Plan Review Details - Permit 11090291
Plan Review Stops For Permit 11090291
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-09-16 Cont ID  
Sent By jwitmer Date 2011-09-16 Time 11:12 Rev Time 0.35
Received By jwitmer Date 2011-09-16 Time 11:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-19 Cont ID  
Sent By rlecky Date 2011-09-19 Time 13:52 Rev Time 0.00
Received By rlecky Date 2011-09-19 Time 12:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-09-15 Cont ID  
Sent By wjolin Date 2011-09-15 Time 10:24 Rev Time 0.00
Received By wjolin Date 2011-09-15 Time 10:21 Sent To  
Notes
2011-09-15 10:23:09222 LAKEVIEW AVENUE - SUITE #800
 PERMIT #11090291
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 STROKE. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-19 Cont ID  
Sent By rlecky Date 2011-09-19 Time 13:56 Rev Time 0.00
Received By rlecky Date 2011-09-14 Time 14:08 Sent To  
Notes
2011-09-14 14:08:21B-2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-09-16 Cont ID  
Sent By jwitmer Date 2011-09-16 Time 11:13 Rev Time 0.22
Received By jwitmer Date 2011-09-16 Time 11:13 Sent To  
Notes
2011-09-16 11:16:19MECHANICAL PROVISO:
 1) SHEET M1 GENERAL NOTE # 14 SMOKE DETECTORS TO COMPLY
 WITH:
 606.2.1 SUPPLY AIR SYSTEMS. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM (0.9 M3/S), IN THE SUPPLY AIR
 DUCT.
  
 EXCEPTION: SMOKE DETECTORS ARE NOT REQUIRED IN THE
 SUPPLY AIR SYSTEM WHERE THE SPACE SERVED BY THE AIR
 DISTRIBUTION SYSTEM IS PROTECTED BY A SYSTEM OF AREA
 SMOKE DETECTORS IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE. THE AREA SMOKE DETECTOR SYSTEM SHALL
 COMPLY WITH SECTION 606.4.
  
 606.4.1 SUPERVISION. THE DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO A FIRE ALARM SYSTEM. THE ACTUATION OF A
 DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.
  
 EXCEPTIONS:
  
 1. THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES.
  
 2. IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A
 FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL
 ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL IN AN APPROVED
 LOCATION. DUCT SMOKE DETECTOR TROUBLE CONDITIONS SHALL
 ACTIVATE A VISIBLE OR AUDIBLE SIGNAL IN AN APPROVED
 LOCATION AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  