Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-11-28 Cont ID  
Sent By rlecky Date 2011-11-28 Time 09:43 Rev Time 0.00
Received By rlecky Date 2011-11-28 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-03 Cont ID  
Sent By rlecky Date 2011-10-03 Time 09:32 Rev Time 0.00
Received By rlecky Date 2011-10-03 Time 09:30 Sent To  
Notes
2011-10-03 09:32:44PENDING RESPONSE TO FIRE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-15 Cont ID  
Sent By wjolin Date 2011-11-15 Time 09:35 Rev Time 0.00
Received By wjolin Date 2011-11-14 Time 13:15 Sent To M
Notes
2011-11-15 09:35:002223 PALM BEACH LAKES BOULEVARD
 PERMIT #11090530
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 NOTE: CONTRACTOR IS PROCEEDING AT OWN RISK AS MASTER
 PERMIT (#11110177 ) HAS NOT BEEN ISSUED.
  
 INDICATE THE CANDELA RATING OF EACH VISUAL APPLIANCE.
  
 ENTIRE FIRE ALARM SYSTEM SHALL BE UL (OR EQUAL)
 CERTIFICATED FOR CENTRAL STATION SERVICE BY FINAL FIRE
 INSPECTION.
  
 TO MEET THE AUDIBILITY REQUIREMENTS OF NFPA 72, THE
 FIRE ALARM SYSTEM NEEDS TO BE INTEGRATED WITH THE
 BUILDING SOUND SYSTEM TO CUT POWER TO THE NON-FIRE
 ALARM SPEAKERS IN AN ALARM CONDITION.
  
 FIRE ALARM FLOOR PLAN NEEDS TO BE UPDATED TO THE NEW
 FLOOR PLAN PER THE MASTER PERMIT #11110177. ADDITIONAL
 NOTIFICATION APPLIANCES AND A PULL STATION WILL NEED TO
 BE ADDED BASED UPON NEW FLOOR PLAN.
  
 UPDATE VOLTAGE DROP AND BATTERY CALCULATIONS TO BREAK
 DOWN THE QUANTITY OF DEVICES. CURRENT CALCULATIONS ONLY
 INDICATE 1 DEVICE. INDICATE THE SIZE OF THE EXISTING
 BATTERY POWER SUPPLY.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. INDICATE THE EXACT MESSAGE ON THE
 PLANS.
  
 INDICATE LOCATION OF NEW REMOTE ANNUNCIATOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-09-22 Cont ID  
Sent By wjolin Date 2011-09-22 Time 13:41 Rev Time 0.00
Received By wjolin Date 2011-09-22 Time 13:16 Sent To M
Notes
2011-09-22 13:41:052223 PALM BEACH LAKES BOULEVARD
 PERMIT #11090530
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADDRESS ON PLANS DOES NOT MATCH THE ADDRESS ON THE
 PERMIT APPLICATION.
  
 NO DRAWING SCALE PROVIDED.
  
 NO VOLTAGE DROP OR BATTERY CALCULATIONS PROVIDED.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 NO OCCUPANCY TYPE INDICATED ON THE PLANS.
  
 NOTIFICATION APPLIANCES IN RESTROOMS NOT PROVIDED WITH
 IDENTIFICATION NUMBER.
  
 INDICATE IF THE EXISTING CRICUITS ARE BEING EXTENDED
 INTO THE NEW AREAS OR IF NEW CIRCUITS ARE BEING
 PROVIDED.
  
 INDICATE THE CANDELA RATING OF EACH VISUAL APPLIANCE.
  
 INDICATE THE CLASS AND STYLE OF WIRING.
  
 THE LOCATIONS OF THE NOTIFICATION APPLIANCES APPEAR TO
 BE GROSSLY OVERSPACED.
  
 ADDING NOTIFICATION APPLIANCES WILL INCREASE THE JOB
 VALUE BEYOND $5,000 AND WILL REQUIRE A PROFESSIONAL
 ENGINEER TO SIGN AND SEAL THE PLANS.
  
 THE AREA INDICATED AS "EVENT HALL ADDITION" ALREADY
 APPEARS TO BE PART OF AN EXISTING APPLIED FOR PERMIT
 (#11070070). SUB-PERMITS ARE GENERALLY NOT ISSUED
 BEFORE MASTER BUILDING PERMITS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-28 Cont ID  
Sent By rlecky Date 2011-11-28 Time 09:43 Rev Time 0.00
Received By rlecky Date 2011-10-14 Time 10:26 Sent To  
Notes
2011-10-14 10:27:10INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-03 Cont ID  
Sent By hmoser Date 2011-09-30 Time 14:39 Rev Time 0.00
Received By rlecky Date 2011-09-22 Time 08:35 Sent To  
Notes
2011-09-22 08:35:31INCOMING SENT TO FIRE BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-17 Cont ID  
Sent By hmoser Date 2011-11-17 Time 12:40 Rev Time 0.00
Received By hmoser Date 2011-11-17 Time 12:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-09-30 Cont ID  
Sent By hmoser Date 2011-09-30 Time 14:39 Rev Time 0.00
Received By hmoser Date 2011-09-30 Time 14:39 Sent To E
Notes
2011-09-30 14:45:43PLANS DENIED
 REFER TO NOTES ON PLANS DUCT DETECTORS SUPPLIED BY
 OTHERS.
 SEPARATE PERMITS WILL BE REQUIRED FOR THE DUCT
 DETECTORS.
 ADDRESS ON PLANS AND APPLICATION DO NOT MATCH.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]