Plan Review Details - Permit 11090510
Plan Review Stops For Permit 11090510
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-09-27 Cont ID  
Sent By rmcdouga Date 2011-09-27 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2011-09-27 Time 08:31 Sent To  
Notes
2011-09-28 14:11:15BUILDING PROVISO
  
 SUBMIT SIGNED AND SEALED COPY OF THE ENERGY COMPLIANCE
 FORM AS REQUIRED BY FBC 13-103.1.1.1.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-26 Cont ID  
Sent By rlecky Date 2011-09-26 Time 14:46 Rev Time 0.00
Received By rlecky Date 2011-09-26 Time 14:46 Sent To  
Notes
2011-09-26 14:48:44AUDITED. REVIEW PERFORMED BY PRIVATE PROVIDER MTCI
 (S.553.791 F.S.)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-09-28 Cont ID  
Sent By wjolin Date 2011-09-28 Time 12:10 Rev Time 0.00
Received By wjolin Date 2011-09-28 Time 10:42 Sent To  
Notes
2011-09-28 12:10:291400 CENTREPARK BOULEVARD - SUITE #770
 PERMIT #11090510
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISED SHEETS*****
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INDICATE THE DOOR HARDWARE TO BE USED ON THE MAIN
 ENTRANCE. THE RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 SHEET A221: GENERAL FINISH NOTE #16 INDICATES THE USE
 OF FABRIC WALL PANELS. INDICATE THE SMOKE/FLAME SPREAD
 RATING OF THIS MATERIAL.
  
 SHEET FP101: GENERAL NOTE #24 INDICATES SHOP DRAWINGS
 TO BE SIGNED/SEALED BY A PROFESSIONAL ENGINEER. THE
 CONSTRUCTION DOCUMENTS ALREADY ESTABLISH JOSE MARTINEZ
 AS THE ENGINEER OF RECORD; THEREFORE, THE SHOP DRAWINGS
 SHALL NOT BE SEALED PER FLORIDA STATUTE 633.
  
 SHEET E201: FIRE ALARM SYSTEM NOT IN COMPLIANCE WITH
 NFPA 72 AS NO VISUAL NOTIFICATION APPLIANCES HAVE BEEN
 PROVIDED. ONE HORN DEVICE (SHOWN AS EXISTING) MAY ALSO
 BE INADEQUATE FOR THIS SIZE SPACE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-09-28 Time   Rev Time 0.00
Received By lmartine Date 2011-09-26 Time 10:38 Sent To  
Notes
2011-09-26 10:38:42B--15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-09-27 Cont ID  
Sent By hmoser Date 2011-09-27 Time 10:15 Rev Time 0.00
Received By hmoser Date 2011-09-27 Time 09:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-09-27 Cont ID  
Sent By rmcdouga Date 2011-09-27 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2011-09-27 Time 08:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-09-27 Cont ID  
Sent By jroach Date 2011-09-27 Time 14:27 Rev Time 0.00
Received By jroach Date 2011-09-27 Time 14:27 Sent To  
Notes
***NONE***