| 2011-09-15 11:12:31 | 1450 CENTREPARK DRIVE - SUITE #250 |
| | PERMIT #11090302 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, |
| | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE. SEVERAL INTERIOR EXIT ACCESS DOORS ARE |
| | FITTED WITH CARD READERS THAT WOULD PROHIBIT OCCUPANTS |
| | FREE EGRESS THROUGHOUT THE TENANT SPACE. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | TRAINING ROOM #108 AND CORRIDOR #106 DOORS ARE REQUIRED |
| | TO SWING IN THE DIRECTION OF EGRESS TRAVEL FOR AN |
| | OCCUPANT LOAD OF 50 OR GREATER PERSONS PER SECTION |
| | 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION CODE: NFPA 101 |
| | - LIFE SAFETY CODE. |
| | |
| | TRAINING ROOM #108 HAS AN OCCUPANT LOAD EXCEEDING 50 |
| | PERSONS AND THEREFORE WOULD BE CONSIDERED AN ASSEMBLY |
| | OCCUPANCY. A SECOND EXIT FROM THIS ROOM REQUIRED AS THE |
| | COMMON PATH OF TRAVEL EXCEEDS 20 FEET. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET E-1: AN ADDITIONAL FIRE ALARM NOTIFICATION |
| | APPLIANCE IS NEEDED IN CORRIDOR #106 AND OPEN OFFICE |
| | #116 AS THE EXISTING DEVICE WILL NOT COVER THIS ENTIRE |
| | SPACE. ALSO, IT WILL BE DIFFICULT TO MEET THE DB |
| | REQUIREMENT IN TRAINING ROOM #108 WITH A STROBE ONLY |
| | NOTIFICATION APPLIANCE. |
| | |
| | SHEET E-1: NO NOTIFICATION APPLIANCES LOCATED IN OTHER |
| | COMMON AREAS: COPY #112, MEETING ROOMS #102, #103 AND |
| | #115. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |