| 2011-10-28 12:07:46 | 4325 NORTH HAVERHILL ROAD |
| | PERMIT #11090479 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | **COMMENTS WERE RESPONDED TO BY TELEPHONE CONVERSATION |
| | WITH JACKIE MICHELS ON 10/28/11 AT 12:00** |
| | |
| | FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE |
| | DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT |
| | LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED |
| | WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED |
| | VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES |
| | PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION |
| | CODE - NFPA 1 UNIFORM FIRE CODE. |
| | RESPONSE: EXISTING ACCESS ROADS ARE PROVIDED ADJACENT |
| | TO THE DELIVERY DRIVE ROAD. |
| | |
| | PROVIDE LISTED SECONDARY CONTAINMENT TANKS FOR LIQUID |
| | CHLORINE OR PROVIDE SPILL CONTROL AND SECONDARY |
| | CONTAINMENT FOR BUILDINGS STORING HAZARDOUS MATERIALS |
| | LIQUIDS IN EXCESS OF 55 GALLONS PER SECTION 60.3.2.8.2 |
| | AND SECTION 60.3.2.8.3 OF FFPC - NFPA 1. |
| | RESPONSE: TANKS WILL BE DOUBLE-WALLED CONTAINMENT |
| | TANKS. |
| | |
| | PROVIDE TWO MEANS OF EGRESS FROM EACH BUILDING WHEN THE |
| | BUILDING SIZE EXCEEDS 200 SQUARE FEET PER SECTION |
| | 60.3.2.4.3 OF FFPC - NFPA 1. |
| | RESPONSE: BUILDINGS WILL BE LESS THAN 100 SQUARE FEET. |
| | |
| | SOME SHEETS REFERENCE THE TANKS AS STORING SODIUM |
| | HYPOCHLORITE WHILE OTHER SHEETS INDICATE PURE CHLORINE. |
| | PLEASE CLARIFY WHAT MATERIAL WILL BE STORED. |
| | RESPONSE: CHEMICAL COMPOSITION WILL BE SODIUM |
| | HYPOCHLORITE CONSISTING OF 12% CHLORINE. AT 12% |
| | CHLORINE IS NOT DEEMED AN OXIDIZER. |
| | |
| | BUILDINGS CONTAINING HAZARDOUS MATERIALS TO BE |
| | IDENTIFIED WITH DIAMOND PLACARD INDICATING HEALTH, |
| | FLAMMABILITY AND REACTIVITY RATINGS PER NFPA 704. |
| | RESPONSE: DIAMOND PLACARDS WILL BE PROVIDED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |