Plan Review Details - Permit 11090586
Plan Review Stops For Permit 11090586
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-08 Cont ID  
Sent By jwitmer Date 2011-11-08 Time 12:29 Rev Time 1.22
Received By jwitmer Date 2011-11-08 Time 07:30 Sent To  
Notes
2011-11-08 13:14:56BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SUBMIT WINDOW PRODUCT APPROVAL FBEFORE BUCK WINDOW
 INSPECTION.
  
 2) ROOFER TO SUBMIT PRODUCT APPROVALS UNDER SEPERATE
 PERMIT W/ ASSOCIATED FEES & REVIEW.
 NOTE ENERGY CALCULATIONS INDICATE SINGLE PLY SYSTEM W/
 2" ISO INSULATION/ 2" CONCRETE/ METAL DECK .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-23 Cont ID  
Sent By jwitmer Date 2011-09-23 Time 13:37 Rev Time 1.50
Received By jwitmer Date 2011-09-23 Time 13:37 Sent To  
Notes
2011-09-23 14:54:34BUILDING PLAN REVIEW
 PERMIT: 11090586
 ADD: 303 SOUTHERN BLVD
 CONT: H GROUP GENERAL CONTRACTORS
 TEL: (561)262-0306
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE PLANS INDICATE THIS BUILDING TO BE A TYPE: II-B
  
 1) 10/03/11 PLEASE SEE NOTE VOIDING THE FIRST COMMENT
 AT END OF REVIEW!!!
 BUILDING CODE DATA: MISSING CODE INFORMATION, THE
 OCCUPANT LOAD OF THE EXISTING BUILDING AND NEW LOAD
 BEING ADDED BY THE CREATION OF AN ADDITION.
 2007/09 FBC- EXISTING BUILDING CODE 1001.2 CREATION OR
 EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE ADDITION IS BEING MADE WITH
 REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING, OR ELECTRICAL SYSTEMS.
  
 2007/09 FBC-B
 903.2.1.2 GROUP A-2. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE PROVIDED FOR GROUP A-2 OCCUPANCIES WHERE ONE
 OF THE FOLLOWING CONDITIONS EXISTS:
  
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2).
  
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
  
 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE
 LEVEL OF EXIT DISCHARGE.
  
 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS
 100 OR MORE.
  
  
 2) PLANS INDICATE WIND PRESSURE BUT MISSING THE WIND
 DESIN CRITERIA: LOCATION IS AN EXPOSURE C WITH EXPOSURE
 AND HEIGHT FACTORS OF 1.29 FOR 20 FT ELEVATION.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) SHEET A-2 INDICATES AN 8'-0" LONG RAMP WILL NEED TO
 COMPLY WITH:
  
 3A) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL
 NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP
 SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE. MISSING THE BOTTOM LANDING.
  
 3B) 11-4.8.4(3) IF RAMPS CHANGE DIRECTION AT LANDINGS,
 THE MINIMUM LANDING SIZE SHALL BE 60" X 60".
  
 3C) 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER
 THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 4) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 4A) EXTERIOR DOORS
  
 4B) EXTERIOR WINDOWS
  
 4C) ROOFING ASSEMBLIES
  
 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) SHEET A-3 DETAIL # 4 DETAIL OF MANSARD TRUSS
 INDICATES A SIMPSON MET 18 STRAP TO TIE OFF THE TOP OF
 THE TRUSS BUT THERE IS NO ANCHORING SYSTEM FOR THE
 BOTTOM PARTION OF THE MANSARD TRUSS, HOW WILL THE
 UPLIFT, SLIDDING AND GRAVITY FORCES BE HANDED AT THIS
 POINT OF CONTACT, PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM.
  
 7) THIS BUILDING IS DECLARED A TYPE II B STRUCTURE
 PLEASE REVIEW SECTION 603.1.3. IT WOULD APPEAR THE
 BUILDING COULD BE DESIGNED TO A LESSER BUILDING TYPE
 WITH AREA INCREASES AND IF SPRINKLERS ARE REQUIRED THE
 ADDTIONAL SQ FOOTAGE ALLOWED FOR SPRINKLERS.
  
 8) THE PLANS DO NOT CONSIDER THE ENERGY CODE, NO FORMS
 WERE SUBMITTED, 13-400.2.A.1 ADDITIONS.
  
 9) SHEET M1 INDICATES A ROOF TOP CURB DETAIL BUT WITH A
 CORRIGATED B TYPE METAL ROOF SYSTEM NOT A PRECAST
 HOLLOW CORE SYSTEM, PLEASE INDICATE THE CORRECT CURB
 ATTACHMENT.
  
 10) PLANS DO NOT ADDRESS ANY INTERIOR FINISHES FBC-B
 TABLE 803.5.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 10/03/11
 NOTE:
 THE FIRST COMMENT IS TO BE STRIKEN, THE EXISTING
 BUILDING CODE 1002.3 FIRE PROTECTION REFERS BACK TO
 THTE FBC-B REQUIRING FIRE SPRINKLER PROTECTION IF THE
 BUILDING NEEDS FIRE SPRINKLERS BECAUSSE OF THE
 ADDITIONAL SQUARE FOOTAGE BEING ADDED AND BEING OVER
 THE ALLOWABLE SQUARE FOOTAGE OF FBC-B TABLE 503/ A-2/
 TYPE II-B CONSTRUCTION ALLOWABLE AREA 9,500 SQUARE
 FEET. THIS BUILDING AND ADDITION IS SMALLER THAN THAT
 WHICH WILL QUALIFY THE BUILDING FOR NOT REQUIRING FIRE
 SPRINKLERS IN EITHER THE ADDITION NOR THE ORIGINAL
 BUILDING.
  
