Plan Review Details - Permit 11090261
Plan Review Stops For Permit 11090261
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-01-19 Cont ID  
Sent By jwitmer Date 2012-01-19 Time 11:30 Rev Time 1.00
Received By jwitmer Date 2012-01-19 Time 10:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-11-28 Cont ID  
Sent By jwitmer Date 2011-11-28 Time 08:28 Rev Time 1.10
Received By jwitmer Date 2011-11-28 Time 08:28 Sent To  
Notes
2011-11-22 16:40:44BUILDING PLAN REVIEW
 PERMIT: 11090261
 ADD: 3654 GEORGIA AVE
 CONT: PRINCE DEVELOPMENT
 TEL: (561)828-0434
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A1 INDICATES ANEW RECESSED EXTERIOR DOOR,
 CONTRACTOR WILL NEED TO SUBMIT THE EXTERIOR DOOR
 PRODUCT APPROVAL TO THE DESIGNER OF RECORD FOR REVIEW
 AS PER:
 WEST PALM BEACH ADMINISTRATIVE CODE CHAPTER 1 2007/09
 FBC-B, 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) 2007/09 FBC-B 1603.1.4 (5) WIND DESIGN CRITERIA:
 PRESSURES FOR COMPONENTS AND CLADDING .
  
 3) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-04 Cont ID  
Sent By jwitmer Date 2011-10-04 Time 01:32 Rev Time 3.00
Received By jwitmer Date 2011-10-04 Time 10:32 Sent To  
Notes
2011-10-04 13:22:14BUILDING PLAN REVIEW
 PERMIT: 11090261
 ADD: 3654 GEORGIA AVE
 CONT: PRINCE DEVELOPMENT GROUP
 TEL: (561)313-2818
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW A DISCREPANCY IN PLANS, SHEET A.01
 BUILDING CODE SUMMARY INDICATES THE BUILDING AS A TYPE
 IIB UNPROTECTED/ NON-SPRIKLERED BUILDING, WHERE AS
 SHEET S1 INDICATES THE USE OF 2X WOOD JOIST FRAMING
 MEMEBERS. FBC-B 603.1.1 WILL NOT ALLOW THE USAGE OF ANY
 COMBUSTIBLE WOOD FLOOR JOIST, IT APPEARS THIS BUILDING
 WILL NEED TO BE RECLASSIFIED AND WILL NEED TO INDICATE
 TYPE OF BUILDING TYPE AND ALLOWABLE FRONTAGE INCREASES
 (FBC-B 506.2) TO QUALIFY FOR 29,026 SQ FT FOR THE FIRST
 FLOOR.
  
 2) PLEASE REVIEW SHEET A0.2 THE FIRST FLOOR LOCATION
 FOR THE ACCESSIBLE LIFT INDICATES THIS AREA TO BE A
 EXISTING TEST KITCHEN. FBC-B 1014.2 (1) EGRESS SHALL
 NOT PASS THROUGH KITCHENS OR SIMILAR PURPOSES. PERMIT #
 06100214 FOR 3624 GEORGIA AVE WERE FOR TOOJAY'S TEST
 KITCHEN SHEET A0.0 INDICATES THIS TO BE A TRAINING
 FACILITY WITH A SEATING AREA AS WELL, NOT JUST A
 KITCHEN, IT IS IMPORTANT TO NOTE ON THE PLANS THE
 LOCATION OF LIFT IS IN THE CUSTOMER SEATING AREA OF THE
 TRAINING FACILITY. PLEASE UPDATE THE PLAN TO REFLECT
 THE
 LIFT IS NOT ACTUALLY LOCATED IN A KITCHEN AS THE USAGE
 OF THIS AREA HAS NOT DEVIATED FROM WHAT WAS ORIGINALLY
 PERMITED.
  
