Plan Review Details - Permit 11090245
Plan Review Stops For Permit 11090245
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-27 Cont ID  
Sent By rlecky Date 2012-02-27 Time 09:24 Rev Time 0.00
Received By rlecky Date 2012-02-27 Time 09:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-22 Cont ID  
Sent By rlecky Date 2011-09-22 Time 08:35 Rev Time 0.00
Received By rlecky Date 2011-09-22 Time 08:35 Sent To  
Notes
2011-09-22 08:59:0611090245
 1554 PALM BEACH LAKES
 SIGN REPLACEMENT
  
 A SIGNED AND SEALED ENGINEERING DETAIL IS REQUIRED FOR
 WIND LOADING. INCLUDE SPECIFIC FASTENER DETAIL FOR EACH
 LETTER. DESIGN DOCUMENT MUST REFERENCE AS A MINIMUM
 ASCE 7-05, EXPOSURE "C", 2007 FLORIDA BUILDING CODE.
 INDICATE THE WIND LOAD CAPABILITIES OF 140 MPH OR
 GREATER SPECIFIC TO THE DESIGN. FBC 1609
  
 ELECTRIC SIGNS MUST BE LISTED BY A NATIONALLY
 REGISTERED TESTING AGENCY. INDICATE ON THE PERMIT
 SUBMITTAL WHO HAS LISTED THE SIGN. NEC 110.3
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-22 Cont ID  
Sent By rlecky Date 2011-09-22 Time 08:35 Rev Time 0.00
Received By rlecky Date 2011-09-22 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-22 Cont ID  
Sent By rlecky Date 2011-09-22 Time 08:35 Rev Time 0.00
Received By rlecky Date 2011-09-12 Time 13:50 Sent To  
Notes
2011-09-12 13:50:46TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-09-21 Cont ID  
Sent By eschneid Date 2011-09-21 Time 14:03 Rev Time 0.25
Received By eschneid Date 2011-09-13 Time 14:16 Sent To E
Notes
***NONE***