Plan Review Details - Permit 11090600
Plan Review Stops For Permit 11090600
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-14 Cont ID  
Sent By rmcdouga Date 2011-10-14 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2011-10-14 Time 10:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-29 Cont ID  
Sent By rmcdouga Date 2011-09-29 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2011-09-29 Time 08:13 Sent To  
Notes
2011-09-29 11:05:232007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF MOUNTING DETAILS FOR A 140 MPH 3
 SECOND GUST WIND SPEED AND EXPOSURE CATEGORY C THAT
 HAVE BEEN SIGNED AND SEALED BY A FLORIDA LICENSED
 ENGINEER. FBC R301.2.1 AND FS 471 THE ONES THAT WERE
 SUBMITTED ARE NOT ACCEPTABLE.
  
 2) THE MOUNTING DETAILS THAT WERE SUBMITTED REFERENCE A
 CODE THAT HAS NOT BEEN ADOPTED BY THE STATE OF FLORIDA.
 THE 2007 FLORIDA BUILDING CODE WITH 2009 REVISIONS IS
 THE CODE THAT APPLIES TO THIS PROJECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-14 Cont ID  
Sent By rmcdouga Date 2011-10-14 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2011-10-12 Time 16:38 Sent To  
Notes
2011-10-12 16:38:09TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-29 Cont ID  
Sent By rmcdouga Date 2011-09-29 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2011-09-23 Time 12:51 Sent To  
Notes
2011-09-23 12:51:33SENT TO PLUMBING UNDER $5000 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-10-17 Cont ID  
Sent By rmcdouga Date 2011-10-17 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2011-10-17 Time 15:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-10-14 Cont ID  
Sent By rmcdouga Date 2011-10-14 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2011-10-14 Time 10:44 Sent To  
Notes
2011-10-14 10:46:192007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 THE COMMENTS FROM THE FIRST REVIEW WERE NOT ADDRESSED.
 SEE BELOW.
  
 1) SUBMIT TWO COPIES OF A PIPING SCHEMATIC FOR THE
 SOLAR WATER HEATING SYSTEM. SHOW ISOLATION VALVE
 LOCATIONS, CIRCULATION PUMP, RELIEF VALVES, ETC. THAT
 WILL BE INSTALLED WITH THIS SYSTEM. SHOW COMPLIANCE
 WITH FBC R CHAPTER 23.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-09-29 Cont ID  
Sent By rmcdouga Date 2011-09-29 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2011-09-29 Time 11:10 Sent To Z
Notes
2011-09-29 11:30:232007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF A PIPING SCHEMATIC FOR THE
 SOLAR WATER HEATING SYSTEM. SHOW ISOLATION VALVE
 LOCATIONS, CIRCULATION PUMP, RELIEF VALVES, ETC. THAT
 WILL BE INSTALLED WITH THIS SYSTEM. SHOW COMPLIANCE
 WITH FBC R CHAPTER 23.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-10-12 Cont ID  
Sent By jroach Date 2011-10-12 Time 08:51 Rev Time 0.00
Received By jroach Date 2011-09-30 Time 14:21 Sent To  
Notes
***NONE***