  
Sent By lwagner Date 2011-10-05 Time 10:15 Rev Time 0.00
Received By lwagner Date 2011-10-04 Time 14:55 Sent To  
Notes
2011-10-04 15:02:33FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1) NEITHER THE PLUMBING SUPPLY NOR THE SANITARY PLANS
 INDICATE COMPLIANCE WITH 2007/09 FBC-P TABLE 403.1 FOR
 A DRINKING FOUNTAIN.
  
 2) THE PLUMBING SUPPLY RISER PLAN INDICATES A WATER
 HEATER BUT THIS APPLIANCE IS NOT LOCATED ON THE
 ARCHITECTURAL PLANS.
 THE PLUMBING SHEET FAILS TO PROVIDE INFORMATION ON
 SAFETY DEVICES :
  
 504.4 RELIEF VALVES.
 504.6 REQUIREMENTS FOR DISCHARGE PIPING.
 504.7 REQUIRED PAN.
 504.7.1 PAN SIZE & DRAIN
 504.7.2 PAN DRAIN TERMINATION.
  
 4) THE WATER PIPE ISO. ON SHEET M-2 HAS NO PIPE SIZE.
  
 5. THE MECHANICAL AREA MAY REQUIRE SANITARY DRAIN,
 VENT, DOMESTIC WATER, ETC. FOR THE VACUUM PUMP AND
 COMPRESSOR ( VACUUM DRAINS SHALL BE CONNECTED DIRECTLY
 TO SANITARY , TRAPPED, AND VENTED NFPA 99C 2005
 5.3.3.6.3)
  
 *****NOTE*****
 THE ELECTRIC SHEET E2 DOES INDICATE A VACUUM AND
 COMPRESSOR; NO MEDICAL GAS PLANS WERE SUBMITTED. A
 MED-GAS PERMIT WILL NEED TO BE ISSUED BEFORE A FRAMING
 AND PLUMBING ROUGH TO BE CERTAIN THAT NO MED-GAS LINES
 ARE TO BE INSTALLED BELOW GRADE. MED-GAS WILL BE
 REVIEWED UNDER A SEPARATE PERMIT WITH SEPARATE PLANS
 AND FEES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-10-12 Cont ID  
Sent By lfranco Date 2011-10-12 Time 15:38 Rev Time 0.25
Received By lfranco Date 2011-10-12 Time 15:38 Sent To  
Notes
2011-10-12 15:41:44 
 PLANNING AND ZONING: ***ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ***
  