 THIS BUILDING ALSO IS NOT A CHANGE IN OCCUPANCY WHICH
 WOULD HAVE TRIGGERED THE THE REQUIREMENT OF FIRE
 SPRINKLERS UNDER THE EXISTING BUILDING CODE. NO FIRE
 SPRINKLERS REQUIRED UNDER 2007/09 EXISTING BUILDING
 CODE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-30 Cont ID  
Sent By rlecky Date 2011-09-30 Time 15:30 Rev Time 0.00
Received By rlecky Date 2011-09-30 Time 15:30 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-11-07 Cont ID  
Sent By mgonzale Date 2011-11-07 Time   Rev Time 0.50
Received By mgonzale Date 2011-11-07 Time   Sent To  
Notes
2011-11-07 15:50:03PLANS REVISED AND PASSED.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-10-26 Cont ID  
Sent By mgonzale Date 2011-10-26 Time   Rev Time 0.50
Received By mgonzale Date 2011-10-26 Time   Sent To  
Notes
2011-10-26 22:38:58FAILED STATUS:
  
 #1 SHOW BETTER DETAIL OF HANDICAP RAMP. LENGTH
 DIMENSION. IF HAND RAILS. SHOW ELEVATIONS AND IF NOT
 SHOW CROSS SECTION.
 CALL OUT LANDING AREAS AND CLEARLY IDENTIFY DOOR.
  
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING SERVICES
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-08 Cont ID  
Sent By wjolin Date 2011-11-08 Time 13:29 Rev Time 0.00
Received By wjolin Date 2011-11-08 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-09-30 Cont ID  
Sent By wjolin Date 2011-09-30 Time 14:43 Rev Time 0.00
Received By wjolin Date 2011-09-30 Time 14:07 Sent To  
Notes
2011-09-30 14:43:54330 SOUTHERN BOULEVARD
 PERMIT #11090586
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE FURNITURE PLAN FOR NEW BAR AREA.
  
 PROVIDE OCCUPANT LOAD FOR SHOWING COMBINED LOAD FOR NEW
 AND EXISTING FLOOR AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-09 Cont ID  
Sent By jwitmer Date 2011-11-09 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2011-11-02 Time 10:09 Sent To  
Notes
2011-11-02 10:09:09B21
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-12 Cont ID  
Sent By hmoser Date 2011-10-26 Time 13:48 Rev Time 0.00
Received By lmartine Date 2011-09-22 Time 08:36 Sent To  
Notes
2011-09-23 08:46:46B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-11-07 Cont ID  
Sent By jwitmer Date 2011-11-07 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2011-11-07 Time 16:03 Sent To  
Notes
2011-11-07 16:04:37PB COUNTY IMPACT FEES
 RECEIPT # 2011-1028-136
 TOTAL $4,494.95

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-10-12 Cont ID  
Sent By hmoser Date 2011-10-12 Time 13:47 Rev Time 0.00
Received By hmoser Date 2011-10-12 Time 13:27 Sent To ENG-P
Notes
2011-10-12 13:47:34PROVIDE A DETAIL FROM THE ENGINEER FOR CURB TO ROOF AND
 UNIT TO CURB TIE DOWN.
 FOR FIRST INSPECTION.
 CAN NOT READ THE DETAIL ON THE PLANS .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-11-09 Cont ID  
Sent By eschneid Date 2011-11-09 Time 14:55 Rev Time 0.50
Received By eschneid Date 2011-11-09 Time 14:55 Sent To  
Notes
2011-11-09 15:01:42PASSED W/PROVISO
  
 1) EACH PLANTER BED TO CONTAIN 1 SHADE/ FLOWERING TREE
 OR PALM EQUIVALENT.
  
 2) THE NEW PLANTING AREAS REQUIRE THE SUBMITTAL AND
 APPROVAL OF A LANDSCAPE PERMIT. THE APPROVED LANDSCAPE
 TO BE INSTALLED PRIOR TO C.O OR FINAL INSPECTION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-09-26 Cont ID  
Sent By eschneid Date 2011-09-26 Time 16:27 Rev Time 0.50
Received By eschneid Date 2011-09-26 Time 16:27 Sent To  
Notes
2011-09-26 16:34:32FAILED
  
 1) PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR OLD, OF
 THE PROPERTY. THE SURVEY SHALL INCLUDE ALL EASEMENTS
 AND OVERHEAD LINES.
  
 2) THIRTY (30) PERCENT OF THE LINEAR FEET AROUND THE
 ADDITION SHALL BE PLANTED WITH FOUNDATION PLANTING. THE
 FOUNDATION PLANTING REQUIRES A SEPARATE LANDSCAPE
 PERMIT.
  
 3) THE SITE PLAN SHALL INCLUDE DIMENSIONS AND SETBACKS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.