Plan Review Details - Permit 11090479
Plan Review Stops For Permit 11090479
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-10-04 Cont ID  
Sent By jwitmer Date 2011-10-04 Time 11:11 Rev Time 1.25
Received By jwitmer Date 2011-10-04 Time 10:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-05 Cont ID  
Sent By rlecky Date 2011-10-05 Time 10:44 Rev Time 0.00
Received By rlecky Date 2011-10-05 Time 10:00 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-10-24 Cont ID  
Sent By mgonzale Date 2011-10-24 Time 12:22 Rev Time 1.00
Received By mgonzale Date 2011-10-24 Time 12:22 Sent To  
Notes
2011-10-24 12:23:13PLAN IS ACCEPTABLE.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-28 Cont ID  
Sent By wjolin Date 2011-10-28 Time 12:07 Rev Time 0.00
Received By wjolin Date 2011-10-28 Time 12:00 Sent To  
Notes
2011-10-28 12:07:464325 NORTH HAVERHILL ROAD
 PERMIT #11090479
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **COMMENTS WERE RESPONDED TO BY TELEPHONE CONVERSATION
 WITH JACKIE MICHELS ON 10/28/11 AT 12:00**
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE - NFPA 1 UNIFORM FIRE CODE.
 RESPONSE: EXISTING ACCESS ROADS ARE PROVIDED ADJACENT
 TO THE DELIVERY DRIVE ROAD.
  
 PROVIDE LISTED SECONDARY CONTAINMENT TANKS FOR LIQUID
 CHLORINE OR PROVIDE SPILL CONTROL AND SECONDARY
 CONTAINMENT FOR BUILDINGS STORING HAZARDOUS MATERIALS
 LIQUIDS IN EXCESS OF 55 GALLONS PER SECTION 60.3.2.8.2
 AND SECTION 60.3.2.8.3 OF FFPC - NFPA 1.
 RESPONSE: TANKS WILL BE DOUBLE-WALLED CONTAINMENT
 TANKS.
  
 PROVIDE TWO MEANS OF EGRESS FROM EACH BUILDING WHEN THE
 BUILDING SIZE EXCEEDS 200 SQUARE FEET PER SECTION
 60.3.2.4.3 OF FFPC - NFPA 1.
 RESPONSE: BUILDINGS WILL BE LESS THAN 100 SQUARE FEET.
  
 SOME SHEETS REFERENCE THE TANKS AS STORING SODIUM
 HYPOCHLORITE WHILE OTHER SHEETS INDICATE PURE CHLORINE.
 PLEASE CLARIFY WHAT MATERIAL WILL BE STORED.
 RESPONSE: CHEMICAL COMPOSITION WILL BE SODIUM
 HYPOCHLORITE CONSISTING OF 12% CHLORINE. AT 12%
 CHLORINE IS NOT DEEMED AN OXIDIZER.
  
 BUILDINGS CONTAINING HAZARDOUS MATERIALS TO BE
 IDENTIFIED WITH DIAMOND PLACARD INDICATING HEALTH,
 FLAMMABILITY AND REACTIVITY RATINGS PER NFPA 704.
 RESPONSE: DIAMOND PLACARDS WILL BE PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-04 Cont ID  
Sent By wjolin Date 2011-10-04 Time 15:12 Rev Time 0.00
Received By wjolin Date 2011-10-04 Time 13:27 Sent To  
Notes
2011-10-04 15:12:124325 NORTH HAVERHILL ROAD
 PERMIT #11090479
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE ? NFPA 1 UNIFORM FIRE CODE.
  
 PROVIDE LISTED SECONDARY CONTAINMENT TANKS FOR LIQUID
 CHLORINE OR PROVIDE SPILL CONTROL AND SECONDARY
 CONTAINMENT FOR BUILDINGS STORING HAZARDOUS MATERIALS
 LIQUIDS IN EXCESS OF 55 GALLONS PER SECTION 60.3.2.8.2
 AND SECTION 60.3.2.8.3 OF FFPC - NFPA 1.
  
 PROVIDE TWO MEANS OF EGRESS FROM EACH BUILDING WHEN THE
 BUILDING SIZE EXCEEDS 200 SQUARE FEET PER SECTION
 60.3.2.4.3 OF FFPC - NFPA 1.
  
 SOME SHEETS REFERENCE THE TANKS AS STORING SODIUM
 HYPOCHLORITE WHILE OTHER SHEETS INDICATE PURE CHLORINE.
 PLEASE CLARIFY WHAT MATERIAL WILL BE STORED.
  
 BUILDINGS CONTAINING HAZARDOUS MATERIALS TO BE
 IDENTIFIED WITH DIAMOND PLACARD INDICATING HEALTH,
 FLAMMABILITY AND REACTIVITY RATINGS PER NFPA 704.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-01 Cont ID  
Sent By hmoser Date 2011-11-01 Time 11:32 Rev Time 0.00
Received By hmoser Date 2011-09-21 Time 09:35 Sent To  
Notes
2011-09-21 09:35:31C3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By hmoser Date 2011-11-01 Time 11:32 Rev Time 0.00
Received By hmoser Date 2011-11-01 Time 11:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-10-26 Cont ID  
Sent By jroach Date 2011-10-26 Time 15:20 Rev Time 0.00
Received By jroach Date 2011-10-26 Time 15:19 Sent To  
Notes
***NONE***