 3) AREA OF RESCUE ASSISTANCE WILL NEED TO COMPLY WITH:
 3A) 11-4.3.11.4 TWO-WAY COMMUNICATION. A METHOD OF
 TWO-WAY COMMUNICATION, WITH BOTH VISIBLE AND AUDIBLE
 SIGNALS, SHALL BE PROVIDED BETWEEN EACH AREA OF RESCUE
 ASSISTANCE AND THE PRIMARY ENTRY. THE FIRE DEPARTMENT
 OR APPROPRIATE LOCAL AUTHORITY MAY APPROVE A LOCATION
 OTHER THAN THE PRIMARY ENTRY.
  
 3B) 11-4.3.11.5 IDENTIFICATION. EACH AREA OF RESCUE
 ASSISTANCE SHALL BE IDENTIFIED BY A SIGN, WHICH STATES
 "AREA OF RESCUE ASSISTANCE" AND DISPLAYS THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE SIGN SHALL
 BE ILLUMINATED WHEN EXIT SIGN ILLUMINATION IS REQUIRED.
 SIGNAGE SHALL ALSO BE INSTALLED AT ALL INACCESSIBLE
 EXITS AND WHERE OTHERWISE NECESSARY TO CLEARLY INDICATE
 THE DIRECTION TO AREAS OF RESCUE ASSISTANCE. IN EACH
 AREA OF RESCUE ASSISTANCE, INSTRUCTIONS ON THE USE OF
 THE AREA UNDER EMERGENCY CONDITIONS SHALL BE POSTED
 ADJOINING THE TWO-WAY COMMUNICATION SYSTEM.
  
 4) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 5) SHEET M-1 PLANS INDICATE DUCT PENETRATING 1 HR FIRE
 RATED WALLS (STAIRWELL) PROVIDE COMPLIANCE WITH SECTION
 FBC-B 712.3.3 DUCTS AND AIR TRANSFER OPENINGS.
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS
 THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH
 SECTIONS 712.2 THROUGH 712.3.1. DUCTS AND AIR TRANSFER
 OPENINGS THAT ARE PROTECTED WITH DAMPERS SHALL COMPLY
 WITH SECTION 716.
  
 716.4 ACCESS AND IDENTIFICATION. FIRE AND SMOKE DAMPERS
 SHALL BE PROVIDED WITH AN APPROVED MEANS OF ACCESS,
 WHICH IS LARGE ENOUGH TO PERMIT INSPECTION AND
 MAINTENANCE OF THE DAMPER AND ITS OPERATING PARTS. THE
 ACCESS SHALL NOT AFFECT THE INTEGRITY OF
 FIRE-RESISTANCE-RATED ASSEMBLIES. THE ACCESS OPENINGS
 SHALL NOT REDUCE THE FIRE-RESISTANCE RATING OF THE
 ASSEMBLY. ACCESS POINTS SHALL BE PERMANENTLY IDENTIFIED
 ON THE EXTERIOR BY A LABEL HAVING LETTERS NOT LESS THAN
 0.5 INCH (12.7 MM) IN HEIGHT READING: FIRE/SMOKE
 DAMPER, SMOKE DAMPER OR FIRE DAMPER. ACCESS DOORS IN
 DUCTS SHALL BE TIGHT FITTING AND SUITABLE FOR THE
 REQUIRED DUCT CONSTRUCTION.
  
 716.5 WHERE REQUIRED. FIRE DAMPERS, SMOKE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION
 DAMPERS SHALL BE PROVIDED AT THE LOCATIONS PRESCRIBED
 IN SECTIONS 716.5.1 THROUGH 716.5.5 AND SECTION 716.6.
 WHERE AN ASSEMBLY IS REQUIRED TO HAVE BOTH FIRE DAMPERS
 AND SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS OR A
 FIRE DAMPER AND A SMOKE DAMPER SHALL BE REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-11-15 Cont ID  
Sent By rlecky Date 2011-11-15 Time 13:59 Rev Time 0.00
Received By rlecky Date 2011-11-15 Time 13:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-03 Cont ID  
Sent By rlecky Date 2011-10-03 Time 16:35 Rev Time 0.00
Received By rlecky Date 2011-10-03 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-01-25 Cont ID  
Sent By wjolin Date 2012-01-25 Time 12:52 Rev Time 0.00
Received By wjolin Date 2012-01-25 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-11-28 Cont ID  
Sent By wjolin Date 2011-11-28 Time 12:00 Rev Time 0.00
Received By wjolin Date 2011-11-28 Time 10:52 Sent To  
Notes
2011-11-28 12:00:073654 GEORGIA AVENUE
 PERMIT #11090261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION PLANS DO NOT INDICATE ANY SCOPE ASSOCIATED
 WITH THE EXISTING SECOND FLOOR/MEZZANINE AREA THAT WAS
 SHOWN ON THE ORIGINAL PERMIT APPLICATION DRAWINGS.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2006. CONFIRM EXISTING
 PARTITION (SEPARATING THE BUSINESS OCCUPANCY FROM THE
 FACTORY OCCUPANCY) IS A TWO-HOUR FIRE RATED SEPARATION.
  
