2011-09-22 13:04:46(ESPERANTE) 222 LAKEVIEW AVENUE - 8TH FLOOR COMMON AREA
 PERMIT #11090529
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. REDLINE THE
 AS-BUILT PLANS TO INDICATE THE HANGER TYPE OR METHOD TO
 BE USED FOR RESTRAINING UPWARD MOVEMENT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW