Plan Review Details - Permit 11090506
Plan Review Stops For Permit 11090506
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-11-22 Cont ID  
Sent By shill Date 2011-11-22 Time 14:27 Rev Time 0.00
Received By shill Date 2011-11-22 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-11-02 Cont ID  
Sent By jgomez Date 2011-11-02 Time 13:02 Rev Time 0.00
Received By jgomez Date 2011-11-02 Time 13:02 Sent To  
Notes
2011-11-02 13:14:29ROOFING RE-SUBMITTAL CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER DOING THE RAS 117 CALCULATIONS NEEDS TO
 REVISE THE FLAT ROOF BASE FASTENING SPACING FOR ZONE #2
 (PERIMETER AREA). ACCORDING TO SEC. 10.4.5 OF RAS 117,
 ALL FRACTIONS SHALL BE ROUNDED DOWN TO THE NEXT WHOLE
 NUMBER. ENGINEER SPECIFIES FASTENER SPACING AT 7.5".
 REVISE AS REQUIRED. NEED TO ROUND DOWN TO THE NEXT
 WHOLE NUMBER.
  
 2- ALL PRODUCT APPROVALS (METAL ROOFING AND FLAT ROOF
 ASSEMBLY) NEED TO BE REVIEWED AND APPROVED IN WRITING
 (NOT SIGNING AND SEALING) BY THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. SUBMIT
 ALL PRODUCT APPROVALS WITH THE ENGINEER'S OF RECORD
 APPROVAL.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-23 Cont ID  
Sent By jwitmer Date 2011-09-23 Time 10:11 Rev Time 0.25
Received By jwitmer Date 2011-09-23 Time 10:01 Sent To  
Notes
2011-09-23 10:33:50BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVAL SUBMITTED FOR FLAT DECK IS FOR
 LIGHTWEIGHT CONCRETE DECK AND ENGINEERING FROM HARVEY
 KOEHNEN IS ALSO FOR A LIGHTWEIGHT CONCRETE DECK.
 PLEASE SUBMIT THE PRODUCT APPROVAL AND INHANCED
 FASTENING FOR THE CORRECT DECK TYPE. SHEET A-3.01
 DETAIL # 3 INDICATES A 5/8 INCH CDX PLYWOOD DECK.
  
 2) THE A-3.01 SHEET DETAIL # 3 ALSO WILL NEED TO BE
 CORRECTED, PLANS INDICATE A METAL PANEL SYSTEM ON THE
 FLAT DECK AREA. IF THIS TYPE APPLICATION WILL BE
 INSTALLED THEN
 1507.4.2 DECK SLOPE REQUIREMENTS WILL NEED TO BE
 ADHERRED TOO.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-22 Cont ID  
Sent By shill Date 2011-11-22 Time 14:27 Rev Time 0.00
Received By shill Date 2011-11-21 Time 14:21 Sent To  
Notes
2011-11-21 14:21:55SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-02 Cont ID  
Sent By jgomez Date 2011-11-02 Time 13:02 Rev Time 0.00
Received By jgomez Date 2011-11-02 Time 13:02 Sent To  
Notes
***NONE***