Plan Review Details - Permit 11090451
Plan Review Stops For Permit 11090451
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-10-17 Cont ID  
Sent By rlecky Date 2011-10-17 Time 12:35 Rev Time 0.00
Received By rlecky Date 2011-10-17 Time 12:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-09-21 Cont ID  
Sent By rlecky Date 2011-09-21 Time 09:11 Rev Time 0.00
Received By rlecky Date 2011-09-21 Time 09:11 Sent To  
Notes
2011-09-21 09:18:08PLEASE INICATE ON THE PLAN TEH FOLLOWING: NEC 215.5,
 NEC T 300.5, 300.5(D) 3
  
 1. SIZE OF THE CONDUIT
 2. BURIAL DEPTH
 3. WARNING RIBBON REQUIRED 12 INCHES ABOVE SERVICE
 CONDUIT
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-17 Cont ID  
Sent By rlecky Date 2011-10-17 Time 12:35 Rev Time 0.00
Received By rlecky Date 2011-10-12 Time 14:02 Sent To  
Notes
2011-10-12 14:02:50TO ELEC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-21 Cont ID  
Sent By rlecky Date 2011-09-21 Time 09:11 Rev Time 0.00
Received By rlecky Date 2011-09-19 Time 16:25 Sent To  
Notes
2011-09-19 16:25:29UNDER 5 K ELECTRIC