 SHEET A0.1 INDICATES THE EXTERIOR DOOR ADJACENT TO
 OFFICE #140 IS NOT AN EXIT. SHEET E-1 INDICATES THIS
 DOOR IS AN EXIT.
  
 SHEET A1.1 REFLECTED CEILING PLAN GENERAL NOTE #4
 INDICATES THE BUILDING IS PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-03 Cont ID  
Sent By wjolin Date 2011-10-03 Time 14:32 Rev Time 0.00
Received By wjolin Date 2011-10-03 Time 11:25 Sent To  
Notes
2011-10-03 14:32:013654 GEORGIA AVENUE
 PERMIT #11090261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A0.1 INDICATES THIS BUILDING IS TYPE IIB
 CONSTRUCTION; HOWEVER, SHEET S1 INDICATES THE SECOND
 FLOOR IS CONSTRUCTED OF WOODEN JOISTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 STAIR DISCHARGES INSIDE THE BUILDING AT OFFICE #121.
 EXITS SHALL TERMINATE DIRECTLY TO THE EXTERIOR UNLESS
 THE DESIGN MEETS THE CRITERIA STATED IN SECTION 7.7 OF
 THE LIFE SAFETY CODE - NFPA 101 FLORIDA EDITION.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 SHEET M -1: NO FIRE DAMPERS PROVIDED IN DUCTWORK
 PENETRATING FIRE RATED STAIR ENCLOSURES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-01-25 Cont ID  
Sent By wjolin Date 2012-01-25 Time 12:52 Rev Time 0.00
Received By wjolin Date 2012-01-06 Time 08:26 Sent To  
Notes
2012-01-09 08:27:08C26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-19 Cont ID  
Sent By shill Date 2011-12-16 Time 11:57 Rev Time 0.00
Received By shill Date 2011-11-09 Time 10:53 Sent To  
Notes
2011-11-09 10:54:00C4
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-09 Cont ID  
Sent By shill Date 2011-10-13 Time 10:52 Rev Time 0.00
Received By shill Date 2011-09-12 Time 16:25 Sent To  
Notes
2011-11-09 10:52:34PULLED FROM REVIEW - SEE FRONT SCREEN NOTES
  
2011-09-12 16:25:59C17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-17 Cont ID  
Sent By hmoser Date 2011-11-17 Time 12:12 Rev Time 0.00
Received By hmoser Date 2011-11-17 Time 08:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-12-01 Cont ID  
Sent By lwagner Date 2011-12-01 Time 09:58 Rev Time 0.00
Received By lwagner Date 2011-12-01 Time 09:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-12-16 Cont ID  
Sent By astelly Date 2011-12-16 Time 14:37 Rev Time 0.00
Received By astelly Date 2011-12-16 Time 14:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-10-01 Cont ID  
Sent By astelly Date 2011-10-01 Time 11:32 Rev Time 0.00
Received By astelly Date 2011-10-01 Time 11:32 Sent To  
Notes
2011-10-01 11:37:01AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SURVEY FOR THE PROPERTY. IT APPEASR AS
 IF THE EXIT DOOR MAY SWING INTO THE RIGHT-OF WAY.